HP R12000XR UPS R1500 XR ERM Installation Instructions

HP R12000XR Manual

HP R12000XR manual content summary:

  • HP R12000XR | UPS R1500 XR ERM Installation Instructions - Page 1
    hp ups R1500 xr models extended runtime module installation instructions Read Instructions Completely Before Beginning Installation Procedures Overview These instructions show how to install an extended runtime module (ERM). The ERM consists of two battery are no user-serviceable components inside.
  • HP R12000XR | UPS R1500 XR ERM Installation Instructions - Page 2
    HP authorized service representative for directions. NOTE: The following label is only an example date. The date on your carton may be different. THIS PRODUCT CONTAINS A NONSPILLABLE BATTERY Next Recharge Date: 14-DEC-04 Please refer to Maintenance Section of Owner's Manual unpacking instructions on
  • HP R12000XR | UPS R1500 XR ERM Installation Instructions - Page 3
    To mount the rails: 1. Loosen the wing nuts (1) and extend the brackets to the desired length (2). Tighten the wing nuts slightly to stabilize the bracket. 4. Insert at least one screw through each rack-mounting rail and into the front of each rail. 1 2 2. Use the rack template tool to measure and
  • HP R12000XR | UPS R1500 XR ERM Installation Instructions - Page 4
    screws for support if any screw service. IMPORTANT: The battery packs charge to: • 90% of their capacity within 4 hours. • 100% of their capacity within 24 hours. Charge the batteries for at least 24 hours before using them to supply power to your devices. For more information, refer to the HP
  • 1
  • 2
  • 3
  • 4

hp ups R1500 xr models
extended runtime module
installation instructions
Read Instructions Completely
Before Beginning Installation Procedures
Hewlett-Packard Company shall not be liable for technical or editorial errors or
omissions contained herein. The information in this document is provided “as is”
without warranty of any kind and is subject to change without notice. The warranties
for HP products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an
additional warranty.
HP UPS R1500 XR Models Extended Runtime Module Installation Instructions
Second Edition (August 2002)
Part Number 215856-022
215856- 022
Overview
These instructions show how to install an extended runtime
module (ERM). The ERM consists of two battery packs in a 2U
chassis. The ERM can be connected directly to a R1500 XR model
or to another ERM. Up to two ERM units can be connected.
Depending on the load, one ERM can extend the available UPS
runtime by up to 15 minutes.
Important Safety Information
Before installing this product, read the
Important Safety
Information
document provided.
WARNING:
The installation of this product must be performed by
individuals who are knowledgeable about the procedures,
precautions, and hazards associated with AC and DC power
products.
There are no user-serviceable components inside.
Weight
37 kg
82 lb
WARNING:
The ERM weighs 37 kg (82 lb) when fully
assembled. To prevent personal injury or damage to
the equipment:
Observe local occupational health and safety
requirements and guidelines for manual material
handling.
Obtain adequate assistance to lift and stabilize the
product during installation or removal. The ERM is
unstable when not fastened to the rails.
Position
WARNING:
To prevent personal injury or damage to the
equipment, take the following precautions when installing the
ERM:
The ERM must be installed at the bottom of the rack, with the
UPS on top of the ERM. If placed in the rack with existing
equipment, the rack must be reconfigured to allow
installation of the UPS and ERM at the bottom of the rack.
The ERM must be mounted on the fixed rails included in the
ERM kit. Use the rack template tool shipped with the ERM kit
to align the rails.