HP R12000XR HP UPS Network Module User Guide

HP R12000XR Manual

HP R12000XR manual content summary:

  • HP R12000XR | HP UPS Network Module User Guide - Page 1
    UPS Network Module User Guide Abstract This document includes installation, configuration, and operation information for the HP UPS Network Module. This document is for the person who installs and maintains power products. HP assumes you are qualified in the servicing of high-voltage equipment and
  • HP R12000XR | HP UPS Network Module User Guide - Page 2
    to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors
  • HP R12000XR | HP UPS Network Module User Guide - Page 3
    Introduction ...6 Overview ...6 Features ...6 HP Power Protector overview ...7 Supported hardware configurations ...7 Configuration A Chrome 19 Navigating the web interface...19 Views ...19 Power Source screen...20 Manual Control screen ...25 Logs ...26 UPS Data Log screen...26 Event Log screen
  • HP R12000XR | HP UPS Network Module User Guide - Page 4
    HP UPS Network Module Configuration Menu 48 HP UPS Network Module Configuration Menu overview 48 Accessing the Service parameters ...76 Troubleshooting ...78 Client communication failure with HP UPS Network Module 79 Support and other resources ...80 Before you contact HP...80 HP contact
  • HP R12000XR | HP UPS Network Module User Guide - Page 5
    Acronyms and abbreviations...82 Documentation feedback ...84 Index...85 Contents 5
  • HP R12000XR | HP UPS Network Module User Guide - Page 6
    Configuration Menu (on page 48)-A text-based menu that is accessed through a terminal emulation session For a detailed list of supported UPSs, see the HP website (http://www.hp.com/go/rackandpower). Features The UPS Network Module is a minislot card that requires UPSs equipped with a minislot. The
  • HP R12000XR | HP UPS Network Module User Guide - Page 7
    script. • Provides redundancy feature support. • Is compatible with the R1500 G3 UPS, R/T3000 G2 UPS, R5000 UPS and R7000 UPS. For more information, see the HP Power Protector User Guide on the HP website (http://www.hp.com/go/rackandpower). HP Power Protector overview HP Power Protector is a UPS
  • HP R12000XR | HP UPS Network Module User Guide - Page 8
    UPS Network Module HPPP Client server HPPP Client server HPPP Client server Network Remote workstation browsing into the HP UPS Network Module or HPPP Client over the network Power connection Communication path Configuration B This figure illustrates one or more HPPP Clients are redundantly powered
  • HP R12000XR | HP UPS Network Module User Guide - Page 9
    interface. Software Internet Explorer Mozilla Firefox Google Browser • Windows Internet Explorer 7 • Windows Internet Explorer 8 • Windows Internet Explorer 9 HP-UX Mozilla 1.4.x • Linux Firefox 3.5.x (native to Linux version) • Windows Firefox 3.6.15 • Windows Firefox 4 Chrome 10.x Introduction
  • HP R12000XR | HP UPS Network Module User Guide - Page 10
    servers, they are automatically added by the UPS Network Module and appear on the Notified Applications screen (on page 42). For more information, see the HP Power Protector User Guide on the HP website (http://www.hp.com/go/rackandpower). Introduction 10
  • HP R12000XR | HP UPS Network Module User Guide - Page 11
    Component identification Front panel connectors and LED indicators Item 1 2 3 4 5 6 Connector/LED Network connector Network Activity LED Network Speed LED Settings/AUX connector UPS Data LED Configuration Menu LED Description Ethernet port • Off-UPS Network Module not connected to the network •
  • HP R12000XR | HP UPS Network Module User Guide - Page 12
    the HP UPS Network Module Precautions See the Important Safety Information guide (included in the UPS kit) before installing this product. WARNING: A risk of personal injury from electric shock and hazardous energy levels exists. The installation of options and routine maintenance and service of
  • HP R12000XR | HP UPS Network Module User Guide - Page 13
    interface. The UPS Network Module also uses the network connection to communicate to the configured HPPP Clients and to facilitate SNMP-based monitoring. Installing the HP UPS Network Module 13
  • HP R12000XR | HP UPS Network Module User Guide - Page 14
    appears. 5. Select the following parameter values, and then click OK. o Bits per second-9600 o Data bits-8 o Parity-None o Stop bits-1 o Flow control-None Installing the HP UPS Network Module 14
  • HP R12000XR | HP UPS Network Module User Guide - Page 15
    the prompt, enter admin. The HP UPS Network Module Configuration Menu appears. Use the HP UPS Network Module Configuration Menu to submenu. b. Enter 2 to modify the network settings. c. Follow the on-screen instructions to enter the static IP parameters. A Done message appears when the parameters are
  • HP R12000XR | HP UPS Network Module User Guide - Page 16
    the UPS Network Module web interface can also be configured using the HP UPS Network Module Configuration Menu (on page 48). Accessing the web network. To access the web interface: 1. On a network computer, launch a supported browser. The browser window appears. 2. In the URL field, enter: http://xxx
  • HP R12000XR | HP UPS Network Module User Guide - Page 17
    5. Click Sign In. The HP UPS Network Module web interface appears. Browser security alert Secure browsing requires the use of SSL. SSL is a protocol 1. Click View Certificate. 2. Verify that the name in the Issued To field is the name of your UPS Network Module. HP UPS Network Module web interface 17
  • HP R12000XR | HP UPS Network Module User Guide - Page 18
    an exported certificate file from the administrator. NOTE: If using Internet Explorer, you can manually import the file into the browser by clicking Tools>Internet Options>Content>Certificates>Import. necessary to verify the identity of the UPS Network Module. HP UPS Network Module web interface 18
  • HP R12000XR | HP UPS Network Module User Guide - Page 19
    temporarily for this session. b. Click OK. NOTE: If using Firefox, you can manually import the file into the browser by clicking Edit>Preferences>Advanced>Security>View Certificates>Authorities> view online help. Views Menu options listed under Views include: HP UPS Network Module web interface 19
  • HP R12000XR | HP UPS Network Module User Guide - Page 20
    • Power Source ("Power Source screen" on page 20) • Manual Control ("Manual Control screen" on page 25) Power Source screen Click Power Source in the menu tree to the UPS is lost, the diagram appears gray. Diagrams do not display for line-interactive UPSs. HP UPS Network Module web interface 20
  • HP R12000XR | HP UPS Network Module User Guide - Page 21
    the UPS operating mode diagram to display UPS data details. UPS data is available for Normal mode, Battery mode, and Bypass mode. The available UPS data depends on the UPS range. Available UPS information -In tolerance Gray-Out of tolerance AC Normal Flow HP UPS Network Module web interface 21
  • HP R12000XR | HP UPS Network Module User Guide - Page 22
    > 50% Orange-Remaining capacity < 50% Battery Output Flow Red-Battery to be checked (battery test result) Yellow-AC to DC converter powered by battery DC to AC Converter Input Flow Gray-AC In tolerance AC Automatic Bypass Flow Red-Out of tolerance HP UPS Network Module web interface 22
  • HP R12000XR | HP UPS Network Module User Guide - Page 23
    utility power or running on the UPS battery • Output load level-The power percentage Battery capacity-The remaining percentage of battery charge and the battery status: o Charging-Utility power is present and the battery charge is in progress o Discharging-The UPS is operating on battery power HP
  • HP R12000XR | HP UPS Network Module User Guide - Page 24
    OK-The test completed correctly. o NOK-The battery needs to be checked. o Deactivated-The automatic battery test was not validated on the UPS. o Aborted-The automatic battery test was not completed on the UPS. UPS Speed-The port speed of the UPS Network Module HP UPS Network Module web interface 24
  • HP R12000XR | HP UPS Network Module User Guide - Page 25
    in the menu tree to display the Manual Control screen. This screen allows an administrator to execute shutdown and restart sequences for the UPS and its the Off Delay time is reached. Connected equipment powers off, and then the load segment powers off. HP UPS Network Module web interface 25
  • HP R12000XR | HP UPS Network Module User Guide - Page 26
    every 60 seconds. NOTE: In the UPS Data Log and the Event Log, the date and time stamps are converted to the local time zone. HP UPS Network Module web interface 26
  • HP R12000XR | HP UPS Network Module User Guide - Page 27
    Output Load level (%)-The percentage of load at the UPS output • Battery Capacity (%)-The percentage of battery charge available • Battery Remaining time (min)-The estimated remaining backup time NOTE: When the can clear logs. • Click Help to view online help. HP UPS Network Module web interface 27
  • HP R12000XR | HP UPS Network Module User Guide - Page 28
    screen displays a log of the events that have occurred on the UPS, such as the UPS switching to battery power. NOTE: In the UPS Data Log and the Event Log, the date and time stamps are administrator privileges can clear logs. • Click Help to view online help. HP UPS Network Module web interface 28
  • HP R12000XR | HP UPS Network Module User Guide - Page 29
    34) • Shutdown Parameters ("Shutdown Parameters screen" on page 35) • Scheduled Shutdown ("Scheduled Shutdown screen" on page 39) • SNMP Settings ("SNMP Settings screen" on page 40) HP UPS Network Module web interface 29
  • HP R12000XR | HP UPS Network Module User Guide - Page 30
    the Keep TCP/IP parameters checkbox, and then click Factory Reset. The configured IP address, subnet mask, gateway, and BOOTP/DHCP parameters are not reset. HP UPS Network Module web interface 30
  • HP R12000XR | HP UPS Network Module User Guide - Page 31
    a web browser. Enter the first administrator account login username and password in HPPP Clients > Device Discovery > Configure Power Source to access HP UPS Network Module. The second and third accounts can be enabled or disabled by the administrator. To configure the administrator account that
  • HP R12000XR | HP UPS Network Module User Guide - Page 32
    the gateway address of the UPS Network Module in the Gateway Address field to allow connection to devices or hosts attached to different network segments. HP UPS Network Module web interface 32
  • HP R12000XR | HP UPS Network Module User Guide - Page 33
    sure to reboot the UPS Network Module by clicking Reset Communication on the System Settings screen (on page 30). Click Help to view online help. HP UPS Network Module web interface 33
  • HP R12000XR | HP UPS Network Module User Guide - Page 34
    and time appears at the top of the screen. To manually enter the date and time: 1. Select the Set manually radio button. 2. Enter the date (yyyy/mm/dd) the first Client that responds. 1. Select the Accept automatic update from HP Power Protector radio button. 2. Click Save. To synchronize the date
  • HP R12000XR | HP UPS Network Module User Guide - Page 35
    for each load segment. Settings for the entire UPS apply to all load segments. Settings for individual load segments only apply to that load segment. HP UPS Network Module web interface 35
  • HP R12000XR | HP UPS Network Module User Guide - Page 36
    Enter a shorter delay for load segments that power less critical equipment to preserve UPS battery power for other load segments. The value you enter is continually compared with the maximum down as late as possible without performing a graceful shutdown. HP UPS Network Module web interface 36
  • HP R12000XR | HP UPS Network Module User Guide - Page 37
    ), enter the minimum amount of battery life that can remain before the load segment shutdown sequence starts (0 to 100%, 20% by default). The UPS Network Module initiates a load segment shutdown when the remaining battery life reaches the specified percentage. HP UPS Network Module web interface 37
  • HP R12000XR | HP UPS Network Module User Guide - Page 38
    Battery capacity Time Utility failure Shutdown initiated Load segment powered down Low battery Battery automatically used. When one of the On Battery triggers is reached, the shutdown sequence starts Restart if battery capacity exceeds field (entire UPS), enter the percentage of battery charge that
  • HP R12000XR | HP UPS Network Module User Guide - Page 39
    an Existing Scheduled Shutdown Settings screen appears. o In the Selected column, select a scheduled shutdown that you want to remove, and then click Delete Scheduled Shutdown. HP UPS Network Module web interface 39
  • HP R12000XR | HP UPS Network Module User Guide - Page 40
    SNMP in the menu tree to display the SNMP Settings screen. This screen allows an administrator to configure SNMP settings for computers that use the HP Power MIB to request information from the UPS Network Module
  • HP R12000XR | HP UPS Network Module User Guide - Page 41
    To configure the SNMP settings: 1. Select the SNMP version supported by the UPS Network Module from the Version pull-down menu. Available options are Disabled, V1, 8 and 24 alphanumeric characters and the symbols. 4. Click Save. Click Help to view online help. HP UPS Network Module web interface 41
  • HP R12000XR | HP UPS Network Module User Guide - Page 42
    Settings screen (on page 44) Applications appear in the order in which they subscribe to the UPS Network Module. SNMP management applications, such as HP Systems Insight Manager, can receive notifications from the UPS Network Module. • Output-The name of the UPS load segment from which the Client is
  • HP R12000XR | HP UPS Network Module User Guide - Page 43
    3. Verify that the selected application received the traps over the network. To simulate a UPS On Battery condition: 1. Select the checkbox for the application you want to test. To select all applications, is working correctly. Click Help to view online help. HP UPS Network Module web interface 43
  • HP R12000XR | HP UPS Network Module User Guide - Page 44
    traps from the UPS Network Module. To configure an application to receive SNMP traps: 1. Enter the name of the application in the Application Name field. HP recommends adding "SNMP" or "Trap" to the name to for easy monitoring. 2. Enter the host name or the IP address of the management server on
  • HP R12000XR | HP UPS Network Module User Guide - Page 45
    text messaging. The required format might vary, depending on the cellular service provider. Contact your cellular service provider for mail to SMS gateway settings. Up to four recipients email address: 1. Select the address for the recipient you want to disable. HP UPS Network Module web interface 45
  • HP R12000XR | HP UPS Network Module User Guide - Page 46
    geographic location of the UPS in the email subject when selected o Event message-Identifies the event generating the message in the email subject when selected HP UPS Network Module web interface 46
  • HP R12000XR | HP UPS Network Module User Guide - Page 47
    format might vary, depending on the cellular service provider. Contact your cellular service provider for mail to SMS gateway settings. To upgrade the firmware: 1. Download the latest firmware version from the HP website (http://www.hp.com/go/rackandpower). 2. Click Browse. 3. Navigate to the folder
  • HP R12000XR | HP UPS Network Module User Guide - Page 48
    Configuration Menu can also be configured using the HP UPS Network Module web interface. Accessing the Service Menu You can access the Configuration Menu to enter the password. 2. At the prompt, enter admin. The HP UPS Network Module Configuration Menu appears. Navigating the menus After you
  • HP R12000XR | HP UPS Network Module User Guide - Page 49
    settings for the UPS Network Module Enables you to configure the port speed for the RJ-45 Ethernet network connector Returns to the previous menu HP UPS Network Module Configuration Menu 49
  • HP R12000XR | HP UPS Network Module User Guide - Page 50
    web interface of the module in context. For example, if the UPS Network Module detects an alarm condition, the module can send a trap to HP SIM with an attached hyperlink that routes users directly to the web interface for the attached UPS. • Conveniently launch the UPS Network Module web interface
  • HP R12000XR | HP UPS Network Module User Guide - Page 51
    enabled by default. # To remove them from the discovery process, comment out the line with a '#' # or remove it. You will need to restart the HP SIM service for # the changes to take effect. In addition you will need to run the Device # Identification task to find any new ports that were defined
  • HP R12000XR | HP UPS Network Module User Guide - Page 52
    NOTE: For more information on uploading and registering a MIB in HP SIM, refer to the HP Systems Insight Manager Technical Reference Guide located on the HP Management CD. Configuring the UPS Network Module to send traps to HP SIM Add the HP SIM server as an SNMP trap recipient on the Trap Receivers
  • HP R12000XR | HP UPS Network Module User Guide - Page 53
    Optional power monitoring using SNMP SNMP monitoring Battery status, power status, events, and traps can be monitored using third-party SNMP managers. SNMP monitoring supports the RFC-1628 MIB and the HP Power MIB (CPQPOWER.MIB). To query SNMP data, you do not need to add SNMP Mangers to the
  • HP R12000XR | HP UPS Network Module User Guide - Page 54
    with the longest Operating system shutdown time. Otherwise, it is automatically replaced by the longest Operating system shutdown time when the Client is connected as the Remaining backup time under or the Battery capacity under conditions, the UPS Network Module starts the shutdown process
  • HP R12000XR | HP UPS Network Module User Guide - Page 55
    segment 2 UPS Network Module setting for load segment 2 Load segment 2 UPS On utility On battery (Shutdown initiated after time) Operating system shutdown time Utility failure-UPS is on battery, and all servers are powered as usual Shutdown process initiated-Shutdown scripts run, applications close
  • HP R12000XR | HP UPS Network Module User Guide - Page 56
    Because the Operating system shutdown time of this Client is the longest, it replaced the Operating system shutdown time of the UPS Network Module after it was is restored, the example UPS behaves as follows: 1. t5-If the Battery capacity exceeds condition exists, the UPS is powered up. 2. t6 and t7
  • HP R12000XR | HP UPS Network Module User Guide - Page 57
    . 5. Launch a terminal emulation program, such as HyperTerminal ("Launching a terminal emulation program" on page 14). The following menu appears HP NETWORK MANAGEMENT CARD BOOTLOADER VERSION : 1.1 RAM autotest in progress. RAM autotest SUCCESS. Commercial reference : 66102 Kitting technical level
  • HP R12000XR | HP UPS Network Module User Guide - Page 58
    Module: • 4679/UDP and TCP (Client) • 4680/UDP and TCP (Client) • 5000/TCP (Alarms) • 5001/TCP (Alarms) To configure the Windows XP with Service Pack 2 Firewall to make an exception for ports 4679, 4680, 5000, and 5001: 1. Click Start, select Control Panel, and then double-click Network Connections
  • HP R12000XR | HP UPS Network Module User Guide - Page 59
    3. Click the Advanced tab. 4. In the Windows Firewall box, click Settings. The Windows Firewall screen appears. 5. On the General tab, verify that the Windows Firewall is enabled (On) and that the Don't allow exceptions checkbox is not checked. Firewall configuration 59
  • HP R12000XR | HP UPS Network Module User Guide - Page 60
    6. Click OK. 7. On the network Properties screen, click the Exceptions tab. 8. Be sure that the File and Printer Sharing check box is selected. Firewall configuration 60
  • HP R12000XR | HP UPS Network Module User Guide - Page 61
    9. Click Add Port to allow communication through ports 4679, 4680, 5000, and 5001. The Add a Port screen appears. 10. Enter a name for the HPPP Client port in the Name field. 11. Enter 4679, 4680, 5000, or 5001 in the port number field. 12. Select the appropriate radio button. Firewall configuration
  • HP R12000XR | HP UPS Network Module User Guide - Page 62
    13. Click Change scope to add more security to the port exception. Firewall configuration 62
  • HP R12000XR | HP UPS Network Module User Guide - Page 63
    Firewall configuration 63
  • HP R12000XR | HP UPS Network Module User Guide - Page 64
    The Change Scope screen appears. 14. Select the Custom list radio button, and then add the IP addresses that are allowed to communicate through the specified port. Firewall configuration 64
  • HP R12000XR | HP UPS Network Module User Guide - Page 65
    15. Click OK to save the scope settings. 16. On the Edit a Port screen, click OK to finish adding the exception port. The Windows Firewall screen displays the newly added HPPP Client port. 17. Click OK. NOTE: Software that helps to protect your computer and blocks access on the network, such as
  • HP R12000XR | HP UPS Network Module User Guide - Page 66
    Firewall configuration 66
  • HP R12000XR | HP UPS Network Module User Guide - Page 67
    the UPS Network Module can be done using SSL, which encrypts the data between the browser and UPS Network Module. The UPS Network Module is supported by a 128-bit encryption level. SSL also provides authentication of the UPS Network Module by means of its digital certificate. Securely importing this
  • HP R12000XR | HP UPS Network Module User Guide - Page 68
    Battery Charger Failure Cleared • UPS Battery Discharged • UPS Battery Discharged Cleared • UPS Battery Disconnected • UPS Battery Disconnected Cleared • UPS Battery Low • UPS Battery Low Cleared • UPS Battery Over Voltage • UPS Battery Over Voltage Cleared • UPS Battery Test Failure • UPS Battery
  • HP R12000XR | HP UPS Network Module User Guide - Page 69
    • UPS Client Communication Restored • UPS DC Bus High Negative Voltage • UPS DC Bus High Negative Voltage Cleared • UPS DC Bus High Positive Voltage • UPS DC Bus High Positive Voltage Cleared • UPS DC Bus Low Negative Voltage • UPS DC Bus Low Negative Voltage Cleared • UPS DC Bus Low Positive
  • HP R12000XR | HP UPS Network Module User Guide - Page 70
    3 Is On • UPS On Auto Bypass • UPS On Auto Bypass Cleared • UPS On Battery • UPS On Battery Cleared • UPS On Boost • UPS On Boost Cleared • UPS On Buck • UPS On Buck Cleared • UPS On Manual Bypass • UPS On Manual Bypass Cleared • UPS Output Is Off • UPS Output Is On • UPS Output Overload • UPS
  • HP R12000XR | HP UPS Network Module User Guide - Page 71
    • UPS Site Wiring Fault • UPS Site Wiring Fault Cleared Alert messages 71
  • HP R12000XR | HP UPS Network Module User Guide - Page 72
    in {time} UPS Shutdown Pending UPS Battery Disconnected UPS Battery Disconnected Cleared UPS Battery Discharged Cleared UPS Battery Discharged UPS Battery Over Voltage Cleared UPS Battery Over Voltage UPS Battery Charger Failure Cleared UPS Battery Charger Failure UPS ABM Controller Disabled UPS
  • HP R12000XR | HP UPS Network Module User Guide - Page 73
    Bypass Cleared UPS On Auto Bypass UPS Bypass Voltage Out Of Range Cleared UPS Bypass Voltage Out Of Range UPS On Manual Bypass Cleared UPS On Manual Bypass UPS In High Efficiency Mode UPS Inverter Failure Cleared UPS Inverter Failure UPS Inverter Overload Cleared UPS Inverter Overload UPS Inverter
  • HP R12000XR | HP UPS Network Module User Guide - Page 74
    Cleared UPS Fan Failure UPS Output Is Off UPS Output Is On UPS Internal Failure Cleared UPS Internal Failure UPS Battery Test Failure Cleared UPS Battery Test Failure UPS Output Overload Cleared UPS Output Overload UPS Over Temperature Cleared UPS Over Temperature UPS Shutdown Imminent Cleared
  • HP R12000XR | HP UPS Network Module User Guide - Page 75
    User name and password SSL 3.0, TLS 1.0 Microsoft® Internet Explorer 6.x or higher HP Systems Insight Manager Standard IETF UPS MIB (RFC 1628) HP Power MIB (cpqpower.mib) DHCP enabled IP address: 192.168.1.2 (manual configuration) Subnet mask: 255.255.0.0 Gateway: 0.0.0.0 NTP server: pool.ntp.org
  • HP R12000XR | HP UPS Network Module User Guide - Page 76
    , Authentication&Privacy writeuser 8 characters minimum, 24 characters maximum - - Accept automatic update from Synchronize with an NTP server, Accept HP Power Protector automatic update from HP Power Protector, Synchronize manually ntpserver 49 characters maximum - - Specifications 76
  • HP R12000XR | HP UPS Network Module User Guide - Page 77
    Parameter Speed Data bits Stop bits Parity Flow control Default value 9600 baud 8 1 without without Possible value Not configurable Not configurable Not configurable Not configurable Not configurable Specifications 77
  • HP R12000XR | HP UPS Network Module User Guide - Page 78
    Troubleshooting Client communication failure with HP UPS Network Module in a VMware operating the Client on the guest operating system. When the Client receives a shutdown notification from the HP UPS Network Module, it sends an operating system shutdown command to the VMware host operating system
  • HP R12000XR | HP UPS Network Module User Guide - Page 79
    time value might be configured as less than the Shutoff time value. Action: Configure the Restart time to a greater value than the Shutoff time value. Troubleshooting 79
  • HP R12000XR | HP UPS Network Module User Guide - Page 80
    HP iLO 4 User Guide or HP Intelligent Provisioning User Guide on the HP website (http://www.hp.com/go/ilo/docs). • Onboard Administrator SHOW ALL report (for HP Care Pack (service upgrade), see the Support & Drivers website (http://www8.hp.com/us/en/support-drivers.html). If the problem cannot be
  • HP R12000XR | HP UPS Network Module User Guide - Page 81
    and Options (http://www.hp.com/support/ProLiantServers-Warranties) HP Enterprise Servers (http://www.hp.com/support/EnterpriseServers-Warranties) HP Storage Products (http://www.hp.com/support/Storage-Warranties) HP Networking Products (http://www.hp.com/support/Networking-Warranties) Regulatory
  • HP R12000XR | HP UPS Network Module User Guide - Page 82
    AC alternating current BOOTP Bootstrap Protocol DC domain controller DHCP Dynamic Host Configuration Protocol DNS domain name system HPPP HP Power Protector HTTPS hypertext transfer protocol secure sockets IPv4 Internet Protocol version 4 IPv6 Internet Protocol version 6 kVA kilovolt-ampere
  • HP R12000XR | HP UPS Network Module User Guide - Page 83
    NTP network time protocol SIM Systems Insight Manager SMS short message service SSL Secure Sockets Layer TFTP Trivial File Transfer Protocol UDP User Datagram Protocol UPS uninterruptible power system USB universal serial bus Acronyms and abbreviations 83
  • HP R12000XR | HP UPS Network Module User Guide - Page 84
    documentation that meets your needs. To help us improve the documentation, send any errors, suggestions, or comments to Documentation Feedback (mailto:[email protected]). Include the document title and part number, version number, or the URL when submitting your feedback. Documentation feedback 84
  • HP R12000XR | HP UPS Network Module User Guide - Page 85
    11 G Google Chrome, secure session 19 H hardware installation 12 hardware supported 7 HP Power Protector overview 7 HP Systems Insight Manager overview 50 HP UPS Network Module Configuration Menu 48 HP UPS Network Module overview 6 I installation precautions 12 installing hardware 12 installing
  • HP R12000XR | HP UPS Network Module User Guide - Page 86
    troubleshooting 78 log files 28, 29 logging in, through a browser 16 Logs tab 26 M mail server, setting up 32 main menu 48 Manual HP Power Protector 7 overview, HP UPS Network Module 6 overview, web interface 16 P password, changing 31 Power Source screen 20 problem alert 17 supported hardware
  • HP R12000XR | HP UPS Network Module User Guide - Page 87
    V views 19 W web interface requirements 9 web interface, accessing 16 web interface, overview 16 web interface, using and navigating 19 Index 87
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87

HP UPS Network Module
User Guide
Abstract
This document includes installation, configuration, and operation information for the HP UPS Network Module. This document is for the person who
installs and maintains power products. HP assumes you are qualified in the servicing of high-voltage equipment and trained in recognizing hazards
in products with hazardous energy levels.
Part Number: 637918-003
June 2013
Edition: 3