    . HP Uninterruptible Power System R3000 XR Models Installation Instructions Second Edition (August 2002) Part Number 192130-022 Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer to the UPS user guide on the Power
  • HP R12000XR | UPS R3000 XR Models Installation Instructions - Page 2
    guide • Power Products Documentation CD • Rack and Power Management Pack CD • This document Rails • Rails, with mounting hardware • Rack template tool 2U (295523-023) UPS • UPS chassis • Battery module • Electronics module • Front bezel • Rear stabilization brackets (2) • Communications port
  • HP R12000XR | UPS R3000 XR Models Installation Instructions - Page 3
    XR-EURO, R3000i XR-SCHUKO, or R3000i XR-SA model. IMPORTANT: If the UPS does not include a power cord that is suitable for your application, contact an HP authorized service representative to obtain the appropriate power cord. Preparing for Installation Unpacking the UPS WARNING: The battery module
  • HP R12000XR | UPS R3000 XR Models Installation Instructions - Page 4
    UPS in the Rack Before attempting to install the UPS, review and adhere to all warnings provided in the "Important Safety Port The UPS includes a communications port that allows the unit to exchange data with the host computer. IMPORTANT: Power management software requires the communications port
  • HP R12000XR | UPS R3000 XR Models Installation Instructions - Page 5
    11. The REPO port allows power to the UPS output receptacles to be switched off from a remote location. To activate the REPO port: 1. Install ). 4. Replace the connector block in the REPO port. 2. Attach the grounding cable and secure the ground bonding screw. IMPORTANT: • The REPO port must meet
  • HP R12000XR | UPS R3000 XR Models Installation Instructions - Page 6
    Utility LED should be flashing green. The load segments are not energized. 15 12345 6 7 8 9 14 10 13 12 11 A 1 General Alarm 9 26% to 50% load 2 On Battery 10 0% to 25% load 3 Bad Battery 11 Configure Mode On LED 4 Site Wiring Fault Indicator 12 Configure button 5 Utility LED 13
  • HP R12000XR | UPS R3000 XR Models Installation Instructions - Page 7
    to charge before putting the UPS into service. IMPORTANT: The battery module charges to: • 90% of its capacity within 3 hours. • 100% of its capacity within 48 hours. Charge the batteries for at least 24 hours before supplying backup power to the devices. Placing the UPS in Operate Mode Press
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7

hp uninterruptible
power system
R3000 xr models
installation instructions
Read Instructions Completely
Before Beginning Installation Procedures
Hewlett-Packard Company shall not be liable for technical or editorial errors or
omissions contained herein. The information in this document is provided “as is”
without warranty of any kind and is subject to change without notice. The warranties
for HP products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an
additional warranty.
HP Uninterruptible Power System R3000 XR Models Installation Instructions
Second Edition (August 2002)
Part Number 192130-022
192130- 022
Overview
These instructions show how to install an uninterruptible power
system (UPS). For detailed information about the UPS, refer to the
UPS user guide on the Power Products Documentation CD.
Important Safety Information
Before installing this product, read the
Important Safety
Information
document provided.
WARNING:
To prevent personal injury from electric shock and
hazardous energy levels, the installation of options and routine
maintenance and service of this product must be performed by
individuals who are knowledgeable about the procedures,
precautions, and hazards associated with AC power products.
WARNING:
To prevent personal injury from earth conductor
leakage current:
Do not operate a UPS that is disconnected from the utility
power source.
Disconnect protected devices from the UPS before
disconnecting the UPS from utility power.
Use the Test/Alarm Reset button to test the batteries rather
than unplugging the UPS. Refer to the UPS user guide for
more information on the operation of the UPS.
NOTE:
The rating label on the device provides the class (A or B) of the
equipment. Class B devices have a Federal Communications Commission
(FCC) logo or FCC ID on the label. Class A devices do not have an FCC logo
or FCC ID on the label. After you determine the class of the device, refer to
the UPS user guide for complete regulatory compliance notices.
Weight
37 kg
82 lb
WARNING:
The UPS weighs 37 kg (82 lb) when fully
assembled. To prevent personal injury or damage to
the equipment:
Observe local occupational health and safety
requirements and guidelines for manual material
handling.
Obtain adequate assistance to lift and stabilize the
UPS during installation or removal. The UPS is
unstable when not fastened to the rails.
Position
WARNING:
To prevent personal injury or damage to the
equipment, take the following precautions when installing
the equipment:
The UPS must be installed at the bottom of the rack. If
placed in the rack with existing equipment, the rack
must be reconfigured to allow installation of the UPS at
the bottom of the rack.
The UPS must be mounted on the rails included in the
UPS kit. Use the rack template tool included in the kit to
align the rails.