HP R12000XR UPS R12000 XR Models Installation Instructions

HP R12000XR Manual

HP R12000XR manual content summary:

  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 1
    . hp uninterruptible power system r12000 xr models installation instructions Second Edition (December 2002) Part Number 146305-002 146305- 002 Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer to the UPS user guide
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 2
    HP authorized service representative for directions. NOTE: The following label is only an example date. The date on your carton may be different. THIS PRODUCT CONTAINS A NONSPILLABLE BATTERY Next Recharge Date: 05-MAR-07 Please refer to Maintenance Section of Owner's Manual installation instructions
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 3
    -out tray to unload the UPS. • The battery modules are charged from the factory. Do not touch the connectors. Transport the packaged UPS to its installation location. Unpack the UPS near the rack where it will be assembled. Follow the unpacking instructions on the carton. Verify that all components
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 4
    Installing the UPS in the Rack Before attempting to install the UPS, review and adhere to all warnings provided in the "Installation Considerations" section of this document. To install with the rack. NOTE: After installing the UPS chassis, insert remaining screws for support, if any screw holes are
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 5
    type CL2, CL2P, CL2R, or CL2X, depending on the requirements of the local installation. 3. Verify that the Remote Circuit is off. Be sure the REPO switch is for the purpose of functional grounding or bonding of ungrounded metal parts. To connect the ground bonding screw: Remove the ground bonding
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 6
    WARNING: The installation of options and routine maintenance and service of this qualified electrician. • There are no user-serviceable components inside the UPS. Requirements The points for the input and output wiring (2). 1 2 1 5. Replace the wiring port cover. 6. Pull the wires through the conduit
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 7
    , bottom to top. CAUTION: Do not damage the LED power cable (1) when inserting the top battery module. 1 10. Replace the wiring port cover by first inserting the screws (1), then the single screw (2). Replace the terminal block cover (3), secure the cover (4), and insert and tighten the screws
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 8
    Inserting the Batteries Slide the batteries into the chassis (1), bottom to top, and tighten the screws (2). 2 damage to the equipment, only use the communications cables that came with the UPS kit, part number 201092-002 (12-ft serial interface cable). This UPS/computer interface cable carries power
  • HP R12000XR | UPS R12000 XR Models Installation Instructions - Page 9
    and has installed all electronics modules, turn on the AC mains at the service panel. All LEDs come on for three seconds as part of the batteries for at least 24 hours before supplying backup power to your devices. For information on operating the UPS, refer to the Operation chapter in the user guide
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9

hp uninterruptible
power system r12000
xr models
installation instructions
Read instructions completely before beginning
installation procedure.
© 2003 Hewlett-Packard Development Company, L.P.
Hewlett-Packard Company shall not be liable for technical or editorial errors or
omissions contained herein. The information in this document is provided “as is”
without warranty of any kind and is subject to change without notice. The warranties
for HP products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an
additional warranty.
hp uninterruptible power system r12000 xr models installation instructions
Second Edition (December 2002)
Part Number 146305-002
146305- 002
Overview
These instructions show how to install an uninterruptible power
system (UPS). For detailed information about the UPS, refer to the
UPS user guide on the Power Products Documentation CD.
These instructions assist qualified personnel with the installation of
the HP UPS. Save these instructions for future reference.
Use the UPS R12000 XR Installation and Startup Package to
facilitate the installation and startup of the UPS.
Table 1:
Installation and Startup Package Numbers
Location
Package Number
United States
FM-BPINS-IN
Worldwide
FP-UPSXR-IN
Important Safety Information
Before installing this product, read the
Important Safety
Information
guide included with the UPS kit.
Regulatory Compliance
Information Numbers
For regulatory compliance certifications and identification
purposes, the UPS models are assigned a series number, also
identified on the Regulatory Compliance label located on the side
of the UPS. For certification information, always refer to the series
number EO3002 and PDU series number EO3024.
NOTE:
The rating label on the device provides the class (A or B) of the
equipment. Class B devices have a Federal Communications Commission
(FCC) logo or FCC ID on the label. Class A devices do not have an FCC logo
or FCC ID on the label. After you determine the class of the device, refer to
the UPS user guide for complete regulatory compliance notices.
Installation Considerations
Weight
190 kg
420 lb
WARNING:
To reduce the risk of personal injury or
damage to the equipment:
Have the floor-loading requirements evaluated by a
facilities engineer before installation.
Observe local occupational health and safety
requirements and guidelines for manual material
handling.
Obtain adequate assistance to lift and stabilize the
product during installation or removal. The UPS
will be unstable when not fastened to the rails.
Remove all batteries and electronics modules to
reduce the overall weight of the UPS chassis.
Use three people to lift and place the UPS in the
rack.
Table 2:
Component Weights
Component
Weight
Chassis
43 kg (95 lb)
Electronics modules (4)
9.5 kg (21 lb) each
Battery modules (4)
27 kg (60 lb) each
Fully assembled UPS
190 kg (420 lb)