Class A Input Connections

Page 47 highlights

HPFFconnex-Binput.wmf Connecting Multiple Units Applications Figure 5.7 Class B Input Connections w Figure 5.8 Class A Input Connections HPFFconnex6-Ainput.wmf HPFFconnex-split.psd Figure 5.9 Split Alarm Connections Figure 5.10 Selective Silencing Connections NOTES for Figures 5.5-5.10: 1. The FACP's NAC output must be regulated (not Full Wave Rectified [FWR]) if the HPFF is programmed for Sync Generator. 2. The number of possible units that can be interconnected depends on the current capability of the FACP output. Each HPFF8 input draws 12.26 mA at 24 VDC. 3. The total line impedance for interconnected units cannot be such that it creates a voltage drop > 2 VDC. Zline total =2V/(1 Unit + 1 ELR) Example: Zline total = 2V/(12.26 mA + (24-2)/4.7K) =118.1 ohms HPFF12 NAC Expander - P/N 53576:B 11/24/2010 47

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

HPFF12 NAC Expander —
P/N 53576:B
11/24/2010
47
Connecting Multiple Units
Applications
Figure 5.7
Class B Input Connections
w
Figure 5.8
Class A Input Connections
NOTES for Figures 5.5–5.10:
1.
The FACP’s NAC output must be regulated (not Full Wave Rectified [FWR]) if the HPFF is programmed for
Sync Generator.
2.
The number of possible units that can be interconnected depends on the current capability of the FACP
output.
Each HPFF8 input draws 12.26 mA at 24 VDC.
3.
The total line impedance for interconnected units cannot be such that it creates a voltage drop > 2 VDC.
Zline total =2V/(1 Unit + 1 ELR)
Example:
Zline total = 2V/(12.26 mA + (24-2)/4.7K) =118.1 ohms
HPFFconnex-Binput.wmf
HPFFconnex6-Ainput.wmf
Figure 5.9
Split Alarm Connections
Figure 5.10
Selective Silencing
Connections
HPFFconnex-split.psd