Fluke 1625 FE 1625 Users Manual - Page 52

Compensation of Earth Electrode Connecting Lead, Measuring process

Page 52 highlights

1625 Users Manual Example: Your clip-on transformer has a transformation ratio of tr = 1000:1. The measurement without clip-on transformer results in a value RE = 0.983 Ω . With a clip-on transformer a value of RE = 1.175 Ω is measured. The deviation thus reads (1.175 - 0.983) Ω= + 0.192 Ω and referring to RE = 0.983 Ω an error evolves as following: 100% × 0.192Ω = +19.5% 0.983Ω The new transformation ratio to be set calculates: trnew = 1000 × 1.175 = 1195 0.983 Compensation of Earth Electrode Connecting Lead If the line resistance to the earth electrode can not be ignored, a compensation of the connecting lead resistance to the earth electrode is possible. Proceed as described below: Measuring process: START TEST 1625 EARTH / GROUND TESTER H /C2 DISPLAY MENU Earth/Ground Resistance 300 k RA CHANGE ITEM 4 POLE 3 POLE 4 POLE 3 POLE AC Resistance 300 k R DC Low Resistance 3k R 2 POLE 2 POLE 4 POLE SELECT OFF S/P2 ES/P1 E /C1 Earth electrode Auxiliary earth electrode edw019.eps Figure 15. Compensation of Earth Electrode Connecting Lead 1. Turn central rotary switch to position "RE 3pole". 2. Wire instrument according to picture. 44

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90

1625
Users Manual
44
Example:
Your clip-on transformer has a transformation ratio of tr = 1000:1. The meas-
urement without clip-on transformer results in a value R
E
= 0.983
. With a
clip-on transformer a value of R
E
= 1.175
is measured.
The deviation thus reads (1.175 - 0.983)
= + 0.192
and referring to R
E
=
0.983
an error evolves as following:
%
5
.
19
983
.
0
192
.
0
%
100
+
=
×
The new transformation ratio to be set calculates:
1195
983
.
0
175
.
1
1000
=
×
=
trnew
Compensation of Earth Electrode Connecting Lead
If the line resistance to the earth electrode can not be ignored, a compensation
of the connecting lead resistance to the earth electrode is possible. Proceed as
described below:
Measuring process:
R
RA
R
Earth/Ground Resistance 300k
AC
Resistance
300k
DC Low Resistance 3k
CHANGE
ITEM
SELECT
START
TEST
DISPLAY
MENU
H/C2
S/P2
ES/P1
E/C1
4
POLE
3
POLE
4
POLE
2
POLE
2
POLE
4
POLE
OFF
3
POLE
EARTH / GROUND TESTER
1625
Auxiliary
earth
electrode
Earth
electrode
edw019.eps
Figure 15. Compensation of Earth Electrode Connecting Lead
1.
Turn central rotary switch to position "R
E
3pole".
2.
Wire instrument according to picture.