HP StorageWorks P9500 Site Preparation Guide Abstract This guide describes the site preparation for HP StorageWorks P9500 disk arrays. The intended audience is a storage system administrator or authorized service provider with independent knowledge of the HP StorageWorks P9500 and Remote Web Console - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 2
2010, 2011 Hewlett-Packard Development Company, L.P. Confidential computer software. Valid license from HP required for possession, use or copying. Consistent with FAR 12.211 and 12.212, Commercial Computer Software, Computer Software Documentation, and Technical Data for Commercial Items are - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 3
5 Responsibilities...5 User responsibilities...5 HP responsibilities...5 Installation Storage requirements...11 Data center requirements...11 Data communication requirements 11 C-Track...12 Insight Remote Support 40 4 Support and other resources 41 Contacting HP...41 Subscription service...41 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 4
Conventions for storage capacity values 42 Typographic conventions...42 Glossary...44 Index...45 4 Contents - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 5
array must be installed by trained HP personnel or trained HP Technical Support. The P9500 disk array is not a customer installable product. User responsibilities You are responsible for performing the following tasks to prepare for installation of the P9500 disk array. • Understand the applicable - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 6
" on the floor) where the P9500 disk array will be installed. User Information Company . Address . Contact . Phone . Mobile . Email . Contact . Phone . Mobile . Email . HP Information Contact . Phone . Mobile . Email . Contact . Phone . Mobile . Email . Notes - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 7
a LAN for Remote Web Console? . . hb-Is the infrastructure available for the default Internet based remote support solution? . . Does the location meet the cable length requirements for the CHAs? . . Does the location meet the requirements for attaching external storage? . . Installation - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 8
of heat. • Warning and safety labels: Safety warnings, cautions, and instructions in various languages are attached to the P9500 disk array components. The safety warnings provide guidelines to follow when working with any equipment. HP recommends that you read all warning labels on the hardware. If - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 9
are provided to prevent possible injury when working with authorized service personnel. Observe the following warning related to moving parts: as a fan. • Tie up long hair. • Unless otherwise specifically instructed, do not supply power to any device that contains rotating or moving parts - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 10
and access to crated or packed equipment. The dimensions of a shipping crate for a single rack are shown in the following table. Table 1 P9500 shipping crate dimensions Item Height Shipping crate, single rack 87 in./2210 mm Width 39 in./991 mm Depth 53 in./1346 mm NOTE: P9500 disk array racks - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 11
to reduce the effects of external fields. The P9500 frames support top access and bottom access for hot cables. Routing the host cables in a P9500 requires HP support personnel to install. The data communication infrastructure needed for the P9500 disk array is described in "Data communication - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 12
of your LAN drop. A public voice phone line near the disk array. Needed to allow your staff and HP representatives to communicate inside and outside your site. C-Track The C-Track remote support solution detects and reports events to the HP Support Service. C-Track transmits heartbeats, SIMs, and - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 13
is not supported on XP and P9500 Disk Arrays. Table 6 P9500 disk array remote support products HP Product AE241A AE242A AE244A AE245A Description Application HP XP/P9500 Remote Device Access Support For customers that fully commit to use HP Remote Support. It uses HP Insight Remote Support for - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 14
http://www.software.hp.com Select Insight Remote Support from the menu on the right. System specifications and requirements This section describes the physical characteristics of a P9500 disk array, including • "Mechanical specifications" (page 14) • "Electrical specifications" (page 15) • " - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 15
"P9500 Electrical specifications - single phase current" (page 16) and "P9500 Electrical specifications - three phase current" (page 17) list the electrical specifications of the P9500 disk array, including power requirements and power consumption. System specifications and requirements 15 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 16
Table 8 P9500 Electrical specifications - single phase current Item Unit Specification Power requirements, system AC, single phase 2 pole + 200 V to 240 V, +6% -8% 50 Hz ±3 Hz, 60 Hz ± 2 Hz operating ground Drive Rack (384 HDD) 5.1KVA (2.5" SAS) Maximum 31.4 KVA Controller chassis power - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 17
as a part of the branch circuit that supplies the unit or system. • The grounding conductor mentioned above should be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the case of a high rise steel-frame structure. • The attachment - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 18
Power connection The AC power input for the P9500 disk array has a duplex PDU structure. This duplex structure PDUs are available for three phase or single phase power for NEMA and IEC compliance applications. Table 10 P9500 AC PDU Options Product Number Local Power Branch circuit Number of - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 19
19)provides the environmental specifications and requirements for the P9500 disk array. Table 11 P9500 environmental specifications Item Temperature (ºF / ºC) Operating 60.8 - 80.9 / 16 to 32 Not Operating -18 - 109.4 -10 to 43 In Storage -45 - 140 -25 to 60 Relative Humidity (%)2 20 to 80 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 20
fans. Airflow is from front to back. Table 12 Heat, power, and airflow Model Number AV400A - HP P9500 Disk Array DKC Module-0 Rack AV401A - HP P9500 DKC Module-1 Rack AV402A - HP P9500 DKU Disk Unit Rack AV413A - HP P9500 Drive Chassis SAS Switch Kit Heat Output (kW) 1.881 1.831 1.471 0.120 Power - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 21
0.072 Gbps FCoE CHA AV440A - HP P9500 0.19 ProcessorBlade AV442A - HP P9500 DKC Hub Kit 0.010 AV443A - HP P9500 2nd SVP High Reliability Kit 0.052 AV444A - HP P9500 Cache 0.068 Memory Adapter AV447A - HP P9500 16GB 0.019 Cache Memory Module AV448A - HP P9500 32GB 0.019 Cache Memory Module - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 22
and airflow (continued) Model Number Heat Output (kW) 3 AV490A - HP P9500 200GB 0. disk array disk array are: • Front/rear = 65 dB (A) • Both sides = 65 dB (A) Service clearance, floor cutout, and floor load rating This section describes the service clearance requirements for the P9500 disk array - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 23
clearances for single rack configuration Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0. 1 0.2 0.1 0.3 0.3 0.5 0.4 C=0.4 0 0.1 0.2 0.4 C=0.6 0 0 0.1 0.3 C=0.6 0 0 0.1 0.2 Service clearance, floor cutout, and floor load rating 23 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 24
for single rack configuration (continued) Floor Load Rating ( disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Two rack configuration (one DKC) The following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 25
15 Floor load rating and required clearances for two rack configuration Floor Load Rating (kg/m2) 500 450 400 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.3 0.2 0.5 0.4 C=0.4 0 0.1 0.3 C=0.6 0 0 0.2 C=0.6 0 0 0 Service clearance, floor cutout, and floor load rating 25 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 26
for two rack configuration (continued) Floor Load Rating (kg disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Two rack configuration (two DKC) The following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 27
rating and required clearances for a two rack configuration (two DKC) Floor Load Rating (kg/m2) 500 450 400 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.3 0.2 0.5 0.4 C=0.4 0 0.1 0.3 C=0.6 0 0 0.2 C=0.6 0 0 0 Service clearance, floor cutout, and floor load rating 27 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 28
configuration (two DKC) (continued) Floor Load Rating ( disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Three rack configuration (left module) The following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 29
for a three rack configuration (left module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.4 0.2 0.8 0.6 1.3 1.1 C=0.4 0 0.1 0.4 0.9 C=0.6 0 0 0.3 0.7 C=0.6 0 0 0 0.4 Service clearance, floor cutout, and floor load rating 29 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 30
(left module) (continued) Floor Load Rating disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Three rack configuration (right module) The following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 31
a three rack configuration (right module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.4 0.3 0.8 0.6 1.4 1.2 C=0.4 0 0.1 0.5 1.0 C=0.6 0 0 0.3 0.8 C=0.6 0 0 0 .1 0.5 Service clearance, floor cutout, and floor load rating 31 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 32
(right module) (continued) Floor Load Rating disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Four rack configuration (left module) The following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 33
for a four rack configuration (left module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.5 0.3 1.1 0.8 1.8 1.5 C=0.4 0 0.1 0.6 1.2 C=0.6 0 0 0.4 1.0 C=0.6 0 0 0 .1 0.6 Service clearance, floor cutout, and floor load rating 33 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 34
(left module) (continued) Floor Load Rating disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Four rack configuration (right module) The following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 35
a four rack configuration (right module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.5 0.3 1.1 0.8 1.8 1.5 C=0.4 0 0.1 0.6 1.2 C=0.6 0 0 0.4 1.0 C=0.6 0 0 0 .1 0.6 Service clearance, floor cutout, and floor load rating 35 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 36
rack configuration (right module) (continued) Floor Load Rating (kg/m2 disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Five rack configuration This following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 37
rack system Table 21 Floor load rating and required clearances for a five rack configuration Floor Load Rating (kg/m2) 500 450 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.6 0.3 C=0.4 0 0.1 C=0.6 0 0 C=0.6 0 0 Service clearance, floor cutout, and floor load rating 37 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 38
for a five rack configuration (continued) Floor Load Rating (kg/m2 disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Six rack configuration This following figure and table shows the service - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 39
six rack system Table 22 Floor load rating and required clearances for a six rack configuration Floor Load Rating (kg/m2) 500 450 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.7 0.4 C=0.4 0 0.1 C=0.6 0 0 C=0.6 0 0 Service clearance, floor cutout, and floor load rating 39 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 40
LAN for Remote Web Console Remote Web Console communicates with the P9500 disk array over a LAN to obtain system configuration and status information and send user-requested commands to the disk array. Remote Web Console serves as the integrated interface for all Resource Manager components. • Cable - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 41
become the property of HP. Related information You can find supporting documents on the Manuals page of the HP Business Support Center website: http://www.hp.com/support/manuals In the Storage section, click Disk Storage Systems for hardware or Storage Software for software, and then select your - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 42
= 1,0006 bytes P9000 disk arrays use the following values to calculate logical storage capacity values (logical ://www.hp.com Bold Commands, their arguments, and argument values Monospace, italic text • Code variables • Command variables Monospace, bold text Emphasized monospace text 42 Support - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 43
bodily harm or death. CAUTION: Indicates that failure to follow directions could result in damage to equipment or data. IMPORTANT: Provides clarifying information or specific instructions. NOTE: Provides additional information. TIP: Provides helpful hints and shortcuts. Typographic conventions 43 - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 44
array and the external host system. Occasionally, this term is used synonymously with the term channel host interface processor (CHIP). Continuous Track. An HP software program that detects internal hardware component problems on an array and automatically reports them to HP Support Services. Disk - HP P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-96331, May 2011) - Page 45
, 10 contacting HP, 41 conventions document, 42 storage capacity values, 42 text symbols, 43 D disk arrays supported models, 5 document conventions, 42 documentation HP website, 41 providing feedback, 41 E equipment clearances, 10 equipment weight, 11 G guidelines access by authorized personnel
HP StorageWorks
P9500 Site Preparation Guide
Abstract
This guide describes the site preparation for HP StorageWorks P9500 disk arrays. The intended audience is a storage system
administrator or authorized service provider with independent knowledge of the HP StorageWorks P9500 and Remote Web
Console.
HP Part Number: AV400-96331
Published: May 2011
Edition: Third