Honeywell HPFF12 Operation Manual - Page 52
NAC Circuit Loop Wiring Requirements
View all Honeywell HPFF12 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 52 highlights
Power Supply Requirements NAC Circuit Loop Wiring Requirements 6.5 NAC Circuit Loop Wiring Requirements Make sure these requirements are met: 1. For any NAC circuit with a full load (up to 3 Amps), the total wire resistance must be less than or equal to 0.66 Ohms. and 2. The NAC loop current draw multiplied by total wire resistance on any single NAC circuit cannot exceed 2.0 volts. NOTE: For loads smaller than 3 Amps, use the second calculation. 52 HPFF12 NAC Expander - P/N 53576:B 11/24/2010
52
HPFF12 NAC Expander —
P/N 53576:B
11/24/2010
Power Supply Requirements
NAC Circuit Loop Wiring Requirements
6.5
NAC Circuit Loop Wiring Requirements
Make sure these requirements are met:
1.
For any NAC circuit with a full load (up to 3 Amps), the total wire resistance must be less than
or equal to 0.66 Ohms.
and
2.
The NAC loop current draw multiplied by total wire resistance on any single NAC circuit
cannot exceed 2.0 volts.
NOTE:
For loads smaller than 3 Amps, use the second calculation.