HP StorageWorks P9500 Site Preparation Guide Abstract This guide describes the site preparation for HP StorageWorks P9500 disk arrays. The intended audience is a storage system administrator or authorized service provider with independent knowledge of the HP StorageWorks P9500 and Remote Web Console - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 2
Computer Software, Computer Software Documentation, and Technical Data for Commercial Items are licensed to the U.S. Government under vendor's standard commercial license. The information contained herein is subject to change without notice. The only warranties for HP products and services are - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 3
User responsibilities...5 HP configuration (right module 34 Five rack configuration...36 Six rack configuration...38 Operational requirements...40 4 Support and other resources 41 Contacting HP...41 Subscription service...41 Related information...41 HP websites...41 Conventions for storage - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 4
Typographic conventions...42 HP product documentation survey 43 Glossary...44 Index...49 4 Contents - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 5
HP Technical Support. The P9500 disk array is not a customer installable product. User responsibilities You are responsible for performing the following tasks to prepare for installation of the P9500 disk array. • Understand the applicable safety requirements associated with installing a P9500 disk - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 6
Location: The specific location in the data center (area or "footprint" on the floor) where the P9500 disk array will be installed. User Information Company . Address . Contact . Phone . Mobile . Email . Contact . Phone . Mobile . Email . HP Information Contact . Phone . - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 7
adequate acoustic insulation to operate the P9500 disk array? . . Operational Requirements . . Does the data center provide a LAN for Remote Web Console? . . hb-Is the infrastructure available for the default Internet based remote support solution? . . Does the location meet the cable - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 8
of heat. • Warning and safety labels: Safety warnings, cautions, and instructions in various languages are attached to the P9500 disk array components. The safety warnings provide guidelines to follow when working with any equipment. HP recommends that you read all warning labels on the hardware. If - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 9
any loose clothing so that it cannot be caught by a moving or rotating part such as a fan. • Tie up long hair. • Unless otherwise specifically instructed, do not supply power to any device that contains rotating or moving parts that are not properly covered. Electrical safety guidelines Even though - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 10
dock, storage area, and P9500 disk array racks are shipped in one of three standard packaging configurations: • Environmental pack - This packaging configuration HP uses special carriers with a dedicated fleet of trucks and specially trained personnel. • Full packaging - This packaging configuration - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 11
to reduce the effects of external fields. The P9500 frames support top access and bottom access for hot cables. Routing the host cables in a P9500 requires HP support personnel to install. The data communication infrastructure needed for the P9500 disk array is described in "Data communication - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 12
may be sent to your authorized HP Channel Partner for on-site service, if configured and available in your country. The HP Insite Remote Support products available for the P9500 disk arrays are described in "P9500 disk array remote support products" (page 13). 12 Installation requirements - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 13
supported on XP and P9500 Disk Arrays. Table 6 P9500 disk array remote support products HP Product AE241A AE242A AE244A AE245A Description Application HP XP/P9500 Remote Device Access Support For customers that fully commit to use HP Remote Support. It uses HP Insight Remote Support for P9500 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 14
http://www.software.hp.com Select Insight Remote Support from the menu on the right. System specifications and requirements This section describes the physical characteristics of a P9500 disk array, including • "Mechanical specifications" (page 14) • "Electrical specifications" (page 16) • " - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 15
Figure 1 P9500 disk array Figure 2 Example P9500 disk array configurations System specifications and requirements 15 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 16
- three phase current" (page 17) list the electrical specifications of the P9500 disk array, including power requirements and power consumption. Table 8 P9500 Electrical specifications - single phase current Item Unit Specification Power requirements, system AC, single phase 2 pole + 200 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 17
Table 9 P9500 Electrical specifications - three phase current Item Unit Specification Power requirements AC, 3 Phase delta • The grounding conductor mentioned above should be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 18
Power connection The AC power input for the P9500 disk array has a duplex PDU structure. This duplex Options P9500 is configured for input power using separate rackmount PDU products. PDUs are available for three phase or single phase power for NEMA and IEC compliance applications. Table 10 P9500 AC - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 19
offline maintenance procedures Figure 3 P9500 AC Power Configuration Diagram Environmental specifications Table 11 (page 19)provides the environmental specifications and requirements for the P9500 disk array. Table 11 P9500 environmental specifications Item Temperature (ºF / ºC) Operating 60 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 20
to 24°C. 2. On shipping/storage condition, the product should be packed with factory packing. 3. The above specifications of vibration are applied to heat output and air flow requirements for the P9500 disk array. Both the control chassis and the disk chassis contain front and rear fans to circulate - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 21
values [loudness in dB (A)] for the P9500 disk array disk array are: • Front/rear = 65 dB (A) • Both sides = 65 dB (A) Service clearance, floor cutout, and floor load rating This section describes the service clearance requirements for the P9500 disk array, based on the floor load rating and - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 22
. Actual clearances for installation should be determined after consulting with the site/facilities manager, as the clearances can vary, depending on building conditions. Single rack configuration The following figure and table show the service clearances and floor load rating for a single rack - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 23
rack system Table 14 Floor load rating and required clearances for single rack configuration Floor Load Rating (kg/m2) 500 450 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0. 1 0.2 0.1 C=0.4 0 0.1 C=0.6 0 0 C=0.6 0 0 Service clearance, floor cutout, and floor load rating 23 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 24
clearancevalues based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) bemade as large as possible. Two rack configuration (one DKC) The following figure and table shows the service clearances and floor load - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 25
15 Floor load rating and required clearances for two rack configuration Floor Load Rating (kg/m2) 500 450 400 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.3 0.2 0.5 0.4 C=0.4 0 0.1 0.3 C=0.6 0 0 0.2 C=0.6 0 0 0 Service clearance, floor cutout, and floor load rating 25 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 26
values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Two rack configuration (two DKC) The following figure and table shows the service clearances and floor load rating - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 27
DKC) Table 16 Floor load rating and required clearances for a two rack configuration (two DKC) Floor Load Rating (kg/m2) 500 450 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.3 0.2 C=0.4 0 0.1 C=0.6 0 0 C=0.6 0 0 Service clearance, floor cutout, and floor load rating 27 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 28
values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Three rack configuration (left module) The following figure and table shows the service clearances and floor load - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 29
required clearances for a three rack configuration (left module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.4 0.2 0.8 0.6 1.3 1.1 C=0.4 0 0.1 0.4 0.9 C=0.6 0 0 0.3 0.7 C=0.6 0 0 0 0.4 Service clearance, floor cutout, and - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 30
values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Three rack configuration (right module) The following figure and table shows the service clearances and floor load - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 31
clearances for a three rack configuration (right module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.4 0.3 0.8 0.6 1.4 1.2 C=0.4 0 0.1 0.5 1.0 C=0.6 0 0 0.3 0.8 C=0.6 0 0 0 .1 0.5 Service clearance, floor cutout, and - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 32
values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Four rack configuration (left module) The following figure and table shows the service clearances and floor load - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 33
required clearances for a four rack configuration (left module) Floor Load Rating (kg/m2) 500 450 400 350 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.5 0.3 1.1 0.8 1.8 1.5 C=0.4 0 0.1 0.6 1.2 C=0.6 0 0 0.4 1.0 C=0.6 0 0 0 .1 0.6 Service clearance, floor cutout, and - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 34
values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Four rack configuration (right module) The following figure and table shows the service clearances and floor load - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 35
rating and required clearances for a four rack configuration (right module) Floor Load Rating (kg/m2) 500 450 400 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.5 0.3 1.1 0.8 C=0.4 0 0.1 0.6 C=0.6 0 0 0.4 C=0.6 0 0 0 .1 Service clearance, floor cutout, and floor load - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 36
clearance values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Five rack configuration This following figure and table shows the service clearances and floor load rating - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 37
rack system Table 21 Floor load rating and required clearances for a five rack configuration Floor Load Rating (kg/m2) 500 450 Required Clearance (a+b) m Clearance (c) m C=0 C=0.2 0.1 0 0.6 0.3 C=0.4 0 0.1 C=0.6 0 0 C=0.6 0 0 Service clearance, floor cutout, and floor load rating 37 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 38
clearance values based on the largest disk array configuration should be used. 3. From the viewpoint of maintenance operations, it is suggested that Clearance (c) be made as large as possible. Six rack configuration This following figure and table shows the service clearances and floor load rating - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 39
Figure 12 Service clearances for a six rack system Service clearance, floor cutout, and floor load rating 39 - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 40
P9500 disk array over a LAN to obtain system configuration and status information and send user-requested commands to the disk array. Remote Web Console serves as the integrated interface for all Resource Manager • External data storage If you plan to attach external storage to the P9500 disk array, - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 41
, see the following HP websites: • http://www.hp.com • http://www.hp.com/go/storage • http://www.hp.com/service_locator • http://www.hp.com/support/manuals • http://www.hp.com/support/downloads • http://www.hp.com/storage/whitepapers Conventions for storage capacity values P9000 disk arrays use the - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 42
bytes P9000 disk arrays use the following values to calculate logical storage capacity hp.com Bold text Element Cross-reference Commands, their arguments, and argument values Monospace, italic text • Code variables • Command variables Monospace, bold text Emphasized monospace text 42 Support - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 43
or data. IMPORTANT: Provides clarifying information or specific instructions. NOTE: Provides additional information. TIP: Provides helpful hints and shortcuts. HP product documentation survey Are you the person who installs, maintains, or uses this HP storage product? If so, we would like to - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 44
, HP StorageWorks Business Copy, or HP StorageWorks P9000 Business Continuity Manager control operations, which are then executed by the array. Consistency group. Consistency group ID. The group identifier used to identify a group of volumes in the HP StorageWorks P9500 Disk Array being replicated - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 45
HP StorageWorks P9000 Command View Advanced Edition. A software product that installs on a user-provided server and provides a browser-based platform from which you can manage the P9000 family of disk arrays CVS devices (OPEN-x CVS or 3390-x CVS) are custom volumes configured using array management - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 46
in the local array. Sometimes refers to a disk in a local host. The RAID Manager instance currently being configured or the instance to which commands are issued. Logical unit number. Logical Unit Size Expansion. The LUSE feature is available when the HP StorageWorks LUN Manager product is installed - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 47
your HP representative for the details about which RAID levels are supported by your specific P9000 or XP disk array. The CLI configuration and replication tool for the P9000 or XP disk array that can be used by system administrators to enter RAID Manager commands from open-system hosts to perform - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 48
SVP that allows you to configure and manage the disk array. Remote I/O. HP StorageWorks RAID Manager. Red Hat package manager. Secondary or remote volume. The copy volume that receives the data from the primary volume. Serial Attached SCSI. State-change-pending. Service information message. Simplex - HP StorageWorks P9000 | HP StorageWorks P9500 Site Preparation Guide (AV400-9630 - Page 49
support team, 5 respopnsibilities user, 5 S specifications, 14 electrical, 16 environmental, 19 equipment noise, 21 heat output, 20 load rating, 21 mechanical, 14 storage capacity values conventions, 41 Subscriber's Choice, HP, 41 symbols in text, 43 T technical support HP, 41 service
HP StorageWorks
P9500 Site Preparation Guide
Abstract
This guide describes the site preparation for HP StorageWorks P9500 disk arrays. The intended audience is a storage system
administrator or authorized service provider with independent knowledge of the HP StorageWorks P9500 and Remote Web
Console.
HP Part Number: AV400-96306
Published: November 2010
Edition: Second