Honeywell HPFF12 Operation Manual - Page 52

NAC Circuit Loop Wiring Requirements

Page 52 highlights

Power Supply Requirements NAC Circuit Loop Wiring Requirements 6.5 NAC Circuit Loop Wiring Requirements Make sure these requirements are met: 1. For any NAC circuit with a full load (up to 3 Amps), the total wire resistance must be less than or equal to 0.66 Ohms. and 2. The NAC loop current draw multiplied by total wire resistance on any single NAC circuit cannot exceed 2.0 volts. NOTE: For loads smaller than 3 Amps, use the second calculation. 52 HPFF12 NAC Expander - P/N 53576:B 11/24/2010