    HP Uninterruptible Power System R1500 XR Models User Guide August 2002 (Second Edition) Part Number 217823-002
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 2
    without notice. The warranties for HP products are set forth in the express limited warranty statements accompanying such products. Nothing herein should be construed as constituting an additional warranty. HP Uninterruptible Power System R1500 XR Models User Guide August 2002 (Second Edition) Part
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 3
    ...1-9 Chapter 2 Operation Front Panel Controls and LED Indicators 2-1 Modes of Operation ...2-2 Charging the Batteries ...2-3 Placing the UPS in Operate Mode ...2-3 Returning to Standby Mode...2-4 Initiating a Self-Test ...2-5 HP Uninterruptible Power System R1500 XR Models User Guide iii
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 4
    Modifications ...A-2 Cables ...A-3 Canadian Notice (Avis Canadien)...A-3 Class A Equipment ...A-3 Class B Equipment ...A-3 European Union Notice...A-3 Japanese Notice ...A-4 China Taiwan Notice ...A-4 Battery Replacement Notice...A-5 iv HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 5
    B Electrostatic Discharge Grounding Methods ...B-1 Appendix C Specifications Physical Specifications ...C-1 Input Specifications ...C-2 Output Specifications...C-3 Battery Specifications ...C-4 Environmental Specifications ...C-4 Index HP Uninterruptible Power System R1500 XR Models User Guide v
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 6
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 7
    : To reduce the risk of personal injury or damage to the equipment, Weight in lb observe local occupational health and safety requirements and guidelines for manual material handling. HP Uninterruptible Power System R1500 XR Models User Guide vii
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 8
    Runtime Module Installation Instructions • HP UPS XR Products Power Cord and Options Reference Guide • Industry Standard Terminology Glossary These documents are located on the Power Products Documentation CD or at www.hp.com. viii HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 9
    : • In the United States, call 1-800-345-1518. • In Canada, call 1-800-263-5868. • Elsewhere, see the HP website for locations and telephone numbers. Reader's Comments To comment on this guide, send e-mail to [email protected]. HP Uninterruptible Power System R1500 XR Models User Guide ix
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 10
    1440 VA/1340 W (R1500 XR NA model) or 1500 VA/1340 W (R1500 XR JPN and R1500 XR H INT'L models) • Support for UPS power management software • Support for HP hardware option cards, connect the communications port to the host computer. HP Uninterruptible Power System R1500 XR Models User Guide 1-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 11
    5-15 plug Japanese, low-voltage rack-mountable UPS with non-detachable NEMA 5-20 plug International, high-voltage rack-mountable UPS with detachable country-specific plug 1-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 12
    Front panel configuration 1 Battery compartment 2 Control buttons 3 LED display For detailed information on using the control buttons and LED indicators, refer to the section, "Front Panel Controls and LED Indicators," in Chapter 2. HP Uninterruptible Power System R1500 XR Models User Guide 1-3
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 13
    1-2, 1-3, and 1-4. 1 2 3 10 9 8 7 65 4 Figure 1-2: Rear panel of R1500 XR NA 1 Communications port/option slot 2 Load segment circuit protectors 3 Load segment 2 (three NEMA NEMA 5-15 plug 9 ERM connector 10 Ground bonding screw 1-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 14
    1 2 3 10 9 8 7 65 4 Figure 1-3: Rear panel of R1500 XR JPN 1 Communications port/option slot 2 Load segment circuit protectors 3 Load segment 2 (three NEMA cord with NEMA 5-20 plug 9 ERM connector 10 Ground bonding screw Overview HP Uninterruptible Power System R1500 XR Models User Guide 1-5
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 15
    1 2 3 4 10 9 8 76 5 Figure 1-4: Rear panel of R1500 XR H INT'L 1 Communications port/option slot 2 Circuit protector 3 IEC-320-C14 . Use RackBuilder Pro (obtainable at www.hp.com) to find the total system leakage current. 1-6 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 16
    192189-B21 For a list of supported PDUs and more information on the available hardware options, refer to the HP UPS XR Products Power Cord and Options Reference Guide included on the Power Products Documentation CD and at www.hp.com. HP Uninterruptible Power System R1500 XR Models User Guide 1-7
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 17
    the National Electrical Code (NEC). • The UPS is used under normal operating conditions. Users must comply with all instructions and labels. • The UPS is not damaged by accident (other than a utility power transient), misuse, or abuse. 1-8 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 18
    Overview Pre-Failure Battery Warranty For specific information on the battery warranty, refer to the section, "Pre-Failure Battery Warranty," in Chapter 4. HP Uninterruptible Power System R1500 XR Models User Guide 1-9
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 19
    troubleshooting the unit. NOTE: For installation considerations and procedures, refer to the instructions included with the UPS. Copies of this document can be downloaded from www.hp UPS voltage configuration is incorrect. continued HP Uninterruptible Power System R1500 XR Models User Guide 2-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 20
    at the UPS output receptacles. - The UPS charges the batteries as necessary. • Configure Mode - Power is available at the UPS output receptacles. - The UPS charges the batteries as necessary. - The UPS configuration can be updated. 2-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 21
    compliance with a short beep. IMPORTANT: If the UPS is running on battery power (no utility power is present), press and hold the On button (1) until the audible alarm sounds. 2 1 100% 25% Figure 2-2: Placing the UPS in Operate mode HP Uninterruptible Power System R1500 XR Models User Guide 2-3
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 22
    : • While in Standby mode, the UPS maintains the charge on the batteries, but no power is available at the output receptacles. • The UPS remains in Standby mode until an alternate mode is selected, or until utility power is removed. 2-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 23
    self-test requires battery power, the self-test cannot be initiated if the batteries are less than 90 percent charged. If the UPS detects a problem, the appropriate self-test detects a problem, refer to Chapter 5, "Troubleshooting." HP Uninterruptible Power System R1500 XR Models User Guide 2-5
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 24
    audible alarm to warn of a problem. For information on what to do if the UPS detects an alarm condition, refer to Chapter 5, "Troubleshooting." Silencing an Audible Alarm To silence seconds while the UPS internal circuitry discharges. 2-6 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 25
    is important in performing other functions on the unit, such as maintaining the battery and troubleshooting alarms. Placing the UPS in Configure Mode The UPS can enter Configure mode off (1). 1 Figure 3-1: Removing the UPS front bezel HP Uninterruptible Power System R1500 XR Models User Guide 3-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 26
    is selected to 100 VAC. () On Battery 110/220 Nom Nominal utility voltage level is selected to 110/220 VAC. () Bad Battery/Low Battery 120/230 Nom Nominal utility voltage level is on the front panel for future enhancement purposes. 3-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 27
    On LED (5) illuminates solid green. When you release the Configure button, the configurable LEDs flash briefly, then the LED associated with the current configuration illuminates. HP Uninterruptible Power System R1500 XR Models User Guide 3-3
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 28
    the Test/Alarm Reset button (1). NOTE: If the unit remains idle for two minutes, Configure mode times out and the configuration settings are not stored. 3-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 29
    the batteries. No user intervention is required while the UPS is in use. For information on keeping the batteries charged while the UPS is in extended storage, refer to the section, "Care and Storage of Batteries," in this chapter. HP Uninterruptible Power System R1500 XR Models User Guide 4-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 30
    : Because of the short shelf life of the battery, avoid storing a battery spare as a backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep these batteries charged while in storage is implemented. 4-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 31
    UPS Batteries can be replaced without powering down the UPS if the UPS is not supplying battery Battery Pack To remove the battery pack: 1. Remove the UPS front bezel by pulling on both ends (1). 1 Figure 4-2: Removing the UPS front bezel HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 32
    Maintenance 2. Remove the plastic battery cover plate, as featured in select models. Figure 4-3: Removing the battery cover plate 3. Remove the two screws to obtain access to the battery pack. Figure 4-4: Removing the two screws 4-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 33
    wiring, it is not necessary to disconnect or reuse the wires connected to the old battery pack. 6. Set the used battery pack and the battery wiring aside for proper disposal. Refer to "Disposing of Used Batteries," in this chapter. HP Uninterruptible Power System R1500 XR Models User Guide 4-5
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 34
    not dispose of used batteries with general office or household waste. Return the used pack for proper disposal to either: • HP, authorized HP Partners, or their agents • A recycling center that meets all local environmental standards 4-6 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 35
    coverage is three years for parts. The warranty for the first year of ownership includes parts and labor. If battery spares are not available for a particular HP UPS model, then the entire UPS, including its battery, is replaced. HP Uninterruptible Power System R1500 XR Models User Guide 4-7
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 36
    . Verify that the airflow around the UPS is not restricted. Wait at least 5 minutes and restart the UPS. If the condition persists, contact an authorized service representative. Contact an authorized service representative. continued HP Uninterruptible Power System R1500 XR Models User Guide 5-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 37
    Troubleshooting Table 5-1: Troubleshooting continued Symptom authorized service representative. Allow the UPS to charge the batteries for 24 hours. Initiate a self-test. If the LEDs remain illuminated, replace the batteries. continued 5-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 38
    configuration. Remove one or more devices to reduce the power requirements. Verify that the devices are not defective. Power down the UPS. Contact an authorized service representative. continued HP Uninterruptible Power System R1500 XR Models User Guide 5-3
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 39
    HP power management software to specify a suitable delay. Repairing the UPS Repairs to the UPS must be carried out by HP or an authorized service representative. Other than battery replacement, there are no UPS user-serviceable parts. 5-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 40
    instructions, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at personal expense. HP Uninterruptible Power System R1500 XR Models
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 41
    accordance with the instructions, may cause user to be notified that any changes or modifications made to this device that are not expressly approved by Hewlett-Packard Company may void the user's authority to operate the equipment. A-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 42
    these directives implies conformity to the following European Norms (in brackets are the equivalent international standards): • EN50091-1 - UPS Product Safety Requirements • EN50091-2 - UPS EMC Requirements HP Uninterruptible Power System R1500 XR Models User Guide A-3
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 43
    Regulatory Compliance Notices Japanese Notice China Taiwan Notice A-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 44
    about battery replacement or proper disposal, contact your authorized reseller or your authorized service provider. WARNING: The UPS contains a sealed lead-acid battery pack them to HP, your authorized HP Partners, or their agents. HP Uninterruptible Power System R1500 XR Models User Guide A-5
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 45
    on conductive floors or dissipating floor mats. • Use conductive field service tools. • Use a portable field service kit with a folding static-dissipating work mat. If you do with product installation, contact your authorized reseller. HP Uninterruptible Power System R1500 XR Models User Guide B-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 46
    , and output specifications for the UPS. Topics also include battery descriptions, battery runtime estimates, and environmental requirements when operating the UPS. Physical 88.9 mm 464.8 mm 23 kg U.S. 17.0 in 3.5 in 18.3 in 50 lb HP Uninterruptible Power System R1500 XR Models User Guide C-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 47
    R1500 XR NA Utility Voltage Frequency (Hz) 50/60 R1500 XR JPN 50/60 R1500 XR H INT'L 50/60 Note: 1 120 on battery 2 110 on battery mA. Use RackBuilder Pro (obtainable at www.hp.com) to find the total system leakage current. C-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 48
    On-line efficiency Voltage wave shape Surge suppression Noise filtering *+0% to -10% at low battery Specification 95% Sine wave; 5% THD with typical PFC load High energy 6500 A peak MOVs and line filter for normal and common mode use HP Uninterruptible Power System R1500 XR Models User Guide C-3
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 49
    Feature Type Voltage Charging Specification Sealed lead-acid; maintenance-free 48 V Battery String HP recommends 24 hours to allow full charge Less than 3 hours to 90 to 9,144 meters (30,000 feet) above sea level Less than 46 dBA C-4 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 50
    troubleshooting 5-1 authorized reseller ix B Bad Battery/Low Battery LED 2-1 batteries care and storage 4-7 charging 2-3, 4-1 determining when to replace management software 1-7 rear panels 1-4 REPO port 1-8 UPS 1-1 warranty 1-8 HP Uninterruptible Power System R1500 XR Models User Guide Index-1
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 51
    A-3 Class A equipment A-1 Class B equipment A-2 device modifications A-2 European Union A-3 HP series number A-1 identification number A-1 Japanese A-4 China Taiwan A-4 related documents viii Remote Emergency Power Off port 1-8 Index-2 HP Uninterruptible Power System R1500 XR Models User Guide
  • HP R12000XR | UPS R1500 XR Models User Guide - Page 52
    support ix telephone numbers ix temperature specifications C-4 Test/Alarm Reset button 2-2 testing batteries 4-6 tools, conductive field service Guarantee 1-8 pre-failure battery 4-7 website, HP ix weight C-1 wrist straps B-1 Index HP Uninterruptible Power System R1500 XR Models User Guide Index-3
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

HP Uninterruptible Power System
R1500 XR Models
User Guide
August 2002 (Second Edition)
Part Number 217823-002