HP 10000 Series Rack Airflow
Optimization Kit
Installation Instructions
Overview
The HP 10000 Series Rack Airflow Optimization Kit enables you to
install foam rail gaskets into your HP 10000 G2 Series 22U, 36U,
42U, and 47U 600-mm (24 in) wide racks and into 42U 800-mm
(31 in) wide racks to improve separation between hot and cold
aisles in the data center.
Kit contents
Callout
Description
1
600-mm (24 in) or 800-mm (31 in) perforated
floor gasket (1)
2
Foam rail gasket roll (4)
Installing foam rail gaskets
IMPORTANT:
This option kit is only compatible with HP
racks that are 600-mm (24 in) or 800-mm (31 in) wide.
1.
Cut the foam rail gasket to fit the size of your rack.
2.
Insert the foam rail gasket into the rack front door on both sides
of the rack.
3.
Insert the foam rail gasket into the space between the 19-in
mounting rails and the vertical frame on both sides of the rack,
with the closed cell side of the foam rail gasket facing the front
of the rack.