Honeywell HPFF12 Operation Manual - Page 38

Split Alarm and Silencing, synchronization

Page 38 highlights

Programming Options Programmable Features 3.2.4 Split Alarm and Silencing DIP switch 8, in conjunction with initiating device signal inputs and DIP switches 1 through 6, is used to program the features of General Alarm, Split Alarm, or Silencing. • DIP switch 8 set to the ON position will split the NAC outputs to pairs. NAC outputs 1 & 2 are controlled by Signal Input 1 and NAC outputs 3 & 4 are controlled by Signal Input 2. The output pairs will be selectively silenced if DIP switches 1 through 6 are set for Pass-through and FACP input is wired and programmed for that operation. • DIP switch 8 set to the OFF position and at least one of the NAC outputs are programmed for synchronization, Signal Input 1 & 2 ON will generate a General Alarm on all four NAC outputs. General Alarm is activation of both visual strobe and audible horns. • DIP switch 8 set to the OFF position and at least one of the NAC outputs are programmed for synchronization, Signal Input 1 ON and Signal Input 1 OFF will silence all four NAC outputs while keeping visual strobe activation. NOTE: See Section 5.1 and 5.2 for proper alarm input wiring when DIP switch 8 is programmed in the OFF position. 38 HPFF12 NAC Expander - P/N 53576:B 11/24/2010

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

38
HPFF12 NAC Expander —
P/N 53576:B
11/24/2010
Programming Options
Programmable Features
3.2.4
Split Alarm and Silencing
DIP switch 8, in conjunction with initiating device signal inputs and DIP switches 1 through 6, is
used to program the features of General Alarm, Split Alarm, or Silencing.
DIP switch 8 set to the ON position will split the NAC outputs to pairs. NAC outputs 1 & 2 are
controlled by Signal Input 1 and NAC outputs 3 & 4 are controlled by Signal Input 2. The
output pairs will be selectively silenced if DIP switches 1 through 6 are set for Pass-through
and FACP input is wired and programmed for that operation.
DIP switch 8 set to the OFF position and at least one of the NAC outputs are programmed for
synchronization, Signal Input 1 & 2 ON will generate a General Alarm on all four NAC
outputs. General Alarm is activation of both visual strobe and audible horns.
DIP switch 8 set to the OFF position and at least one of the NAC outputs are programmed for
synchronization, Signal Input 1 ON and Signal Input 1 OFF will silence all four NAC outputs
while keeping visual strobe activation.
NOTE:
See Section 5.1 and 5.2 for proper alarm input wiring when DIP switch 8 is programmed
in the OFF position.