    HP Uninterruptible Power System R3000 XR Models User Guide Part Number 192131-003 August 2002 (Third Edition)
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 2
    12.212, Commercial Computer Software, Computer Software Documentation, and Technical Data for Commercial Items are licensed to the U.S. Government under vendor's standard commercial license. HP Uninterruptible Power System R3000 XR Models User Guide August 2002 (Third Edition) Part Number 192131-003
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 3
    of Operation...2-2 Charging the Batteries ...2-3 Placing the UPS in Operate Mode...2-3 Returning to Standby Mode...2-4 Initiating a Self-Test ...2-5 Audible Alarm...2-6 Silencing an Audible Alarm...2-7 Shutting Down the System ...2-7 HP Uninterruptible Power System R3000 XR Models User Guide iii
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 4
    Canadien)...A-4 Class A Equipment...A-4 Class B Equipment ...A-4 European Union Notice...A-4 Japanese Notice...A-5 China Taiwan Notice...A-5 Battery Replacement Notice ...A-6 Appendix B Electrostatic Discharge Grounding Methods ...B-1 iv HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 5
    Contents Appendix C Specifications Physical Specifications...C-1 Input Specifications ...C-2 Output Specifications ...C-3 Battery Specifications...C-5 Battery Runtime ...C-5 Environmental Specifications...C-6 Index HP Uninterruptible Power System R3000 XR Models User Guide v
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 6
    one individual to handle safely. WARNING: To prevent personal injury or damage to the equipment, observe local occupational health and safety requirements and guidelines for manual material handling. HP Uninterruptible Power System R3000 XR Models User Guide vii
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 7
    . IMPORTANT: Text set off in this manner presents clarifying information or specific instructions. NOTE: Text set off in this manner presents commentary, sidelights, or serif typeface is used for uniform resource locators (URLs). viii HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 8
    Instructions • HP UPS XR Products Power Cord and Options Reference Guide • Industry Standard Terminology Glossary Getting Help If you have a problem and have exhausted the information in this guide, further information and other help is available in the following locations. HP Technical Support
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 9
    : • In the United States, call 1-800-345-1518. • In Canada, call 1-800-263-5868. • Elsewhere, see the HP website for locations and telephone numbers. Reader's Comments To comment on this guide, send an email to [email protected]. x HP Uninterruptible Power System R3000 XR Models User
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 10
    hardware option cards • Support for extended runtime modules (ERMs) • Support for power distribution units (PDUs) • Support for Remote Emergency Power Off (REPO) • Power protection for loads up to 3000 VA/2700 W • Load segment control HP Uninterruptible Power System R3000 XR Models User Guide 1-1
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 11
    plug International, high-voltage, rack-mountable UPS with non-detachable CEE 7/7 SCHUKO plug International, high-voltage, rack-mountable UPS with non-detachable BS-546 plug 1-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 12
    Front panel configuration 1 Battery compartment 2 Control buttons 3 LED display For detailed information on using the control buttons and LED indicators, refer to the section, "Front Panel Controls and LED Indicators," in Chapter 2. HP Uninterruptible Power System R3000 XR Models User Guide 1-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 13
    through Figure 1-7. 12 3 456 10 9 8 7 Figure 1-2: Rear panel of R3000 XR-NA and R3000 XR-JPN 1 REPO port 2 ERM connector 3 Communications port/option slot 4 Load segment 1 clip attachment locations 10 Ground bonding screw 1-4 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 14
    -C13 receptacles) 6 Load segment 3 (three IEC-320-C13 receptacles) 7 PDU output (L6-20) receptacle (load segment 1) 8 Cord retention clip attachment locations 9 Ground bonding screw 10 Power cord with L6-20 plug Overview HP Uninterruptible Power System R3000 XR Models User Guide 1-5
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 15
    receptacle (load segment 1) 9 Cord retention clip attachment locations 10 Input power receptacle (IEC-320-C19) for country-specific plug attachment 11 Ground 3.5 mA, use the UPS R3000i XR-EURO, R3000i XR-SCHUKO, or R3000i XR-SA model. 1-6 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 16
    12 3 456 7 11 10 9 8 Figure 1-5: Rear panel of R3000i XR-EURO 1 REPO port 2 ERM connector 3 Communications port/option slot 4 Load clip attachment locations 10 Ground bonding screw 11 Power cord with IEC-309 plug Overview HP Uninterruptible Power System R3000 XR Models User Guide 1-7
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 17
    12 3 456 7 11 10 9 8 Figure 1-6: Rear panel of R3000i XR-SCHUKO 1 REPO port 2 ERM connector 3 Communications port/option slot 4 Load clip attachment locations 10 Ground bonding screw 11 Power cord with CEE 7/7 SCHUKO plug 1-8 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 18
    3 456 7 11 10 9 8 Figure 1-7: Rear panel of R3000i XR-SA 1 REPO port 2 ERM connector 3 Communications port/option slot 4 attachment locations 10 Ground bonding screw 11 Input power receptacle with BS-546 power cord Overview HP Uninterruptible Power System R3000 XR Models User Guide 1-9
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 19
    a list of supported PDUs, go to www.hp.com. For more information on the supported hardware options, refer to the HP UPS XR Products Power Cord and Options Reference Guide included on the Power Products Documentation CD and on www.hp.com. 1-10 HP Uninterruptible Power System R3000 XR Models User
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 20
    pressed and a REPO is detected, battery start is inhibited and the UPS is not able to assume the load. The electronic module fans spin and the Alarm LED and an audible alarm are active as long as the On button is held. HP Uninterruptible Power System R3000 XR Models User Guide HP2:06 PM 1-11
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 21
    is not damaged by accident (other than a utility power transient), misuse, or abuse. Pre-Failure Battery Warranty For specific information on the battery warranty, refer to the section, "Pre-Failure Battery Warranty," in Chapter 4. 1-12 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 22
    to 50% load Green-UPS load is approximately 26% to 50% of maximum power. 5 0% to 25% load Green-UPS load is approximately 0% to 25% of maximum power. 6 General Alarm Red-UPS detected a general alarm. Perform a self-test. continued HP Uninterruptible Power System R3000 XR Models User Guide 2-1
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 23
    at the UPS output receptacles. - The UPS charges the batteries as necessary. • Configure Mode - Power is available at the UPS output receptacles. - The UPS charges the batteries as necessary. - The UPS configuration can be updated. 2-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 24
    compliance with a short beep. IMPORTANT: If the UPS is using battery power (no utility power present), press and hold the On button (1) until the audible alarm sounds. 2 1 100% 25% Figure 2-2: Placing the UPS in Operate Mode HP Uninterruptible Power System R3000 XR Models User Guide 2-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 25
    button (1) until the audible alarm sounds. The Utility LED (2) flashes, and power to the load ceases. 2 100% 1 25% Figure 2-3: Placing the UPS • While in Standby mode, the UPS maintains the charge on the batteries, but no power is available at the output receptacles. • The UPS remains in Standby
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 26
    test requires battery power, the self-test cannot be initiated if the batteries are less than 90 percent charged. If the UPS detects a problem, the -test detects a problem, refer to the section, "Alarm Troubleshooting," in Chapter 5. HP Uninterruptible Power System R3000 XR Models User Guide 2-5
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 27
    . Operating from battery. Battery disconnected. Low battery. Audible Alarm On-Steady On-5 second beep On-5 second beep No audible alarm On-5 second beep On-5 second beep On-5 second beep Can be disabled? Yes Yes Yes N/A Yes Yes No 2-6 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 28
    all load devices. 2. Press the Standby button to take the UPS out of Operate mode. Power to the load receptacles ceases. 3. Disconnect the UPS from utility power. 4. Wait at least 60 seconds while the UPS internal circuitry discharges. HP Uninterruptible Power System R3000 XR Models User Guide 2-7
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 29
    troubleshooting alarms. Placing the UPS in Configure Mode The UPS can enter Configure mode while in Operate or Standby mode. To place the UPS in Configure mode: 1. Remove the UPS front bezel by snapping it off (1). 1 Figure 3-1: Removing the UPS front bezel HP Uninterruptible Power System R3000 XR
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 30
    R3000h XR-JPN models.) Note: For units factory-configured for 200 V or 208 V, the Site Wiring Fault function has been disabled. If reconfiguring a 230 V to operate at 208 V, the Site Wiring Fault function must be manually disabled. 3-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 31
    General Alarm On Battery Bad Battery/Low Battery Site Wiring Fault Indicator General Alarm On Battery Bad Battery/Low Battery Site Wiring Fault Indicator General Alarm On Battery Bad Battery/Low Battery Site Wiring Fault Indicator HP Uninterruptible Power System R3000 XR Models User Guide 3-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 32
    Configure mode by pressing and holding the Configure button until the Configure Mode On LED turns solid green. When the Configure button is released, the configurable LEDs flash and out and the configuration settings are not stored. 3-4 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 33
    the batteries. No user intervention is required while the UPS is in use. For information on keeping the batteries charged while the UPS is in extended storage, refer to the section, "Care and Storage of Batteries," in this chapter. HP Uninterruptible Power System R3000 XR Models User Guide 4-1
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 34
    replacement is required. If the Bad Battery/Low Battery LED (1) remains red, replace the batteries as soon as possible. For more information on initiating a self-test, refer to the section, "Initiating a Self-Test," in Chapter 2. 4-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 35
    all load devices. 2. Press the Standby button to take the UPS out of Operate mode. Power to the load receptacles ceases. 3. Disconnect the UPS from utility power. 4. Wait at least 60 seconds while the UPS internal circuitry discharges. HP Uninterruptible Power System R3000 XR Models User Guide 4-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 36
    1. Remove the front bezel (1) by pulling on both ends. 1 Figure 4-2: Removing the front bezel 2. Remove the two screws from the metal battery bracket (1) and remove the bracket (2). 2 1 1 Figure 4-3: Removing the battery bracket 4-4 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 37
    "Troubleshooting." IMPORTANT: The batteries charge to 80 percent of their capacity within approximately three hours. Charge the batteries for 24 hours before using the UPS to supply backup power to devices. The load may not be fully protected for 48 hours. HP Uninterruptible Power System R3000 XR
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 38
    the UPS to remain in Standby mode. c. Allow the UPS to charge the batteries for 24 hours. d. Update the Battery Recharge Date label. CAUTION: Because of the short shelf life of the battery, avoid storing a battery spare as a backup. 4-6 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 39
    warranty coverage is three years for parts. The warranty for the first year of ownership includes parts and labor. If battery spares are not available for a particular UPS model, then the entire UPS, including its battery, is replaced. HP Uninterruptible Power System R3000 XR Models User Guide 4-7
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 40
    the batteries. Allow the UPS to charge the batteries for 24 hours. Initiate a self-test. If the LED does not turn off, replace the batteries. Install the battery module. If the battery module is already installed, remove and re-insert. HP Uninterruptible Power System R3000 XR Models User Guide 5-1
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 41
    a qualified electrician to verify that the utility power is suitable for the UPS. Allow batteries to charge for 24 hours, and initiate a self-test. If the LED is red, replace the batteries. Re-insert the battery module. continued 5-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 42
    . Contact an HP authorized service representative. All LEDs are flashing red and an audible alarm cannot be silenced. An internal UPS fault condition exists. Power down the UPS. Contact an HP authorized service representative. HP Uninterruptible Power System R3000 XR Models User Guide 5-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 43
    the problem. For a detailed listing and location of each LED, refer to the section, "Front Panel Controls and LED Indicators," in Chapter 2. Table 5-3: Alarm Troubleshooting contact an HP authorized service representative. continued 5-4 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 44
    ( ). If the Bad Battery/Low Battery LED ( ) is still on, the battery may need to be replaced. Check the battery connections. Call an HP authorized service representative if the problem continues. Have a qualified electrician correct the wiring. The UPS is receiving utility power that may be unstable
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 45
    service representative. The alarm cannot be silenced. Repairing the UPS Repairs to the UPS must be carried out by HP or an HP authorized service representative. Other than battery replacement, there are no UPS user-serviceable parts. 5-6 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 46
    instructions, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at personal expense. HP Uninterruptible Power System R3000 XR Models
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 47
    used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a continuous quality improvement, calls may be recorded or monitored. A-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 48
    . Cables Connections to this device must be made with shielded cables with metallic RFI/EMI connector hoods to maintain compliance with FCC Rules and Regulations. HP Uninterruptible Power System R3000 XR Models User Guide A-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 49
    these directives implies conformity to the following European Norms (in brackets are the equivalent international standards): • EN50091-1 - UPS Product Safety Requirements • EN50091-2 - UPS EMC Requirements A-4 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 50
    Japanese Notice Regulatory Compliance Notices China Taiwan Notice HP Uninterruptible Power System R3000 XR Models User Guide A-5
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 51
    , battery modules, and accumulators should not be disposed of together with the general household waste. To forward them to recycling or proper disposal, use the public collection system or return them to your authorized HP Partners or their agents. A-6 HP Uninterruptible Power System R3000 XR
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 52
    conductive field service tools. • Use a portable field service kit with HP authorized reseller install the part. NOTE: For more information on static electricity, or assistance with product installation, contact your HP authorized reseller. HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 53
    battery runtime estimates, and environmental requirements when operating the UPS. Physical Specifications Table C-1: Physical Specifications Feature Dimensions Weight Width Height Depth Metric 440.7 mm 89 mm 622 mm 37 kg U.S. 17.5 in 3.5 in 25 in 82 lb HP Uninterruptible Power System R3000 XR
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 54
    power cord with NEMA L6-20 plug Detachable power cord with country-specific plug Non-detachable power cord with 16 A IEC-309 plug Non-detachable power cord with 16 A CEE 7/7 SCHUKO plug Non-detachable power cord with 16 A BS-546 plug C-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 55
    , C13 3 x IEC-320, C13 1 x IEC-320, C20 3 x IEC-320, C19 3 x IEC-320, C13 3 x IEC-320, C13 1 x IEC-320, C20 3 x IEC-320, C13 3 x IEC-320, C13 HP Uninterruptible Power System R3000 XR Models User Guide C-3
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 56
    110 120 127 200 208 230 240 Source of Power Utility power (normal range) Other features Battery power Feature Online efficiency Voltage wave shape Surge suppression Noise A peak MOVs and line filter for normal and common mode use C-4 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 57
    capacity at default nominal utility voltage and no load. Battery Runtime Table C-6: Estimated Battery Runtime Load (Percent) 20 50 80 100 Estimated Battery Runtime (Minutes) 40 12 6.5 5 UPS with ERM Runtime (Minutes) 120 45 30 20 HP Uninterruptible Power System R3000 XR Models User Guide C-5
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 58
    2,000 m (6,600 ft) above sea level Non-operating altitude 15,000 m (49,212 ft) above sea level Audible noise Less than 45 dBA Note: UPS will be de-rated above 2,000 m (6,600 ft). C-6 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 59
    of batteries 4-6 E electric shock symbol v electrostatic discharge See ESD entering Configure mode 3-1 Operate mode 2-3 Standby mode 2-4 environmental specifications C-6 ESD (electrostatic discharge) B-1 exchanging data 1-2 HP Uninterruptible Power System R3000 XR Models User Guide Index-1
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 60
    transporting B-1 protection, overcurrent 1-2 R rear panels 1-4 regulatory compliance notices cables A-3 Canadian A-4 Class A equipment A-1 Class B equipment A-2 Compaq series number A-1 device modifications A-3 European Union A-4 Index-2 HP Uninterruptible Power System R3000 XR Models User Guide
  • HP R12000XR | UPS R3000 XR Models User Guide - Page 61
    new batteries 4-5 warranties $25,000 Computer Load Protection Guarantee 1-12 applicability 1-12 limited warranty 1-12 pre-failure battery 4-7 three-year limited 1-12 website, HP vii weight C-1 wrist straps B-1 www.hp.com vii Index HP Uninterruptible Power System R3000 XR Models User Guide Index
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61

HP Uninterruptible Power System
R3000 XR Models
User Guide
Part Number 192131-003
August 2002 (Third Edition)