Compaq R6000 HP UPS Best Practices

Compaq R6000 - UPS - Lead Acid Expandable Manual

Compaq R6000 manual content summary:

  • Compaq R6000 | HP UPS Best Practices - Page 1
    Recommended Duration of Use...2 Battery Replacement ...3 Select Load UPS ...10 HP Three-phase Rack-mountable UPS 11 HP Tower UPS Advantages...12 HP Tower UPS 18 Worldwide Power Requirements 19 UPS/PDU services are set forth in the express warranty statements accompanying such products and services
  • Compaq R6000 | HP UPS Best Practices - Page 2
    o Software error (14%) o Human error (32%) o Hardware failure (44%), often triggered by power problems  According to Price Waterhouse research, after a power outage disrupts IT systems: o More than 33% of companies require more than one day to recover o 10% of companies take more than one week o It
  • Compaq R6000 | HP UPS Best Practices - Page 3
    example, at a 40ºC (104ºF) ambient, battery life is reduced approximately 70 percent from what would be expected at 25ºC (77ºF). Even when the UPS is in use and the batteries are fully charged, higher ambient conditions will reduce "float" service life. Battery rule ability to support a help requires
  • Compaq R6000 | HP UPS Best Practices - Page 4
    Graceful Shutdown In addition to providing an excellent USB, Serial or Web enable management capability equipment. Instead, the UPS will run until the batteries are depleted and then drop the attached load. Used loss, HP Power Management Software also helps users stay informed with UPS alarms sent
  • Compaq R6000 | HP UPS Best Practices - Page 5
    located Data Centers Provide access to multiple users Include a web interface management software that can be accessed with a web browser Include a Service Menu, a text-based menu that can be accessed through telnet or hyperterminal emulation session Use HP Management Module Software version 2.0 or
  • Compaq R6000 | HP UPS Best Practices - Page 6
    as industry-leading power density and more true power in a smaller form factor, HP rackmount UPSs deliver maximum uptime with a host of competitive advantages including: Enhanced Battery Management (EBM)  Doubles battery service life  Provides the fastest, safest recharge time  Provides up to 60
  • Compaq R6000 | HP UPS Best Practices - Page 7
    delivers an unprecedented 2700 watts in a 2U form factor. The R5500 model features an impressive 1500 support either a single UPS configuration or provides additional power protection with support system downtime  HP pre-failure warranty replaces batteries free of charge within 3-year period 
  • Compaq R6000 | HP UPS Best Practices - Page 8
    environments. Offering 1500VA/1050Watts of protection, the R1500 G2 occupies just 1U of valuable rack space, while delivering key benefits such as Enhanced Battery Management, Load Segment Control, and serial and USB ports for data exchange. HP R3000 Rackmount UPS The HP R3000 UPS is a high power
  • Compaq R6000 | HP UPS Best Practices - Page 9
    Conversion Kit for non rack applications outside the data center or to support multiple tower servers, wiring closets, and blade enclosures such as the HP c3000 BladeSystem. An industry leading 3 year warranty and enhanced battery management with pre-failure warning insures that the HP R/T3000
  • Compaq R6000 | HP UPS Best Practices - Page 10
    extra-long battery life with Enhanced Battery Management (EBM); longer runtime with Digital Signal Processing technology (DSP); extended battery runtime with optional Extended Runtime Modules (now supports up to 4 ERMs with FW version 2.08 or higher); and easy serviceability with hot-swappable
  • Compaq R6000 | HP UPS Best Practices - Page 11
    the power density of any comparable product on the market. Furthermore, the scalable design of the UPS helps customers meet the changing demands of their data centers, as it can expand from the RP36KW model to 12kVA/12kW modules allow upgrade up to a 60kVA/60kW n+1 configuration) Page 11 of 27
  • Compaq R6000 | HP UPS Best Practices - Page 12
    ensure all data is saved during an extended blackout  Serial and USB ports for data exchange with the host computer  Hot-swappable batteries for simplified service without powering down the UPS  Power Management Software o Bundled free with every UPS, the software allows easy UPS management and
  • Compaq R6000 | HP UPS Best Practices - Page 13
    for small and medium businesses and desktop/workstation environments with power requirements of 750VA/500 watts and less, the HP T750 G2 increased power rating, intuitive front panel display, hot-swappable batteries and prioritized shutdown using bundled HP Power Manager management software.
  • Compaq R6000 | HP UPS Best Practices - Page 14
    , Watts 335 670 T1500 G3 and T1500 Japan Load, percent 50% 100% Load, Watts 475 950 R3000 Load, percent 20% 50% 80% 100% With Standby Battery 40 minutes 12 minutes 6.5 minutes 5 minutes R/T3000 Low Volt Models Load, percent 20% 50% 80% 100% With Standby
  • Compaq R6000 | HP UPS Best Practices - Page 15
    /4950 6 minutes *6000/5400 5 minutes * International model only. †Requires firmware v2.08 or higher With 1 ERM 160 minutes 75 minutes 62 minutes Load per R8000/3 kW % 1.6 20% 2.4 30% 4 50% 6 75% 8 100% Battery Runtime Chart Internal +1 ERM +2 ERM +3 ERM +4 ERM 55 118 183 253 329 37 78
  • Compaq R6000 | HP UPS Best Practices - Page 16
    Rack Height Three Phase Modular 8.6 kVA PDU AF432A R8000/3 INTL AF504A AF513A AF508A Three Phase Monitored 8.6 kVA Single Input Full Rack Height Three Phase Modular 11 kVA PDU Three Phase Monitored 11 kVA Single Input Full Rack Height Page 16 of 27
  • Compaq R6000 | HP UPS Best Practices - Page 17
    Three Phase Monitored 8.6 kVA Single Input Full Rack Height Three Phase Monitored 17.3 kVA Dual Input Full Rack Height Three Phase Modular 11 kVA PDU Three Phase Monitored 11 kVA Single Input Full Rack Height Three Phase Monitored 22.1 kVA Dual Input Full Rack Height Three Phase Modular 8.6 kVA PDU
  • Compaq R6000 | HP UPS Best Practices - Page 18
    has a required time for shutdown, which must be taken into account when configuring the UPS software so sufficient battery life is to your Owner's Manual for further instructions. 3. Installing Extended Runtime Modules (ERMs) Depending on the UPS model, you may need to manually inform the UPS when
  • Compaq R6000 | HP UPS Best Practices - Page 19
    equivalent of a REPO signal being sent to the UPS. Please refer to the users guide detailed installation instructions. 8. R12000/3 and A-B-C clockwise phase rotation The HP three phase UPS require A-B-C clockwise phase rotation for the input wiring. The unit detects and reports this Phase Rotation
  • Compaq R6000 | HP UPS Best Practices - Page 20
    Page 20 of 27
  • Compaq R6000 | HP UPS Best Practices - Page 21
    Page 21 of 27
  • Compaq R6000 | HP UPS Best Practices - Page 22
    Low Voltage NEMA L5-30P Output receptacles LS 1 -1 - L5-30R LS 2 - 3 - NEMA 5-15R LS 3 - 3 - NEMA 5-15R HP R3000 high voltage UPS NA/JPN Part number: AF423A / AF424A Input plug type High Voltage NEMA L6-20P Output receptacles LS 1 - 1 - L6-20R/ LS 1 - 3 - IEC320 C-13 LS 2 - 3 - IEC320 C-13 LS
  • Compaq R6000 | HP UPS Best Practices - Page 23
    LS 2 - 1 - IEC320-C19 HP R5500 high voltage UPS NA/JPN Part number: AF426A Input plug type High Voltage NEMA L6-30P Output receptacles LS - IEC C-19 LS 2 - 2 - IEC C-13 HP R5500 high voltage UPS INTL Part number: AF416A Input plug type High Voltage IEC309 32A Output receptacles LS 1 - 1 L6-
  • Compaq R6000 | HP UPS Best Practices - Page 24
    L21-30P Output receptacles 1 - NEMA L15-30 HP R8000/3 high voltage UPS INTL Part number: AF432A Input plug type IEC309 516P6 (16A) Output receptacles 1 - IEC309 516C6 (16A) HP R12000/3 high voltage UPS NA Part number: AF429A Input plug type IEC 560P9 (60A) Output receptacles 2 - NEMA L15-30
  • Compaq R6000 | HP UPS Best Practices - Page 25
    HP RP36000/3 high voltage UPS NA Part number: AF438A No Photo Available Receptacles on output modules 2 - NEMA L15-30 HP RP36000/3 high voltage UPS INTL Part number: AF439A No Photo Available Receptacles on output modules 2 - IEC309 516C9 (16A) Page 25 of 27
  • Compaq R6000 | HP UPS Best Practices - Page 26
    NEMA 5-15P Output receptacles 4 - Low Voltage NEMA 5-15R HP T750 G2 UPS INTL Part number: AF447A Input receptacle type High Voltage IEC320 C14 Output receptacles 4 - High Voltage IEC320 C13 HP T750 UPS JAPAN Part number: AF456A Input plug type Low Voltage NEMA 5-15P Output receptacles 6 - Low
  • Compaq R6000 | HP UPS Best Practices - Page 27
    Voltage IEC320 C14 Output receptacles 4 - High Voltage IEC320 C13 HP T1500 UPS JAPAN Part number: AF458A Input plug type Low Voltage NEMA 5-15P Output receptacles 6 - Low Sizing: www.upssizer.com For sales and technical questions or contacts, email: [email protected] Page 27 of 27
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27

Page 1 of 27
HP UPS Best Practices
Abstract
.........................................................................................................................................
2
Introduction
...................................................................................................................................
2
The Importance of Power Protection
............................................................................................
2
Recommended Duration of Use
....................................................................................................
2
Battery Replacement
....................................................................................................................
3
Select Load Appropriately / Sizing A UPS
....................................................................................
3
Select Application Voltage / High volt VS Low Volt (120V or 208V)
.............................................
3
HP UPS Management
...................................................................................................................
4
HP Power Manager Software
....................................................................................................
4
HP Management Module (AF401A)
..........................................................................................
5
Rackmount UPS Model Numbers
.............................................................................................
6
Tower UPS Model Numbers
.....................................................................................................
6
UPS Options
.............................................................................................................................
6
HP Rackmount UPS Advantages
.................................................................................................
6
HP Rackmount UPS Models
.........................................................................................................
8
HP R1500 G2 Rackmount UPS
................................................................................................
8
HP R3000 Rackmount UPS
......................................................................................................
8
HP R/T3000 Rackmount UPS
...................................................................................................
9
HP R5500 Rackmount UPS
....................................................................................................
10
HP Three-phase Rack-mountable UPS
..................................................................................
11
HP Tower UPS Advantages
........................................................................................................
12
HP Tower UPS Models
...............................................................................................................
13
HP T750 G2 UPS
....................................................................................................................
13
HP T1000 G3 and T1500 G3 UPSs
........................................................................................
13
HP T750 Japan T1000 Japan and T1500 Japan UPSs
..........................................................
13
Run Time per HP UPS Model
.....................................................................................................
14
Recommended Power Distribution Units (PDU)
.........................................................................
16
Avoiding Potential Glitches
.........................................................................................................
18
Worldwide Power Requirements
.................................................................................................
19
UPS/PDU power cord plug/receptacle reference
........................................................................
22
Additional Information
.................................................................................................................
27
The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth
in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting
an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.