HP R12000XR UPS R6000 ERM Installation Instructions

HP R12000XR Manual

HP R12000XR manual content summary:

  • HP R12000XR | UPS R6000 ERM Installation Instructions - Page 1
    instructions Second Edition (December 2002) Part Number 347219-002 About This Device These instructions user-serviceable components of the device, refer to the UPS user guide for complete regulatory compliance notices. Weight 69 kg requirements and guidelines for manual material handling. • Obtain
  • HP R12000XR | UPS R6000 ERM Installation Instructions - Page 2
    being recharged, contact an HP authorized service representative for directions. NOTE: The following Documentation • Important Safety Information guide • International Regulatory Compliance guide • This document Rails • it will be assembled, following the instructions on the carton. Verify that all
  • HP R12000XR | UPS R6000 ERM Installation Instructions - Page 3
    To mount the rails: 1. Loosen the wing nuts (1) and extend the brackets to the desired length (2). Tighten the wing nuts slightly to stabilize the bracket. 4. Insert at least one screw through each rack-mounting rail and into the front of each rail. 2. Use the rack template tool to measure and
  • HP R12000XR | UPS R6000 ERM Installation Instructions - Page 4
    nuts supplied with the rack. NOTE: After installing the ERM chassis, insert remaining screws for additional support, if any screw holes are unoccupied. WARNING: To prevent personal injury, make sure that the battery Use the screw that was removed in step 7. 6. Place the UPS in Manual Bypass mode.
  • HP R12000XR | UPS R6000 ERM Installation Instructions - Page 5
    Completing the ERM Assembly Installing and Connecting the Battery Packs 1. Slide the battery packs into the chassis. 4. Connect the cables. IMPORTANT: Leave the battery circuit breaker in the off position. 2. For each battery pack: a. Take out the connector cover screw (1). b. Remove the connector
  • HP R12000XR | UPS R6000 ERM Installation Instructions - Page 6
    Setting up the UPS Refer to the user guide for information on setting up the UPS to recognize the ERM. Charging the Batteries With the UPS in Standby mode, allow the ERM batteries to charge before placing the UPS into service. IMPORTANT: The battery packs charge to: • 90% of their capacity within 4
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6

hp ups r6000 models
extended runtime
module
installation instructions
Read instructions completely before beginning
installation procedure.
© 1998, 2002 Hewlett-Packard Development Company, L.P.
Hewlett-Packard Company shall not be liable for technical or editorial errors or
omissions contained herein. The information in this document is provided “as is”
without warranty of any kind and is subject to change without notice. The warranties
for HP products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an
additional warranty.
hp ups r6000 models extended runtime module installation instructions
Second Edition (December 2002)
Part Number 347219-002
347219- 002
About This Device
These instructions show how to install an extended runtime
module (ERM). The ERM consists of two battery packs in a
3U chassis. The ERM can be connected directly to an R6000
model or to another ERM. Up to two ERM units can be connected.
Depending on the load, one ERM can extend the available UPS
runtime by up to 15 minutes.
Important Safety Information
Before installing this product, read the
Important Safety
Information
document provided.
WARNING:
The installation of this product must be performed by
individuals who are knowledgeable about the procedures,
precautions, and hazards associated with AC and DC power
products.
There are no user-serviceable components inside.
Regulatory Compliance Identification
Numbers
For regulatory compliance certifications and identification
purposes, the units are assigned a series number, also identified on
the Regulatory Compliance label located on the side of the ERM.
For certification information, always refer to the series number
EO3001B.
NOTE:
The rating label on the device provides the class (A or B) of the
equipment. Class B devices have a Federal Communications Commission
(FCC) logo or FCC ID on the label. Class A devices do not have an FCC logo
or FCC ID on the label. After you determine the class of the device, refer to
the UPS user guide for complete regulatory compliance notices.
Weight
69 kg
150 lb
WARNING:
The ERM weighs 69 kg (150 lb) when fully
assembled. To prevent personal injury or damage to
the equipment:
Observe local occupational health and safety
requirements and guidelines for manual material
handling.
Obtain adequate assistance to lift and stabilize the
product during installation or removal. The ERM is
unstable when not fastened to the rails.
Position
WARNING:
To prevent personal injury or damage to the
equipment, take the following precautions when installing the
ERM:
The ERM must be installed at the bottom of the rack, with the
UPS on top of the ERM. If placed in the rack with existing
equipment, the rack must be reconfigured to allow
installation of the UPS and ERM at the bottom of the rack.
The ERM must be mounted on the fixed rails included in the
ERM kit. Use the rack template tool shipped with the ERM kit
to align the rails.