    . hp uninterruptible power system R6000 models installation instructions Second Edition (December 2002) Part Number 347222-003 About This Device These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer to the UPS user guide on
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 2
    Regulatory Compliance guide • Important Safety Information guide • Power Products Documentation CD • Rack and Power Management Pack CD • This document Rails • Rails, with mounting hardware • Rack template tool 6U (347221-022) UPS • UPS chassis (with electronics module) • Battery modules (2) • Two
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 3
    To mount the rails: 1. Loosen the wing nuts (1) and extend the brackets to the desired length (2). Tighten the wing nuts slightly to stabilize the bracket. 4. Insert the screws supplied in the UPS kit through each
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 4
    REPO circuit is an IEC950 Secondary Extra Low Voltage (SELV) circuit. The server room Emergency Power shutdown circuit conductors that connect to the power products. • The UPS must be connected directly to the AC branch circuit (AC mains) by a qualified electrician. • There are no user-serviceable
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 5
    • Single phase • 50-60 Hz NOTE: For ease of service and maintenance, use flexible metal conduit when hardwiring the UPS. Replace the input terminal block cover. Completing the UPS Assembly Installing and Connecting the Battery Modules WARNING: To prevent personal injury, be sure that the battery
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 6
    chassis. 5. Connect the cables. 3. For each battery module: a. Take out the connector cover screw (1). b. Remove the connector cover (2) and discard. c. Replace the connector cover screw to secure sheet metal. NOTE: When attaching battery cable connectors, the connectors will provide a positive
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 7
    only the specific cable supplied with the UPS to connect the communications port to the host computer. NOTE: If optional extended runtime modules (ERMs) are attached, place the ERM battery circuit breakers in the On position after the UPS circuit breaker is placed in the On position. 5. Attach the
  • HP R12000XR | UPS R6000 Models Installation Instructions - Page 8
    to charge before putting the UPS into service. IMPORTANT: The battery modules charge to: • 90% of their capacity within 3 hours • 100% of their capacity within 48 hours Charge the batteries for at least 24 hours before supplying backup power to the devices. Placing the UPS in Operate Mode Press
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

hp uninterruptible
power system R6000
models
installation instructions
Read instructions completely before beginning
installation procedure.
© 1999, 2002 Hewlett-Packard Development Company, L.P.
Hewlett-Packard Company shall not be liable for technical or editorial errors or
omissions contained herein. The information in this document is provided “as is”
without warranty of any kind and is subject to change without notice. The warranties
for HP products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an
additional warranty.
hp uninterruptible power system R6000 models installation instructions
Second Edition (December 2002)
Part Number 347222-003
347222- 003
About This Device
These instructions show how to install an uninterruptible power
system (UPS). For detailed information about the UPS, refer to the
UPS user guide on the Power Products Documentation CD.
Important Safety Information
Before installing this product, read the
Important Safety
Information
guide included with the UPS kit.
Regulatory Compliance Identification
Numbers
For regulatory compliance certifications and identification
purposes, the UPS models are assigned a series number, also
identified on the Regulatory Compliance label located on the side
of the UPS. For certification information, always refer to the series
number EO3001.
NOTE:
The rating label on the device provides the class (A or B) of the
equipment. Class B devices have a Federal Communications Commission
(FCC) logo or FCC ID on the label. Class A devices do not have an FCC logo
or FCC ID on the label. After you determine the class of the device, refer to
the UPS user guide for complete regulatory compliance notices.
Weight
136 kg
300 lb
WARNING:
The UPS weighs 136 kg (300 lb) when fully
assembled. To prevent personal injury or damage to the
equipment:
Observe local occupational health and safety
requirements and guidelines for manual material
handling.
Obtain adequate assistance to lift and stabilize the
product during installation or removal. The UPS is
unstable when not fastened to the rails.
Remove the battery module to reduce the overall
weight of the product.
Position
WARNING: To prevent personal injury or damage to the
equipment, take the following precautions when installing the
equipment:
The UPS must be installed at the bottom of the rack. If
placed in the rack with existing equipment, the rack must be
reconfigured to allow installation of the UPS at the bottom
of the rack.
The UPS must be mounted on the rails included in the UPS
kit. Use the rack template tool included in the kit to align
the rails.