HP Scitex FB10000 Geffen TS Error 66117

HP Scitex FB10000 Manual

HP Scitex FB10000 manual content summary:

  • HP Scitex FB10000 | Geffen TS Error 66117 - Page 1
    Error ID: 66117: Unified Cooler - Water Overflow FB10000 Error Messages Troubleshooting Error ID: 66117: Unified Cooler - Water Overflow Error Severity: Warning Possible Causes • Water Level over the Overflow mark • Faulty Overflow LED • Faulty Overflow Sensor • Faulty
  • HP Scitex FB10000 | Geffen TS Error 66117 - Page 2
    Cooler - Water Overflow Troubleshooting 2. If the water Error button in the printer SW to check if the problem was solved. WARNING! High Voltage System! Do not touch any wiring while system is UP! From this stage and on, only an HP certified electrician may perform the tests. 4. If the water level is
  • HP Scitex FB10000 | Geffen TS Error 66117 - Page 3
    ID: 66117: Unified Cooler - Water Overflow Troubleshooting Removing the Cooler Electric Panel cover 7. Using check the continuity in the Molex connector. 9. To access the Molex connector, open the top service cover. 10. Using a Fluke tester, check the continuity between the two J1 connections: on
  • HP Scitex FB10000 | Geffen TS Error 66117 - Page 4
    Error ID: 66117: Unified Cooler - Water Overflow Overflow sensor Troubleshooting J1 Molex connector Unified Cooler Overflow Sensor and J1 Connector 11. If there this case, replace the J1 connector. 12. If all these steps did not solve the problem, contact your HP regional technical specialist. 4
  • 1
  • 2
  • 3
  • 4

Error ID: 66117: Unified Cooler – Water Overflow
FB10000 Error Messages Troubleshooting
FB10000 Error Messages Troubleshooting
Error ID: 66117: Unified Cooler – Water Overflow
Error Severity:
Warning
Possible Causes
Water Level over the Overflow mark
Faulty Overflow LED
Faulty Overflow Sensor
Faulty J1 connector
Recommended Actions
1.
Visually check the water level in the Unified Cooler water level indicator.
Cooler Water Level Indicator
Overflow mark
Overflow LED
Drain valve