- HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 1
Site Preparation Guide hp rp7405/rp7410 Servers Second Edition Manufacturing Part Number: A6752-96009 21102 USA © Copyright 2002 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 2
The information in this document is subject to change without notice. Hewlett-Packard makes no warranty of any kind with regard to this manual, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Hewlett-Packard shall not be held liable for - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 3
Ducts 21 Dust and Pollution Control 21 Electrostatic Discharge (ESD) Prevention 22 Acoustics 22 Computer Room Safety 24 Fire Protection 24 Lighting Requirements for Equipment Servicing 24 iii - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 4
Contents Facility Characteristics 25 Floor Loading 25 Windows 27 Space Requirements 28 Delivery Space Requirements 28 Operational Space Requirements 28 Zinc Particle Contamination 30 3. Pre-installation Survey Pre-installation Survey Content 32 Typical Installation Schedule 33 Site - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 5
viii Table 1-1. hp rp7405/rp7410 Server Dimensions and Weights 2 Table 1-2. hp rp7405/rp7410 Component Weights 2 Table 1-3. Power Cords 3 Table 1-4. AC Power Specifications 4 Table 1-5. AC Frequency Specifications 4 Table 1-6. Typical hp rp7405/rp7410 Configurations 7 Table 2-1. Computer - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 6
Tables vi - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 7
Floor Ground System 16 Figure 2-2. Cabinet Dimensions 28 Figure 2-3. Footprint 29 Figure 3-1. Delivery Survey (Part 1 38 Figure 3-2. Delivery Survey (Part 2 39 Figure B-1. hp rp7405/rp7410 Space Requirements 48 Figure B-2. hp rp7405/rp7410 Cabinet Template 51 Figure B-3. Planning Grid 52 vii - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 8
Figures viii - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 9
Preface - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 10
Revision History Table 1 Revisions Revision Part Number Second A6752-96003 First A6752-96003 Release Date Description November 2002 Made general updates and corrections throughout book August 2002 Initial Release viii - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 11
Notational Conventions WARNING Warnings highlight procedures or information necessary to avoid injury to personnel. The warning should tell the reader exactly what will result from what actions and how to avoid them. CAUTION A caution highlights procedures or information necessary to avoid - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 12
the cabinet manually. To service guidelines. WARNING Do not stand in front of the equipment as it is rolled off the pallet onto the ramps. When removing the equipment from the shipping pallet, follow the guidelines specified in the Installation Procedures section of the appropriate equipment guides - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 13
Figure 1 Declaration of Conformity xi - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 14
. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 15
Korean RFI Statement Certification Number: E - AAAAA - BB - CCCC • E: EMC registration • AAAAA: equipment codes (RRL notice, 2000.10.26) • BB: certification year • CCCC: registration number Figure 3 Korean RFI Translation Class A Equipment: Please note that this equipment has been approved for - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 16
BSMI (Taiwan Area) This product is fully compliant to CNS 13438 (CISPR 22: 1993) Class A. The EMC label is in the form shown in Figure 4. Figure 4 Taiwan Area EMC Acoustics (Germany) Acoustic Noise (A-weighted Sound Pressure Level LpA) measured at the bystander position, normal operation, to ISO - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 17
Installation Conditions See installation instructions before connecting this equipment to the input supply. Voir la notice d'installation avant de raccorder au réseau. WARNING NORDIC Class 1 Equipment Denmark: Før tilslutning af de ø - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 18
. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer's instructions and local disposal requirements. IMPORTANT Switzerland: Annex 4.10 of SR 814.013 applies to batteries. Australian C-Tick Label Figure 5 C-Tick - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 19
housing. In the USA, the DVD is certified as a Class 1 laser product conforming to the requirements contained in the Department of Health and Human Services (DHHS) regulation 21 CFR, Subchapter J. The certification is indicated by a label on the DVD housing. Outside the USA, the DVD is certified as - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 20
xviii - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 21
1 System Specifications Chapter 1 1 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 22
and Weights Dimensions and Weights This section provides dimensions and weights of the system components. Table 1-1 hp rp7405/rp7410 Server Dimensions and Weights Standalone Packaged Height - Inches (centimeters) Width - Inches (centimeters) Depth - Inches (centimeters) Weight - Pounds - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 23
Electrical Specifications Electrical Specifications This section provides electrical specifications for hp rp7405/rp7410 servers. Grounding The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets. Install a PE (protective earthing) conductor - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 24
rating Per line cord Table 1-5 System Power Requirements Power Required (50 - 60 Hz) Maximum configuration hp rp7405/rp7410 server PA8700 Typical configuration hp rp7405/rp7410 server PA8700 VA 3000 1700 Comments Theoretical Typical Future upgrades may increase the Maximum Theoretical System - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 25
Environmental Specifications This section provides the environmental, power dissipation, noise emission, and air flow specifications for the hp rp7405/rp7410 server. Temperature and Humidity The cabinet is actively cooled using forced convection in a Class C1-modified environment. Operating - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 26
Qty 2 2 2 2 Watts 2000 1810 1757 1148 BTU/Hr 6826 6179 5998 3919 Acoustic Noise Specification The acoustic noise specification for the hp rp7410 server is 57.3 db (sound pressure level at bystander position) It is appropriate for dedicated computer room environments, not office environments. The - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 27
System Specifications Environmental Specifications Figure 1-1 illustrates the location of the inlet and outlet airducts on a single cabinet. Figure 1-1 Airflow Diagram Chapter 1 7 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 28
System Specifications Environmental Specifications 8 Chapter 1 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 29
2 Facility Guidelines Chapter 2 9 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 30
installation of a power distribution system for an hp rp7405/rp7410 server requires specialized skills. Those responsible for this task good design, when coupled with proper installation practices, produces the most trouble-free operation. The electrical factors discussed in this section are: A - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 31
Facility Guidelines Electrical Load Requirements (Circuit Breaker Sizing) Electrical Load Requirements (Circuit Breaker Sizing) It is always a good idea to derate power distribution systems for one or more of the following reasons: • To avoid nuisance tripping from load shifts or power transients, - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 32
. However, testing cannot conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for server equipment: • Dedicated power source-Isolates server power distribution system from other circuits in the - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 33
Facility Guidelines Distribution Hardware Distribution Hardware This section describes wire selection and the types of raceways (electrical conduits) used in the distribution system. Wire Selection Use copper conductors instead of aluminum, as aluminum's coefficient of expansion differs - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 34
Facility Guidelines Grounding Systems Grounding Systems hp rp7405/rp7410 servers require two methods of grounding: • Power equipotential ground to all points. Main Building Electrical Ground The main electrical service entrance equipment should have an earth ground connection, as required by - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 35
inductive to provide adequate high frequency ground return paths. Therefore, the server is shipped with a ground strap for connecting the system cabinet to grid should be connected to the equipment cabinet and electrical service entrance ground at multiple connection points using a minimum #6 AWG - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 36
grid with bolted down stringers and corrosion resistive plating (to provide low resistance and attachment points for connection to service entrance ground and server equipment). The use of conductive floor tiles with this style of grid further enhances ground performance. Figure 2-1 Raised Floor - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 37
Hewlett-Packard equipment. Refer to the appropriate installation guide for installation procedures. Wiring Connections Expansion and contraction that are too loose have a high resistance that cause serious problems, such as erratic equipment operation. A high resistance connection overheats and - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 38
(ESD) prevention • Acoustics (noise reduction) Computer Room Preparation The following guidelines are recommended when preparing a computer room for an hp rp7405/rp7410 server system: • Locate the computer room away from the exterior walls of the building to avoid the heat gain from windows and - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 39
computer room • Scalable overhead distribution system-This system distributes water overhead to air heat exchangers, which cool the air locally over the servers. This system called DataCoolTM is primarily used in high density environments of 100 to 500 watts per square foot. Basic Air Distribution - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 40
Facility Guidelines Environmental Elements • Underfloor air distribution system-Downflow air conditioning equipment located on the raised floor of the computer room uses the cavity beneath the raised floor as plenum for the supply air. Perforated floor panels (available from the raised floor - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 41
levels of electrostatic charges. This increases the electrostatic discharge (ESD) voltage potential. ESD can cause component damage during servicing operations. Paper feed problems on high-speed printers are usually encountered in low-humidity environments. Low humidity levels are often the result - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 42
Facility Guidelines Environmental Elements Special precautions are necessary if the computer room is near a source of air pollution. Some air pollutants, especially hydrogen sulfide (H2S), are not only unpleasant but corrosive as well. Hydrogen sulfide damages wiring and delicate sound equipment. - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 43
Facility Guidelines Environmental Elements Acoustics Computer equipment and air conditioning blowers cause computer rooms to be noisy. Ambient noise level in a computer room can be reduced as follows: • Dropped ceiling-Cover with a commercial grade of fire-resistant, acoustic rated, fiberglass - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 44
Facility Guidelines Computer Room Safety Computer Room Safety Inside the computer room, fire protection and adequate lighting (for equipment servicing) are important safety considerations. Federal and local safety codes govern computer installations. Fire Protection The national Fire Protection - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 45
that must be considered for the installation or operation of an hp rp7405/rp7410 server. Facility characteristics are: • Floor loading • Windows • Altitude effects Floor Loading The computer room floor must be able to support the total weight of the installed computer system as well as - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 46
floor or span of raised floor tiles covered by the hp rp7405/rp7410 server footprint. Typical Raised Floor Site This section contains an example cm) by 24 in. (61.0 cm) floor panels be used to support the server installation. NOTE If the specific floor being evaluated or considered is other than - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 47
With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 48
This section contains information about space requirements for an hp rp7405/rp7410 server. This data should be used as the basic guideline be eliminated. The locations of lighting fixtures and utility outlets affect servicing operations. Plan equipment layout to take advantage of lighting and utility - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 49
Facility Guidelines Space Requirements The service area space requirements, shown in Figure 2-3, are minimum dimensions. If other equipment is located so that it exhausts heated air near the cooling air intakes - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 50
concern has developed in computer rooms where these conductive contaminants are formed on the bottom of some raised floor tiles. Although this problem is relatively rare, it may be an issue within your computer room. Since metallic contamination can cause permanent or intermittent failures on - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 51
3 Pre-installation Survey This chapter provides a site survey information packet consisting of an information form and checklists to be used to evaluate a computer facility. The checklists should be completed and the information sheets and information forms filled out by the customer and a Hewlett- - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 52
-installation Survey Content The site Pre-installation survey information is designed to identify problems that might occur before, during, or after the installation of the system personnel. • Pre-installation survey information forms-List delivery information and special instructions. 32 Chapter 3 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 53
check made with an Hewlett-Packard site preparation specialist to resolve any last minute problems NOTE Not all installations follow a schedule like the one noted above. Sometimes, HP Servers are purchased through another vendor which can preclude a rigid schedule. Other conditions could also - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 54
Pre-installation Survey Site Inspection Site Inspection Table 3-1 contains the basic Customer and Hewlett-Packard information. Table 3-2 contains the Site Inspection Checklist. Table 3-1 Customer and Hewlett-Packard Information Customer Information Name: Street Address: Phone No: City or - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 55
Power and lighting No. Area or condition Yes No 13. Are lighting levels adequate for maintenance? 14. Are there AC outlets available for servicing needs? (i.e. vacuuming) 15. Does the input voltage correspond to equipment specifications? 15A Is dual source power used? If so, identify type - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 56
purposes? 24. Is there a fire protection system in the computer room? 25. Is antistatic flooring installed? 26. Are there any equipment servicing hazards (loose ground wires, poor lighting, etc.)? Cooling No. Area or condition Yes No 27. Can cooling be maintained between 20° C and - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 57
the appropriate information in the areas provided on the form. Special instructions or recommendations should be entered on the special instructions or recommendations form. The following list gives examples of special instructions or issues: • Packaging restrictions at the facility, such as size - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 58
Pre-installation Survey Delivery Survey • Special security requirements applicable to the facility, such as security clearance Figure 3-1 Delivery Survey (Part 1) DELIVERY CHECKLIST DOCK DELIVERY Is dock large enough for a semitrailer? Yes No Circle the location of the dock and give street - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 59
Figure 3-2 Delivery Survey (Part 2) Pre-installation Survey Delivery Survey ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb or kg) Depth Height Width Depth Height Width STAIRS Please list number of flights and stairway dimensions. Number - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 60
Pre-installation Survey Delivery Survey 40 Chapter 3 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 61
A System Requirements Summary This appendix summarizes the requirements that must be considered in preparing the site for the hp rp7405/rp7410 server. Appendix A 41 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 62
initial installation or as a later update. Refer to the applicable documentation for such devices to determine the power and air-conditioning that is required to support these devices. 42 Appendix A - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 63
System Requirements Summary Power Consumption and Air Conditioning Table A-1 Example Power Consumption (Theoretical Maximum) and Air Conditioning Requirement Summary Component Chassis Cell Board (PA8700) PCI Card (Maximum 25W) Power Supply (BPS) DVD Disk Drive Core I/O PCI Power Supply Quantity - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 64
System Requirements Summary Power Consumption and Air Conditioning Requirement Power Consumption and Air Conditioning Requirement Table A-3 Example Power Consumption (Typical) and Air Conditioning Requirement Summary Component Quantity Multiply Quantity By: Power Dissipated (kilowatts) Air - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 65
consumption of every subsystem in the box, and should be used to size worst case power consumption. Typical power consumption numbers are what HP engineers have measured running power intensive applications. These are generally lower than maximum power numbers due to the fact that getting all of - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 66
System Requirements Summary Weight Weight To determine overall weight, follow the examples in Table A-5, then complete the entries in Table A-6. Table A-5 Example Weight Summary Component Quantity Multiply By Weight (kg) Cell Boards 2 PCI Card (varies - used A3739B here) 4 Power Supply - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 67
B Templates This appendix contains blank floor plan grids and equipment templates. Combine the necessary number of floor plan grid sheets to create a scaled version of the computer room floor plan. Appendix B 47 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 68
Templates Figure B-1 illustrates the overall dimensions required for an hp rp7405/rp7410 system. Figure B-1 hp rp7405/rp7410 Space Requirements 48 Appendix B - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 69
same scale as the floor plan grid (1/4 inch = 1 foot). These templates are provided to show basic equipment dimensions and space requirements for servicing. The service areas shown on the template drawings are lightly shaded. The equipment templates should be used with the floor plan grid to define - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 70
Templates Computer Room Layout Plan Computer Room Layout Plan Use the following procedure to create a computer room layout plan: Step 1. Remove several copies of the floor plan grid. Step 2. Cut and join them together (as necessary) to create a scale model floor plan of your computer room. Step 3. - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 71
Templates Computer Room Layout Plan Step 5. Position pieces until the desired layout is obtained; then fasten the pieces to the grid. Mark locations of computer room doors, air conditioning floor vents, utility outlets, and so on. Figure B-2 hp rp7405/rp7410 Cabinet Template Appendix B 51 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 72
Templates Computer Room Layout Plan Figure B-3 Planning Grid Scale: 1/4 inch = 1 foot 60SP016A 12/20/99 52 Appendix B - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 73
Index A AC frequency specifications, 4 AC power specifications, 3 acoustics, 22 air conditioning, 19 system recommendations, 19 air conditioning ducts, 21 air distribution system room space return air, 19 air ducts, 8 illustrated, 8 average floor loading, 26 B backplane mass storage, 2 system, 2, 6 - HP Rp7410 | Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 74
Index power distribution system distribution hardware, 13 power quality, 12 power system protection, 12 power wiring, 13, 17 preinstallation survey, 31 R raised floor ground system, illustrated, 16 S site inspection, 34 sources of electrical disturbances, 12 space requirements, 28 computer room
Site Preparation Guide
hp rp7405/rp7410 Servers
Second Edition
Manufacturing Part Number: A6752-96009
21102
USA
© Copyright 2002