Honeywell HPFF12 Operation Manual - Page 30

Mounting Addressable Modules, 2.4.1 Mounting Modules from Honeywell Fire Systems

Page 30 highlights

Installation Mounting Addressable Modules 2.4 Mounting Addressable Modules The HPFF12 and the HPFF12E are designed to mount Honeywell Fire Systems addressable control or relay modules on the Control circuit board inside the power supply cabinet. This allows power to be fed from the Auxiliary output directly to the module, if needed, without running the power wires outside the cabinet. For a list of compatible optional modules that can be connected to the Auxiliary output, see Appendix A, "Device Compatibility". Two single output modules may be mounted directly above each other if required by applications such as Split Alarm or Selective Silence. Alternately, two outputs of a 6-output addressable module can also be used and mounted on the Control board. 2.4.1 Mounting Modules from Honeywell Fire Systems Addressable modules can be mounted directly to the Control circuit board as shown in Figure 2.14 for the wall cabinet. This allows wiring to remain in the cabinet. Two modules can be mounted on top of each other if the application requires two independent inputs, such as silencing. Alternately, two outputs of a six-output addressable module can also be used. The six-output module can also be mounted directly on the Control board. Mounting addressable modules on the Control circuit board is also possible in the HPFF12CM(E) units. However, the six-output module must be mounted in an optional multi-module chassis if used in the large cabinet enclosure. See Section 2.5, "Power-Limited Wiring Requirements". HPFF12mntcmf.wmf Figure 2.14 Mounting Details for Control & Relay Modules from Honeywell Fire Systems 30 HPFF12 NAC Expander - P/N 53576:B 11/24/2010

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

30
HPFF12 NAC Expander —
P/N 53576:B
11/24/2010
Installation
Mounting Addressable Modules
2.4
Mounting Addressable Modules
The HPFF12 and the HPFF12E are designed to mount Honeywell Fire Systems addressable control
or relay modules on the Control circuit board inside the power supply cabinet. This allows power to
be fed from the Auxiliary output directly to the module, if needed, without running the power wires
outside the cabinet. For a list of compatible optional modules that can be connected to the Auxiliary
output, see Appendix A, “Device Compatibility”.
Two single output modules may be mounted
directly above each other if required by applications such as Split Alarm or Selective Silence.
Alternately, two outputs of a 6-output addressable module can also be used and mounted on the
Control board.
2.4.1
Mounting Modules from Honeywell Fire Systems
Addressable modules can be mounted directly to the Control circuit board as shown in Figure 2.14
for the wall cabinet. This allows wiring to remain in the cabinet. Two modules can be mounted on
top of each other if the application requires two independent inputs, such as silencing. Alternately,
two outputs of a six-output addressable module can also be used. The six-output module can also
be mounted directly on the Control board.
Mounting addressable modules on the Control circuit board is also possible in the HPFF12CM(E)
units. However, the six-output module must be mounted in an optional multi-module chassis if used
in the large cabinet enclosure.
See Section 2.5, “Power-Limited Wiring Requirements”.
Figure 2.14
Mounting Details for Control & Relay Modules from
Honeywell Fire Systems
HPFF12mntcmf.wmf