HP Scitex FB10000 Geffen TS Error 66124

HP Scitex FB10000 Manual

HP Scitex FB10000 manual content summary:

  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 1
    Error Message Troubleshooting FB10000 Error Message Troubleshooting Error ID: 66124: Unified Cooler - Temperature in coolant tank is too high (over 60º C) 66124 Temperature in coolant tank is too high (over 60º C). For more details open the Troubleshooting guide Possible Causes
  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 2
    Error ID: 66124: Unified Cooler - Temperature in coolant tank is too high (over 60º C) FB10000 Error Message Troubleshooting • Large Heater/contactor is faulty (see error 66115) • Coolant flow fault error (see errors 66116 and 66125 ) (diagnostics) Recommended actions Note: Prior to starting with
  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 3
    in coolant tank is too high (over 60º C) Air filter is clogged 1. Remove the two Air Filters out of their compartment. FB10000 Error Message Troubleshooting 2. Clean the two air filters and slide them back into their compartment. 3. Bi-Metal sensors are faulty 4. Check the three Bi-metal
  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 4
    FB10000 Error Message Troubleshooting 2. Verify that its propeller runs continuously or intermittently during operation [both cases are OK]. 3. Ensure that none of the propeller wings is bent or damaged. 4. If any of the propeller wing is damaged, replace the fan [Call HP Service
  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 5
    - Temperature in coolant tank is too high (over 60º C) Fan CB is faulty 1. Open the Circuit Breaker Flap in the Front of the Cooler. FB10000 Error Message Troubleshooting 2. Check the Fan Circuit Breaker (CB Fan + left and right). 3. If the CB is down, switch it on. 4. If the CB shuts down again
  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 6
    FB10000 Error Message Troubleshooting WARNING! High Voltage System! Do not touch any wiring while system is UP! From this stage and on, only an HP certified both sides (TB_DIS 13,14,15) 10. If none of the above solved the problem than check in the Cooler's B&R module. 11. If the E LED (E=Error)
  • HP Scitex FB10000 | Geffen TS Error 66124 - Page 7
    Troubleshooting 14. If all LEDS in the BM_3 module are lit in red, this indicates a communication problem. 15. If only BM_3 is lit in red, this indicates that the BM_3 module caused the error and it might be faulty. 16. Replace the BM_3 B&R control module [HP Service only] 17. If the problem
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7

Error ID: 66124:
Unified Cooler - Temperature in coolant tank is too high (over 60º C)
FB10000 Error Message Troubleshooting
FB10000 Error Message Troubleshooting
Error ID: 66124:
Unified Cooler - Temperature in coolant tank is too high (over 60º C)
66124 <Month, Day, Time>
Temperature in coolant tank is too high (over 60º C).
For more details open the
Troubleshooting guide
Possible Causes
Fan main air inlet or outlet are obstructed
Air filter is clogged (Standalone)
Bi-Metal sensors are faulty (Standalone)
Fan is faulty (standalone)
Fan CB is faulty
Small Heater/SSR is faulty (see error 66114)
1