HP ProLiant DL288 ISS Technology Focus, Number 13

HP ProLiant DL288 Manual

HP ProLiant DL288 manual content summary:

  • HP ProLiant DL288 | ISS Technology Focus, Number 13 - Page 1
    discovers the rack installation of ProLiant G7 servers that use HP Common Slot Platinum Power Supplies server re-boots. The switch works similarly for a manually entered device, such as a third-party device, for which the device's UUID is properly matched to its outlets. When an iPDU running firmware
  • HP ProLiant DL288 | ISS Technology Focus, Number 13 - Page 2
    , and automates the EcoPOD's power, cooling, and safety systems. IT load monitoring The ECS uses an industrial-quality programmable logic controller (PLC). The PLC gathers IT power consumption data from HP Monitored Power Distribution Units (PDU), up to two per rack. Each PDU accepts 3-phase 415V
  • HP ProLiant DL288 | ISS Technology Focus, Number 13 - Page 3
    years ago by showing working prototypes. Today, HP provides GPGPUs on 14 different ProLiant servers in multiple configurations and offers complete supercomputer clusters of purpose-built ProLiant servers. Even vendors for proprietary supercomputers are using this idea. Favorite project: Birth of the
  • HP ProLiant DL288 | ISS Technology Focus, Number 13 - Page 4
    » HP Advanced Memory Error Detection Technology » Understanding HP SIM's Federated Search Architecture » HP custom ESXi images for ProLiant servers » ISS Technology Communications » Past Article Index » Subscribe/Unsubscribe » Follow us on Twitter HP respects your privacy. If you would like to
  • 1
  • 2
  • 3
  • 4

ISS Technology Focus
Number 13
In this issue:
»
Outlet Control in HP
Intelligent Power
Discovery
»
HP EcoPOD 240a
Environment Control
System
»
Meet the Expert
Bill
Whiteman
»
Recent publications
ISS TechComm
iTunes
New posts are now
available on Apple
iTunes, either check
your iTunes page or go
to ours:
iTunes page
.
Follow us:
Like us:
Outlet Control in HP Intelligent Power Discovery
This article describes the Outlet Control feature of HP Intelligent Power Discovery
(IPD). IPD solves major power distribution challenges: provisioning power to IT devices;
monitoring and managing servers’ real
-time power use; and verifying power
connections to critical servers. This article involves the latter. A common cause of
server failure is human error when connecting power to serv
ers’ redundant power
supplies.
How IPD works
Our IPD solution automatically discovers the rack installation of ProLiant G7 servers that
use HP Common Slot Platinum Power Supplies. IPD includes Intelligent Power
Distribution Unit (iPDU) cores with six monitored C-19 outlets, Intelligent Extension Bars
with five monitored C-13 outlets, and IPD power cords with embedded RS-232 data
lines. The iPDU core has an embedded management module that lets you access
power topology information locally through the HP Intelligent PDU Management GUI or
remotely using HP Insight Control software or SNMP.
When administrators connect ProLiant servers to the IPD components, the iPDU cores
immediately detect and communicate with each server’s iLO device before the server is
powered on. The iPDU cores and the iLO devices exchange identity data
hostname, IP
address, and unique universal identification number
through the IPD power cords. This
allows each iPDU to track the servers plugged into the Extension Bar outlets on each
load segment (iPDU outlet). IPD is the only solution in the server industry today that
automatically correlates server identity to power outlets.
Power Cycle Control
If you need to reset a server by cycling power to it, you must cycle the correct outlet(s)
or you can shut down the wrong server. Also, if a server uses redundant power supplies,
you have to cycle all power supplies simultaneously.
Using the HP Intelligent PDU Management GUI or Insight Control remotely, you can
view and control the status of all outlets on each load segment. The Control page of the
management GUI (Figure 1) shows the Redundancy Control option and Power Control
switch for each outlet.
The Power Cycle Control column includes a switch that allows you to turn power on or
off simultaneously to the redundant outlets for each server. By cycling redundant outlets
simultaneously, the switch prevents boot errors and power supply errors when the
server re-boots. The switch works similarly for a manually entered device, such as a
third-
party device, for which the device’s UUID is properly matched to its outlets. When
an iPDU running firmware v1.4 detects a non-IPD device on an outlet, an assisted