INSTALLATION MANUAL ROOM AIR CONDITIONER WALL MOUNTED TYPE HSU-09HEA03/R2(DB)-I HSU-12HEA03/R2(DB)-I HSU-18HEA03/R2(DB)-I Read this manual before installation Explain sufficiently the operating means to the user according to this manual. NO.0010523238 - Haier HSU-18HEA03 | User Manual - Page 2
- Haier HSU-18HEA03 | User Manual - Page 3
Gas leakage detector or soap-and-water solution 11.Measuring tape 12.Reamer Drawing for the installation of indoor and outdoor units Screw Plastic cap 4 6 Drain-elbow 1 7 Cushion 4 8 1 Pipe supporting plate Optional parts for piping Mark A Parts name Non-adhesive tape B Adhesive - Haier HSU-18HEA03 | User Manual - Page 4
R2(DB)-I HSU-12HEA03/R2(DB)-I HSU-18 HEA03/R2(DB)-I Fixing of outdoor unit Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally. When fitting the unit to wall surface, roof or rooftop, fix a supporter unit. Place, where cold air can be spread in a 12.7mm(1/2") 2 - Haier HSU-18HEA03 | User Manual - Page 5
Indoor unit 1.Fitting of the Mounting Plate and Positioning of the wall Hole When the mounting plate is first fixed 1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail. 2. Make - Haier HSU-18HEA03 | User Manual - Page 6
,QGRRUXQLW ,QVWDOODWLRQRIWKH,QGRRU8QLW 'UDZLQJRISLSH 5HDUSLSLQJ 'UDZSLSHVDQGWKHGUDLQKRVHWKHQIDVWHQWKHPZLWKWKHDGKHVLYHWDSH /HIW /HIWUHDUSLSLQJ ,QFDVHRIOHIWVLGHSLSLQJFXWDZD\ZLWKDQLSSHUWKHOLGIRUOHIWSLSLQJ ,QFDVHRIOHIWUHDUSLSLQJEHQGWKHSLSHVDFFRUGLQJ - Haier HSU-18HEA03 | User Manual - Page 7
cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. The type of connecting wire is R2(DB)-I HSU12HEA03/R2(DB)-I {POWER Outdoor unit B 1 (N) 2 (L) 3 (C) 4G0.75mm2 Indoor unit B HSU18HEA03/R2(DB)-I { POWER 2(N) 1(L) 5 Power cable: 09-12 - Haier HSU-18HEA03 | User Manual - Page 8
Liquid side 6.35mm(1/4") 18N.m Liquid side 9.52mm(3/8") 42 N.m Gas side 12.7mm(1/2") 55N.m Spanner Torque wrench Gas side 15.88mm(5/8") 60 N.m Be must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant - Haier HSU-18HEA03 | User Manual - Page 9
valve 3-way valve Open 90o Service port 90ofor 6 sec. Liquid Side 6.35mm(1/4") 2-way valve Gas Side 9.52mm(3/8") 12.7mm(1/2") 3-way valve If the liquid refrigerant into air conditioner according to the amount marked on the name plate. 2-way valve 3-way valve Service port cap Valve rod cap - Haier HSU-18HEA03 | User Manual - Page 10
The power source must be exclusively used for air conditioner. (Over I0A) In the case of installing an air conditioner in a moist place, please install an Run Please kindly explain to our customers how to operate through the instruction manual. Check Items for Test Run Put check mark in boxes Gas