CyberPower CP825LCD Function Guide

CyberPower CP825LCD Manual

CyberPower CP825LCD manual content summary:

  • CyberPower CP825LCD | Function Guide - Page 1
    power fluctuations. If you utility service is stable, you can select Good (103V~136V). The unit will go to Battery Mode more often. Function Sensitivity Low Battery Warning High Transfer Voltage Low Transfer Voltage 136V-142V (CP600LCD/CP825LCD) 135V-144V (CP685AVRLCD/CP825AVRLCD) 140V 97V-103V
  • CyberPower CP825LCD | Function Guide - Page 2
    ) Escape to Function Menu Default L. of Description "L.on"(Auto off is on): In Line mode, LCD screen will off automatically after 1 min of inactivity; in Battery mode, LCD screen is always on. "L.off"(Auto off is off): LCD screen is always on. Last Fault Reason Back to Default Return to Status
  • 1
  • 2

1
2
FUNCTION SETUP GUIDE
The LCD display indicates a variety of UPS operational conditions. All descriptions apply when the
UPS is plugged into an AC outlet and turned on or when UPS is on battery.
K01-0000733-00
Function
LCD Display
Options
Default
Description
Output Quality
* Only when Min or MAX O/P
voltage is configured.*
Poor (86V~144V) AVR series
(91V~144V) CP-LCD
Normal (90V~140V) AVR series
(96V~140V) CP-LCD
Good (94V~135V) AVR Series
(100V~135V) CP-LCD
Escape to Function Menu
Normal
This function determines how the
UPS will switch to Battery Mode.
3 different output voltage ranges
can be chosen according to the
quality of the AC utility service in
your location.
If you utility service is not stable,
you can select Poor (97V~142V).
The UPS will go to Battery Mode
less often to tolerate the utility
power fluctuations.
If you utility service is stable, you
can select Good (103V~136V). The
unit will go to Battery Mode more
often.
High Transfer Voltage
136V-142V
(CP
600
LCD/CP825LCD)
135V-144V
(CP685AVRLCD/CP825AVRLCD)
140V
In Output Quality setting, only 3
types of fixed voltage ranges can be
chosen. However, you can fine tune
the MAX O/P voltage in this
function.
In the utility voltage is usually high,
and the connected equipment can
word in this condition, you can set
the output voltage range higher to
reduce the UPS from going to
Battery Mode as often.
Low Transfer Voltage
97V-103V
(CP6
00
LCD/CP825LCD)
95V-104V
(CP685AVRLCD/CP825AVRLCD)
100V
In Output Quality setting, only 3
types of voltage ranges can be
chosen. However, you can fine turn
the MIN O/P voltage in this
function.
If the utility voltage is usually low,
and the connected equipment can
work in this condition, you can set
the output voltage range lower to
reduce the UPS from going to AVR
Mode or Battery Mode as often.
Function
LCD Display
Options
Default
Description
Sensitivity
Low
Medium
High
Escape to Function Menu
Medium
If the connected equipment can
tolerate more power events
(Example: unstable power often
associated with stormy weather),
select Low sensitivity. The UPS will
go to Battery Mode less often. If
the connected equipment is more
sensitive to power events, select
High sensitivity. The UPS will go to
Battery Mode more often.
Low Battery Warning
5~8 mins
Escape to Function Menu
5 mins
The audible alarm will sound and
when the remaining runtime is less
than the value selected.
Self-Test
(Battery Test)
Yes
Escape to Function Menu
Medium
In Line Mode, select YES to perform
a self-test on the battery.
Buzzer
b.on
b. off
Escape to Function Menu
b. on
“b. on” is buzzer enable; “b. off” is
buzzer disable. If b. off is selected,
the unit will mute all alarm except
for fault or overload condition.
You can also set the audible alarm
with the MUTE button mentioned
before.