Fluke 1625 FE 1625 Users Manual - Page 24
RH with, Umeas = 48 V, RH with Umeas = 20 V, Resolution, electrode resistance R
View all Fluke 1625 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 24 highlights
1625 Users Manual fluencing conditions (see diagramm), the display shows a warning symbol W and a notice that RS or RH are too high. F 1000% 100% 10% 1 % 3000 1000 RH/RE= 300 100 30 10 3 1 0,3 0 ,1% 1 0 100 1 k 10k 100k 1M RS edw005.eps Automatic switchover of measuring resolution in dependence to auxiliary earth electrode resistance RH: RH with Umeas = 48 V < 300 Ω < 6 kΩ < 60 kΩ < 600 kΩ RH with Umeas = 20 V < 250 Ω < 2,5 kΩ < 25 kΩ < 250 kΩ Resolution 1 mΩ 10 mΩ 100 mΩ 1 Ω 16
1625
Users Manual
16
fluencing conditions (see diagramm), the display shows a warning symbol
W
and a notice that
RS or RH are too high.
%