Honeywell F500A1000 Owner's Manual

Honeywell F500A1000 - Whole House HEPA Air Cleaner Manual

Honeywell F500A1000 manual content summary:

  • Honeywell F500A1000 | Owner's Manual - Page 1
    Whole House/ Light Commercial HEPA Filtration System APPLICATION The F500 Whole House/Light Commercial HEPA Air Cleaner connects to the return air duct of a forced air system. The HEPA filter captures 99.97percent of the particles from the air that passes through it. PRODUCT DATA/OWNER'S GUIDE
  • Honeywell F500A1000 | Owner's Manual - Page 2
    to change each filter. 25-1/2 (648) MOUNTING STRAP 12-1/2 (328) 19 (483) Whole House HEPA Filtration System PROVIDE 26-1/2 (673) SERVICE CLEARANCE IN FRONT OF UNIT 10 (254) 4 (102) M20574 ORDERING INFORMATION Fig. 1. F500 dimensions. When purchasing replacement and modernization products
  • Honeywell F500A1000 | Owner's Manual - Page 3
    , have a qualified electrician install one.) 4. Choose a location that is readily accessible for checking and replacing the filter. (Allow at least 26-1/2 in. (673 mm) clearance in front of the unit.) Planning Ducting The F500 can be mounted to the whole-house forced air system using a bypass
  • Honeywell F500A1000 | Owner's Manual - Page 4
    F500 WHOLE HOUSE/ LIGHT COMMERCIAL HEPA FILTRATION SYSTEM S688A1007 SAIL SWITCH (OPTIONAL) 120 VAC 60 HZ SUPPLY WITH GROUND FRESH AIR HEAT RECOVERY VENTILATOR RETURN AIR F500 HIGH EFFICIENCY AIR CLEANER AIR HANDLER (FURNACE) M20264A Fig. 4. Typical F500 bypass installation with heat recovery
  • Honeywell F500A1000 | Owner's Manual - Page 5
    F500 WHOLE HOUSE/ LIGHT COMMERCIAL HEPA FILTRATION SYSTEM Installing HEPA AIRWATCH™ Indicator Mount the HEPA AIRWATCH™ reset the timer after replacing the parts. TM On/Battery Odor Filter Prefilter HEPA Filter Whole House HEPA Filtration System Honeywell.com/yourhome 7. Install two AAA alkaline
  • Honeywell F500A1000 | Owner's Manual - Page 6
    turn on the system blower. 4. Verify that the Whole House/Light Commercial HEPA Air Cleaner turned on. TROUBLESHOOTING See Table 3 for troubleshooting guide. Symptom Poor airflow AIRWATCH beeping and/or flashing Table 3. Troubleshooting Guide. Cause Filters plugged Poor power supply at the site
  • Honeywell F500A1000 | Owner's Manual - Page 7
    -001 32006028-001 Description HEPA AIRWATCH™ Indicator Blower Motor Assembly Carbon-Odor Filter Pleated Prefilter HEPA Filter TM On/Battery Odor Filter Prefilter HEPA Filter Whole House HEPA Filtration System Honeywell.com/yourhome 1 2 3 4 5 Fig. 7. Illustrated Parts List. 7 M20575 68-0263
  • Honeywell F500A1000 | Owner's Manual - Page 8
    Automation and Control Solutions Honeywell 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9 68-0263-2 G.H. Rev. 4-04 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

PRODUCT DATA/OWNER’S GUIDE
68-0263-2
® U.S. Registered Trademark
Copyright © 2004 Honeywell •
All Rights Reserved
F500 Whole House/
Light Commercial
HEPA Filtration System
APPLICATION
The F500 Whole House/Light Commercial HEPA Air Cleaner
connects to the return air duct of a forced air system. The
HEPA filter captures 99.97percent of the particles from the air
that passes through it.
FEATURES
HEPA media captures at least 99.97 percent of 0.3
micron particles that pass through it.
Application for forced air systems.
Power cord plugs into grounded 120 Vac electrical
outlet.
Requires no maintenance except periodic media filter
replacement.
Quick and easy media filter replacement.
Wall-mounted AIRWATCH
TM
Indicator included
provides filter change reminders.
Three-filter system:
Activated carbon filter for odors.
High-efficiency pleated pre-filter extends HEPA fil-
ter life.
HEPA filter traps at least 99.97 percent of the
0.3 micron particles that pass through it.
Easy installation.
Includes four isolation straps.
Rugged steel cabinet.
Quiet operation.
Model available with fully-insulated cabinet for
installation in unconditioned environments.
Contents
Application and Features
...................................................
1
Specifications
....................................................................
2
Ordering Information
.........................................................
2
Planning the Installation
....................................................
3
Installation
.........................................................................
4
Startup and Checkout
........................................................
6
Troubleshooting
.................................................................
6
Parts List
...........................................................................
7