Compaq 245161-B22 10842 Rack Reference Guide

Compaq 245161-B22 - 10642 42U Rack Shock Pallet Manual

Compaq 245161-B22 manual content summary:

  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 1
    HP 10842 Rack Reference Guide December 2002 (Second Edition) Part Number 284358-002
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 2
    in this document is provided "as is" without warranty of any kind and is subject to change without notice. The warranties for HP products are set forth in the express limited warranty statements accompanying such products. Nothing herein should be construed as constituting an additional warranty
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 3
    Text...ix Getting Help...x Technical Support ...x HP Website...x Authorized Reseller...xi Reader's Comments...xi Chapter 1 Overview HP 10842 Rack ...1-1 Rack Options ...1-3 Delivery Considerations 1-5 Installation Sequence Summary 1-5 Installation Service ...1-6 HP 10842 Rack Reference Guide iii
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 4
    Fixed Rails 4-6 Installing the Adjustable Fixed Rails 4-7 Preparing the Sliding Rails 4-9 Installing the Sliding Rails 4-13 Preparing the Component 4-14 Adjustable Fixed Rails 4-14 iv HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 5
    B Transportation Instructions Transportation Methods B-1 Air Transport...B-1 Land Transport ...B-2 Sea Transport ...B-2 Delivery Services...B-2 Inside Rack Delivery Service B-2 Expedited Rack Delivery Service B-3 Shipping/Delivery Considerations B-4 Index HP 10842 Rack Reference Guide v
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 6
    About This Guide This guide provides step-by-step instructions for installation and reference information for operation for the HP 10842 Rack. the presence of hazardous energy circuits or electric shock hazards. Refer all servicing to qualified personnel. WARNING: To reduce the risk of injury from
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 7
    About This Guide This symbol indicates the presence of electric shock hazards. The area contains no user or field serviceable parts. Do not open for any reason. WARNING: occupational health and safety requirements and guidelines for manual material handling. viii HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 8
    extended for any reason. Symbols in Text These symbols may be found in the text of this guide. They have the following meanings. WARNING: Text set off in this manner indicates that failure to information to emphasize or supplement important points of the main text. HP 10842 Rack Reference Guide ix
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 9
    Getting Help If you have a problem and have exhausted the information in this guide, you can get further information and other help in the following locations. Technical Support In North America, call the HP Technical Support Phone Center at 1-800-652-6672. This service is available 24 hours a day
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 10
    reseller: • In the United States, call 1-800-345-1518. • In Canada, call 1-800-263-5868. • Elsewhere, see the HP website for locations and telephone numbers. Reader's Comments HP welcomes your comments on this guide. Please send your comments and suggestions by e-mail to ServerDocumentation
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 11
    using U measurements. For example, one U is 44.45 mm (1.75 inches) high. HP 10842 Rack The HP 10842 rack is a 800 x 1000 mm 42U rack that arrives in a server/storage configuration that allows routing and cable management • Perforated rack top with egress slot HP 10842 Rack Reference Guide 1-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 12
    the switching devices to be mounted on both front and rear sets of internal mounting rails. Figure 1-1: 10842 rack Figure 1-2: Dual-opening perforated rear doors 1-2 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 13
    sampling of the many rack option kits available. For more information, refer to the HP website, www.hp.com. Table 1-1: Rack Options Option Side Panels Rack Option Kit Stabilizer Rack Option Kit multiple servers Routes and organizes cables within the rack continued HP 10842 Rack Reference Guide 1-3
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 14
    complete information about these products, see the HP website, www.hp.com. Contact the nearest HP authorized reseller or service provider for information about ordering rack option kits. For the name of the nearest HP authorized reseller, refer to "About This Guide." 1-4 HP 10842 Rack Reference
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 15
    delivery considerations available. For more information, visit the Best Practices Web page at www.hp.com. When preparing to receive palletized racks, consider the following: • The dock door Power Distribution Units (PDUs) or switch boxes in sidewall locations. HP 10842 Rack Reference Guide 1-5
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 16
    by qualified guaranteed service providers. This installation service covers the entire hardware installation sequence, from unpacking the components to cable routing and running a test of the system. For more information on HP support, refer to "About This Guide." 1-6 HP 10842 Rack Reference
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 17
    rack. Rack Configuration Software To help you plan your rack configuration more efficiently, HP provides Rack Builder Online, the browser-based rack configuration tool. The latest version you select the individual devices that are required for your configuration HP 10842 Rack Reference Guide 2-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 18
    rack configuration labeling and rack suite graphics for configurations that include multiple racks • Third-Party Support-Allows you to define and add third-party products If you are planning a new rack, Online for installation and use of the software features. 2-2 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 19
    UPS is installed, do not exceed its output rating. Be sure to review the installation instructions provided with each component for important cautions and warnings. • PDUs-Install PDUs before installing prior installation of a 1U Keyboard Drawer Rack Option Kit. HP 10842 Rack Reference Guide 2-3
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 20
    rated (CL2P) cable, please contact your local HP authorized reseller to obtain the following options: • 149363-B21-20-foot (609.6-cm) plenum cable • 149364-B21-40-foot (1219.2-cm) plenum cable • . • Stabilizing Feet-A stand-alone rack requires stabilizing feet. 2-4 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 21
    . • At least 38 cm (15 inches) of clearance is needed around a power supply to facilitate servicing. Power Requirements WARNING: To reduce the risk of personal injury, fire, or damage to the equipment, 80 percent of the marked electrical current rating of the UPS. HP 10842 Rack Reference Guide 2-5
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 22
    a grounded (earthed) power outlet that is easily accessible and located as close as possible to the equipment. The grounding plug is an important safety feature. 2-6 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 23
    -ventilated, climate-controlled environment. The HP Maximum Recommended Ambient Operating Temperature (TMRA Equipment Included HP rack-mountable servers HP rack-mountable options HP PDUs Other manufacturers temperature beyond the maximum rating specified by HP. • Make sure that the manufacturer's
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 24
    Configuration Factors Airflow Requirements HP rack-mountable products typically draw in cool air through the front and exhaust warm air out through cause changes in the airflow that adversely affect cooling within the rack. Cover these gaps with blanking panels. 2-8 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 25
    : • Required tools • Checking the hardware • Removing the rack doors • Removing the side panels • Stabilizing the rack - Standalone racks - Multiple racks • Server/storage vs. switching configurations HP 10842 Rack Reference Guide 3-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 26
    battery-powered screwdrivers. Checking the Hardware After unpacking the rack and its components, locate the HP Rack Kit Components List that was shipped with your rack. Be sure that you received component installation. Retain the extra fasteners for future use. 3-2 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 27
    handle release button down (2) until the handle pops out. 2. Lift the handle up and out to open the door (3). 3 1 2 Figure 3-1: Opening the rack front door HP 10842 Rack Reference Guide 3-3
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 28
    the bottom hinge bracket. Store the front door in an upright position, taking care to protect it from damage. 2 1 Figure 3-2: Removing the rack front door 3-4 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 29
    Preparing the Rack To remove the rack rear doors: 1. Rotate the rack rear door handle to the right (1). 2. Pull the rack rear door handle to open the rack rear doors (2). 1 2 Figure 3-3: Opening the rack rear doors HP 10842 Rack Reference Guide 3-5
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 30
    them from the rack (2). Store the rear doors in an upright position, taking care to protect them from damage. 2 1 1 Figure 3-4: Removing the rack rear doors 3-6 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 31
    panel from the rack (3). Store the side panels in an upright position, taking care to protect them from damage. 2 1 3 Figure 3-5: Removing the rack side panels Instructions for replacing the side panels are given in Side Panel Rack Option Kit Installation
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 32
    you must follow these instructions carefully and heed all cautions and warnings throughout the installation instructions. Standalone Racks If in leveling feet bases provided with your rack. These feet support the rack and help compensate for uneven surfaces. After HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 33
    to each side of the rack. Stabilizing feet are not required on the back of a standalone rack. Figure 3-6: Full-size stabilizing feet attached (top view) HP 10842 Rack Reference Guide 3-9
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 34
    /storage configuration with internal mounting rails that are front-justified, providing the customer greater room in the rear of the rack for cable routing. 3-10 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 35
    topics: • General guidelines • Component installation overview • Using the template • Installing the cage nuts • Preparing and installing rack-mountable rails • Preparing the component • Installing the component HP 10842 Rack Reference Guide 4-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 36
    equipment installed does not impede airflow to the rack-mountable ProLiant servers or increase the internal rack temperature beyond the maximum rating specified by HP. • Be sure that the option equipment installed does not exceed the manufacturer's Maximum Recommended Ambient Operating Temperature
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 37
    installation and service. Component Installation Overview NOTE: The stabilizer feet should be installed before any component installation. IMPORTANT: The following installation instructions are for the cable management arm to the rack and then to the component. HP 10842 Rack Reference Guide 4-3
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 38
    sure that you adhere to all cautions and warnings contained in the individual component installation instructions. 8. Remove the cable access panel and route the cables (using the conduit if the front mounting rails. Figure 4-1: Measuring with the template 4-4 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 39
    top lip of the cage nut. 3. Pull the cage nut through the hole until the top lip snaps into position. Figure 4-2: Installing the cage nuts HP 10842 Rack Reference Guide 4-5
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 40
    -Mountable Rails IMPORTANT: The installation instructions in this section are for standard installations. For specific installation instructions, please refer to the documentation the wing nuts slightly to stabilize the rail-mounting brackets during installation. 4-6 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 41
    fixed rail to the front of the rack. NOTE: After installing your components, insert at least one more screw into each adjustable rail for additional support. Figure 4-4: Securing the adjustable fixed rails to the front of the rack
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 42
    rail to the rear of the rack. NOTE: After installing your components, insert at least one more screw into each adjustable rail for additional support. Figure 4-5: Securing the adjustable fixed rails to the rear of the rack 3. Retighten the wing nuts on the adjustable fixed rails. The adjustable
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 43
    attach the component rails to the component before you insert the unit into the rack. 2 1 Figure 4-6: Removing the component rails from the sliding rail assembly HP 10842 Rack Reference Guide 4-9
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 44
    rack-mounting brackets: a. The front flange (1) has alignment tabs. b. The back flange (2) is designed to install flush against the rack. 1 2 Figure 4-7: Rack-mounting brackets 4-10 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 45
    front of the sliding rail assembly. 6. Adjust the inner slide until you can access another screw hole (2) and insert one 8-32 x 3/8 screw. (Refer to Figure 4-9.) HP 10842 Rack Reference Guide 4-11
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 46
    rail assembly to the rack-mounting brackets. Repeat the steps 4 through 7 for the other sliding rail. The sliding rails are now ready for installation. 4-12 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 47
    on the front of the sliding rails help you align them correctly with the mounting rails. Figure 4-10: Securing the front of the sliding rails HP 10842 Rack Reference Guide 4-13
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 48
    of the sliding rails Preparing the Component This section contains general instructions for preparing a typical rack-mountable component for installation. Refer documentation that ships with each component for complete installation instructions. Adjustable Fixed Rails If the component mounts with
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 49
    assemblies. 2. Use three 8-32 x 3/8 screws to install each component rail on the side of the component. Figure 4-12: Attaching the component rails to the component HP 10842 Rack Reference Guide 4-15
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 50
    in the Rack Cable Management Arm Bracket If the component uses a cable management arm, use two 6-32 x ¼ screws to attach the bracket that supports the cable management arm. NOTE: The cable management arm is installed after the component is installed into the rack. Figure 4-13: Attaching the cable
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 51
    health and safety requirements and guidelines for manual material handling. • Get help to lift rack with adjustable fixed rails: With the unit well supported, lift the component up and slide it into place rails. 2. With the unit well supported, lift it up and align the component rails on the
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 52
    the component into the rack 4. Using the cage nuts, tighten the thumbscrews on the front of the unit to secure it to the rack. 4-18 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 53
    screws to attach the cable management arm to the bracket you installed on the component. Figure 4-15: Attaching the cable management arm to the bracket HP 10842 Rack Reference Guide 4-19
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 54
    stay untangled. Figure 4-16: Attaching the cable management arm to the rack 4. Secure any cables that you connect to the component to this arm. 4-20 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 55
    voltage selection switch to the appropriate position. c. Connect the AC power cord to the unit. Figure 4-17: Connecting the AC power cord to the component HP 10842 Rack Reference Guide 4-21
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 56
    cables over the top of the cable management arm and down the conduit, if present. Figure 4-18: Routing the cables for server/storage applications 4-22 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 57
    from the hinge bracket (4). Store the panel in an upright position, taking care to protect it from damage. 3 1 3 4 2 Figure 4-19: Removing the cable access panel HP 10842 Rack Reference Guide 4-23
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 58
    Unit (PDU). NOTE: If you are not using a PDU, route the power cord directly to a properly rated and grounded AC wall or floor outlet. 4-24 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 59
    .4 inches) 1219 mm (48 inches) 985 mm (38.8 inches) 115 kg (253 lbs) 148 kg (325 lbs) 907 kg (2000 lbs) 454 kg (1000 lbs) HP 10842 Rack Reference Guide 5-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 60
    a grounded surface before removing them from their containers. • Avoid touching pins, leads, or circuitry. • Always be properly grounded when touching a static-sensitive component or assembly. HP 10842 Rack Reference Guide A-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 61
    field service kit with a folding static-dissipating work mat. If you do not have any of the suggested equipment for proper grounding, have HP authorized reseller install the part NOTE: For more information on static electricity, or assistance with product installation, contact your HP authorized
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 62
    Transportation Instructions NOTE: The following section is only a sampling of the many delivery considerations available. For more information, visit the Best Practices Web page at www.hp. prepare them for delivery, or choose an alternative transportation method. HP 10842 Series Reference Guide B-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 63
    Transportation Instructions Because of them. Delivery Services HP provides two methods of delivery for customers in North America: Inside Rack Delivery Service and Expedited Rack Delivery Service. If Transportation personnel provide material-handling equipment. B-2 HP 10842 Series Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 64
    Transportation Instructions • The rack is delivered to the desired location within the facility (see "Limitations"). • Delivery service is service is available only in the continental United States, Alaska, and Hawaii. • Inside rack delivery is not included. HP 10842 Series Reference Guide B-3 HP
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 65
    Transportation Instructions Shipping/Delivery Considerations The following precautions should be observed when receiving the racks and components. • A dock . Ideally, the palletized rack should be moved to its final destination and then removed from the pallet. B-4 HP 10842 Series Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 66
    arm 4-19 cables 4-21 power cords 4-21 authorized reseller xi authorized, service provider 1-6 B balance considerations 2-3 ballast rack option kit 1-3 baying offset rack installing 4-5 clearance around the rack 2-5 between wall and rack 4-3 to unpack 2-5 HP 10842 Rack Reference Guide Index-1
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 67
    storing products A-1 transporting products A-1 types of damage from A-1 expedited delivery service B-3 F fan rack option kit 1-3 features 10842 Rack 1-1 Rack A-2 guidelines for component installation 4-3 H hardware shipped with rack 3-2 heel straps, using A-2 Index-2 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 68
    HP authorized service provider 1-4 HP Maximum Recommended Ambient Operating Temperature 2-7 HP website x I inside delivery service B-2 installation overview of 4-3 service Me Build It Mode, Rack Builer Online 2-1 HP 10842 Rack Reference Guide Index M marking with the template 4-4 Maximum Recommended
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 69
    front door 3-3 rear doors 3-5 side panels 3-7 replacing side panels 3-7 reports, Rack Builder Online 2-2 requirements blanking panels 1-4 environment 2-5 grounding 2-6 power 2-5 temperature 2-7 wiring 2-4 routing, cables 4-22 Index-4 HP 10842 Rack Reference Guide
  • Compaq 245161-B22 | 10842 Rack Reference Guide - Page 70
    required parts 2-4 server/storage vs. switching 3-10 service for installing racks 1-6 shipping by air B-1 by damage to A-1 T technical support x telephone numbers x, xi HP x weight considerations 2-3 wiring requirements 2-4 wrist straps specifications A-2 using A-2 HP 10842 Rack Reference Guide
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70

HP 10842 Rack
Reference Guide
December 2002 (Second Edition)
Part Number 284358-002