Campbell Scientific 03002 03002, 03101, and 03301 R. M. Young Wind Sentry Sens
Campbell Scientific 03002 Manual
View all Campbell Scientific 03002 manuals
Add to My Manuals
Save this manual to your list of manuals |
Campbell Scientific 03002 manual content summary:
- Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 1
03002 R.M. Young Wind Sentry Set 03101 R.M. Young Wind Sentry Anemometer 03301 R.M. Young Wind Sentry Vane Revision: 9/13 Copyright © 1986-2013 Campbell Scientific, Inc. - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 2
- Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 3
BY CAMPBELL SCIENTIFIC, INC. are warranted by Campbell Scientific, Inc. ("Campbell") to be free from defects in materials and workmanship under normal use and service for twelve (12) months from date of shipment unless otherwise specified in the corresponding Campbell pricelist or product manual - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 4
problem, an RMA number will be issued. Please write this number clearly on the outside of the shipping container. Campbell Scientific's shipping address is: CAMPBELL SCIENTIFIC customer at the customer's expense. Campbell Scientific reserves the right to refuse service on products that were exposed - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 5
Siting ...9 7.2 Assembly and Mounting 10 7.2.1 03002 Wind Sentry Set 10 7.2.2 03101 Anemometer 10 7.2.3 03301 Vane 11 7.3 Wiring 11 7.4 Programming 13 7.4.1 Wind Speed 13 7.4.2 Wind Direction 13 7.4.3 Wind Vector Processing Instruction 14 7.4.4 Example Programs 14 7.4.4.1 CR1000 Program - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 6
Table of Contents 9. Troubleshooting 18 9.1 Wind Direction 18 9.2 Wind Speed 18 10. References 19 Appendices A. Wind Direction Sensor Orientation A-1 A.1 Determining True North and Sensor Orientation A-1 B. Wind Direction Measurement Theory B-1 B.1 BRHalf Instruction B-1 B.2 EX-DEL-SE (P4) - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 7
. However, this jacket will support combustion in air. It is 03002, inspect the packaging and contents for damage. File damage claims with the shipping company. Immediately check package contents against the shipping documentation (see Section 3.1, Ships With List). Contact Campbell Scientific - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 8
A) • small screw driver provided with datalogger • UV resistant cable ties • small pair of diagonal-cutting pliers • 6 - 10" torpedo level Install the 03002 using: • Standard 1.0-in. IPS schedule 40 pipe (pn 3659) • CM220 Right-Angle Mounting Kit (FIGURE 4-1 and FIGURE 4-2), or • 17953 1 x 1 inch NU - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 9
the site. 4. Secure the 12 in. aluminum pipe to the CM220 mount or 17953 NU-RAIL. The 3659 aluminum pipe is shipped with the 03002. 5. Place the 03002 on the pipe, and orient the sensor crossarm North-South with the vane to the North. 6. Tighten the mounting post band clamp. Final sensor - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 10
R.M. Young Wind Sentry Alumimum Pipe CM220 CM200-Series Crossarm FIGURE 4-2. 03002 mounted to CM200-Series Crossarm with CM220 Aluminum Pipe pn 17953 NU-RAIL CM200-Series Crossarm Cable Tie FIGURE 4-3. 03002 mounted to CM200-Series Crossarm with pn 17953 4 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 11
2 - Use SCWin Short Cut to Program Datalogger and Generate Wiring Diagram The simplest method for programming the datalogger to measure the 03002 is to use Campbell Scientific's SCWin Short Cut Program Generator. 1. Open Short Cut and click on New Program. 2. Select the Datalogger and enter the Scan - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 12
R.M. Young Wind Sentry 3. Select 03002 Wind Speed & Direction Sensor and select the right arrow (in center of screen) to add it to the list of sensors to be measured then select Next. 4. Select Wind Vector for the output and then select Finish. 6 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 13
03002 Wind Sentry Set is used to measure horizontal wind speed and direction. Wind speed is measured with a three cup anemometer. Rotation of the cup wheel produces an ac sine wave voltage with frequency proportional to wind speed. This is a special version of the 03102 built for Campbell Scientific - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 14
R.M. Young Wind Sentry The 03002's cable can terminate in: • Pigtails that connect directly to a Campbell Scientific datalogger (option -PT). • Connector that attaches to a prewired enclosure (option -PW). Refer to www.campbellsci.com/prewired-enclosures for more information. • Connector that - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 15
R.M. Young Wind Sentry Threshold: Transducer: Output: Output Frequency: Cup Wheel Diameter: Weight: 0.5 m s-1 (1.1 mph) Stationary coil, 1300 ohm nominal resistance AC sine wave signal induced by rotating magnet on cup wheel shaft 100 mV peak-to-peak at 60 rpm; 6 V peak-to-peak at 3600 rpm 1 cycle - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 16
also be mounted at the top of a CM110, CM115, or CM120 tripod with the CM216 (see FIGURE 7-1). Fits in Mast FIGURE 7-1. The CM216 allows an 03002 or 03101 to mount atop the mast of a CM110, CM115, or CM120 tripod 7.2.2 03101 Anemometer Install the cupwheel to the anemometer shaft using the Allen - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 17
it to the 03002 small crossarm. Part number 4913 pipe mount (not included with the sensor) can be used to attach the 03301 to a CM200-series crossarm (with the CM220 or pn 1049), and the mounting pipe that ships with the sensor. 7.3 Wiring Connections to Campbell Scientific dataloggers are given - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 18
R.M. Young Wind Sentry TABLE 7-1. 03002-L Wiring Color Red Black Clear White Green Blue Description Wind Spd. Signal Wind Spd. Reference Shield Wind Dir. Reference Wind Dir. Signal Wind Dir. Excitation - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 19
Set to Low Level AC, Output "Hz") Model Meters/Second Miles/Hour 03002 / 03101 M = 0.750 M = 1.677 Off = 0.2 Off = instruction. Edlog dataloggers (CR510, CR10X, CR23X) use Edlog Instruction 4-Excite, Delay (P4). Excitation voltages, range codes, and multipliers for Campbell Scientific - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 20
Wind Vector output instruction is used to process and store mean wind speed, unit vector mean wind direction, and standard deviation of the wind direction (optional) from the measured wind speed and direction values. 7.4.4 Example Programs The following programs measure the 03002 every 5 seconds - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 21
or 03101 RM Young Wind Sentry Wind Speed Sensor measurement - WS_ms: PulseCount(WS_ms,1,1,1,1,0.75,0.2) If WS_ms - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 22
If (XF) (P89) 1: 2 X Loc [ WS_ms ] 2: 4 < 3: 0.21 F 4: 30 Then Do 4: Z=F x 10^n (P30) 1: 0 F 2: 0 n, Exponent of 10 3: 2 Z Loc [ WS_ms ] 5: End (P95) ;03002 or 03301 RM Young Wind Direction Sensor measurement - WindDir: 6: Excite-Delay (SE) (P4) 1: 1 Reps 2: 5 2500 mV Slow - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 23
P4) measurement instruction should be manual. The potentiometer has a life expectancy of fifty million revolutions. As it becomes worn, the element can produce noisy signals or become nonlinear. Replace the potentiometer when the noise or nonlinearity becomes unacceptable. Contact Campbell Scientific - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 24
Troubleshooting 9.1 Wind Direction Symptom: NAN, -9999, or no change in direction 1. Check that the sensor is wired to the excitation and single-ended channel specified by the measurement instruction the 03301 and blue/red or white/red for the 03002 should vary from 1 kΩ to 11 kΩ depending on vane - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 25
of the American Association of State Climatologists: Height and Exposure Standards, for Sensors on Automated Weather Stations, vol. 9, No. 4. WMO, 1983: Guide to Meteorological Instruments and Methods of Observation, World Meteorological Organization, No. 8, 5th edition, Geneva, Switzerland. 19 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 26
R.M. Young Wind Sentry 20 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 27
number of degrees between True North and Magnetic North. The preferred method to obtain the magnetic declination for a specific site is to use a computer service offered by NOAA at www.ngdc.noaa.gov/geomag. Magnetic declination can also be obtained from a map or local airport. A general map showing - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 28
Appendix A. Wind Direction Sensor Orientation FIGURE A-1. Magnetic declination for the contiguous United States (2004) A-2 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 29
Appendix A. Wind Direction Sensor Orientation FIGURE A-2. Declination angles east of True North are subtracted from 0 to get True North FIGURE A-3. Declination angles west of True North are added to 0 to get True North A-3 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 30
Appendix A. Wind Direction Sensor Orientation A-4 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 31
operation of the 03002 with Campbell Scientific's datalogger. Rt EXCITATION VOLTAGE (Vx) Rs SIGNAL + (Vs) AZIMUTH REFERENCE EARTH GROUND CONNECTION FIGURE B-1. 03002 and 03301 potentiometer in a half bridge circuit B.1 BRHalf Instruction The BRHalf() instruction outputs a precise excitation - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 32
degrees is 352 degrees / 2500 mV = 0.1408 for the CR10X, or, 352 degrees / 5000 mV = 0.0704 for the CR23X. See Section 13.5 in the datalogger manual from more information on the bridge measurements. B-2 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 33
METEOROLOGICAL INSTRUMENTS INSTRUCTIONS WIND SENTRY MODEL 03002-5 R.M. YOUNG COMPANY 2801 AERO PARK DRIVE, TRAVERSE CITY, MICHIGAN 49686, USA TEL: (231) 946-3980 FAX: (231) 946-4772 WEB: www.youngusa.com P/N: 03002-5-90 REV: D110210 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 34
Standard bearings have light contacting seals to exclude contamination and help retain lubricant for longer service life. Cup wheel rotation produces an AC sine wave voltage signal with frequency directly it may not be practical or necessary to meet these guidelines. 03002-5-90(D) Page 1 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 35
. When anemometer and vane are mounted on the same cross arm (Model 03002), the azimuth potentiometer has been aligned at the factory such that the mounting should only be performed by a qualified instrument technician. If service facilities are not available, return the instrument to the factory - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 36
, gently push out lower bearing from above. Declaration of Conformity R. M. Young Company 2801 Aero Park Drive Traverse City, MI 49686 USA Models 03002, 03102, 03302 The undersigned hereby declares on behalf of R. M. Young Company that the above-referenced product, to which this declaration relates - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 37
CABLE & WIRING DIAGRAM 03002-5-90(D) Page 4 - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 38
GENERAL ASSEMBLY & REPLACEMENT PARTS Page 5 03002-5-90(D) - Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 39
- Campbell Scientific 03002 | 03002, 03101, and 03301 R. M. Young Wind Sentry Sens - Page 40
Centro Caribe S.A. (CSCC) 300 N Cementerio, Edificio Breller Santo Domingo, Heredia 40305 COSTA RICA www.campbellsci.cc • [email protected] Campbell Scientific Ltd. (CSL) Campbell Park 80 Hathern Road Shepshed, Loughborough LE12 9GX UNITED KINGDOM www.campbellsci.co.uk • [email protected]
03002 R.M. Young Wind Sentry Set
03101 R.M. Young Wind Sentry Anemometer
03301 R.M. Young Wind Sentry Vane
Revision: 9/13
Copyright © 1986-2013
Campbell Scientific, Inc.