Haier HC60C1VAR User Manual

Haier HC60C1VAR Manual

Haier HC60C1VAR manual content summary:

  • Haier HC60C1VAR | User Manual - Page 1
    Installation & Operation Manual Central Air Conditioner 10 to 13 SEER 1.5 to 5 Tons Models: HC18-60A1VAR/S HC18-60C1VAR HC18-60D1VAR No.0010572324 K The information contained in this booklet is subject to change without notice.
  • Haier HC60C1VAR | User Manual - Page 2
    adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices. Attach the service panel to the outdoor unit securely
  • Haier HC60C1VAR | User Manual - Page 3
    Troubleshooting guide 12 9.3.Wiring diagram 12 1.INTRODUCTION This manual contains the installation and operating instructions for your new air conditioner retain this manual for future reference. 2.NOMENCLATURE FOR MODEL NUMBER H Brand symbol - H: Haier C System type - C: Air conditioner; R: Heat
  • Haier HC60C1VAR | User Manual - Page 4
    in Figure 1. Physical and electrical specifications are provided in Table 1 for 10 SEER systems respectively. Table 1: Model:HC18-60A1VAR/S 2 MODEL: HC18A1VAR HC24A1VAR HC30A1VAR HC36A1VAS HC42A1VAR HC48A1VAR HC60A1VAR Unit Supply Voltage 208/230-1-60 Normal Voltage Range Compressor Brand
  • Haier HC60C1VAR | User Manual - Page 5
    2:System Cooling Capacity Figure 1 Outdoor Unit With This Indoor Air handler Model Number Air Handler Compressor Cooling Capacity (Btu/h) SEER Rated HC18A1VAR HC24A1VAR HC30A1VAR HC36A1VAS HC42A1VAR HB2400VA1M20 HB2400VA1M20 HB3000VA1M20 HB3600VA1M20 HB4200VA1M25 brand Bristol Bristol
  • Haier HC60C1VAR | User Manual - Page 6
    249 [113] 262[119] 282[128] Table 6:System Cooling Capacity Outdoor Unit Model Number HC18D1VAR HC24D1VAR HC30D1VAR HC36D1VAR HC42D1VAR HC48D1VAR HC60D1VAR With This Indoor Air handler Air Handler Compressor Cooling Capacity (Btu/h) brand Sensible Total HB2400VD1M20 Bristol 13300 18000
  • Haier HC60C1VAR | User Manual - Page 7
    to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure. attempting any installation: Structural strength of supporting members. Clearances and provision for servicing. Power supply and wiring. Location for
  • Haier HC60C1VAR | User Manual - Page 8
    cork pad. For rooftop application, make sure the building construction can support the weight and that proper consideration is given to the weather-tight such as corners provide a minimum of 10" clearance on all air inlet sides. For service access to the compressor and control box, allow 18" minimum
  • Haier HC60C1VAR | User Manual - Page 9
    to avoid capacity loss and increased operating costs. Refrigerant lines must be adequately supported. If metal strapping is used to secure the tubing, do not allow on the piping and to prevent heat gain caused by surrounding air. Generally 3/8" wall thickness of Armflex or equivalent is satisfactory
  • Haier HC60C1VAR | User Manual - Page 10
    cause personal injury. ! CAUTION - The piston is in the accessory bag. Don't forget to take it out and put into the indoor liquid pipe orifice. Instructions on the field tubing connections and valve opening procedure are as follow: 8
  • Haier HC60C1VAR | User Manual - Page 11
    getting into the system. 4.Remove the cap and Schrader valve core from the service port to protect the valve seals. 5.Wrap a wet rag around the valve gases and moisture are removed prior to charging the system. Air in a system causes high condensing pressure, which increases power consumption
  • Haier HC60C1VAR | User Manual - Page 12
    service gage manifold to the valve service ports, being sure to evacuate lines. 3.Startup the system (Refer to the Section 7 - "System Startup"). Run system at least 10 minutes to allo System Superheat Ambient Return Air the installation manual and be furnished with this instruction). Note: Some
  • Haier HC60C1VAR | User Manual - Page 13
    "Charging the System"). 7.Replace service port caps. Service port cores are for system access only and will leak if not tightly capped. 8.Check unit for tubing and sheet metal rattles. 9.Instruct the owner on operation and maintenance. Leave this "Installation and Operating Manual" and the "Use and
  • Haier HC60C1VAR | User Manual - Page 14
    . 9.3. Wiring Diagram Refer to the appropriate wiring diagram included in this manual.(P14) Table 10:Troubleshooting Guide ! WARNING - Disconnect all electrical power to the unit before servicing. Disconnect power to both the indoor and outdoor units. NOTE: There may be more than one electrical
  • Haier HC60C1VAR | User Manual - Page 15
    sized unit Recalculate load Insufficient Cooling Improper airflow Check - should be 400CFM/Ton Incorrect refrigerant charge Charge correctly per instruction. Air, non-condensibles or moisture in system Recover refrigerant, evacuate & recharge, add filter drier Incorrect voltage At compressor
  • Haier HC60C1VAR | User Manual - Page 16
    HC18-60A1VAR/S HC18-60C1VAR HC18-60D1VAR Air Conditioner Wi ri ng Diagram 5 YL 6C S R RD BK RD OFM 6 M BR R S BR BK PU L1 BK L2 WH GND 208 power connect ions di rect ly to elect ric h eater kit pow er terminals. Consult heat er ki t inst allation instructions for complete det ails. 14
  • Haier HC60C1VAR | User Manual - Page 17
    Made in P.R.C.
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17

No.0010572324
K
10 to 13 SEER
1.5 to 5 Tons
Models: HC18-60A1VAR/S
HC18-60C1VAR
HC18-60D1VAR
Installation & Operation Manual
Central Air Conditioner
The information contained in this booklet is subject to change without notice.