    NS2 may be used as a standalone panel with independent card and transaction storage or, with a software upgrade, as a fully monitored online access control device. Communication to the front-end computer is achieved through an RS-232 serial cable (included with installation VDC (NCI Part #: BAT-3)
  • Honeywell NS2 | Configuration Guide - Page 2
    NS2 Configuration Guide Honeywell Access Systems Reader Wiring Each reader port supports a single 12-volt reader with Wiegand output format. Reader 1 Terminal TB3-1 TB3-2 TB3-3 TB3-4 TB3-5 TB3-6 Wire Color Brown Green White Black Red Variable Wiegrand Reader LED Control Data 0 Signal Data 1
  • Honeywell NS2 | Configuration Guide - Page 3
    Honeywell Access Systems NS2 Configuration Guide Outputs Four form-C relays SPDT (Single Poll Double Throw) goldcontact relays are provided for controlling door locks or other output devices (I.E. sounder, burg panel, phone dialer....etc.). Output Terminal TB7-1 TB7-2 TB7-3 TB7-4 TB7-5 TB7-6 TB8
  • Honeywell NS2 | Configuration Guide - Page 4
    NS2 Configuration Guide Honeywell Access Systems Enclosure Specifications Mounting One NS2 panel in a standard 19-inch, high density enclosure. Up to eight NS2 panels in a single 19-inch rack mountable enclosure Dimensions Board ] are not supported with the NS2 panel(s). 4 7-101004-01
  • Honeywell NS2 | Configuration Guide - Page 5
    Honeywell Access Systems DIP Switch Settings NS2 Configuration Guide S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 SELECTION OFF OFF OFF OFF OFF Address 0 ON OFF OFF OFF OFF Address 1(default) OFF
  • Honeywell NS2 | Configuration Guide - Page 6
    NS2 Configuration Guide Connection Schematic Honeywell Access Systems TB1 READER2 READER1 PWR FAIL/AUX7 COMMON ENCTMPR/AUX8 TB2 RESERVED RESERVED RESERVED RESERVED BROWN GREEN LED DATA 0 WHITE DATA 1 BLACK COMMON RED +12VDC
  • Honeywell NS2 | Configuration Guide - Page 7
    Honeywell Access Systems Configuration Diagrams RS-232 Connection One NS2 panel for each COM port. NS2 Configuration Guide NStar Server COM 1 COM 2 CBL50 (RS-232) 50 ft. Max. CBL50 (RS-232) 50 ft. Max. NS2 Panel DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600
  • Honeywell NS2 | Configuration Guide - Page 8
    NS2 Configuration Guide RS-485 Connection Thirty-one NS2 panels for each drop line. Honeywell Access Systems NStar Server COM Port RS-232 (50 Ft. Max.) RS-485 (4,000 Ft.) N-485-PCI-2 Refer to 485-PCI / NS2 Panel Connection Detail diagram. RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White
  • Honeywell NS2 | Configuration Guide - Page 9
    Honeywell Access Systems NSLAN1 Connection One NSLAN1 for each NS2 panel, Maximum sixty-four IP connections. NS2 Configuration Guide NIC 100BaseT (CAT 5) 328 Ft. Max. HUB NStar Server DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF NS2
  • Honeywell NS2 | Configuration Guide - Page 10
    NS2 Configuration Guide LANSRL100 Connection Thirty-one NS2 panels for each drop line, Maximum sixty-four IP connections. Honeywell Access Systems NIC 100BaseT (CAT 5) 328 Ft. Max. NStar Server HUB RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green
  • Honeywell NS2 | Configuration Guide - Page 11
    Honeywell Access Systems LANSRLU1 Connection Thirty-one panels for each drop line, Maximum sixty-four IP connections. NS2 Configuration Guide NIC 100BaseT (CAT 5) 328 Ft. Max. NStar Server HUB 100BaseT (CAT 5) 328 Ft. Max. RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+)
  • Honeywell NS2 | Configuration Guide - Page 12
    Ft.) M-9600-LO NStar Server Refer to 485-PCI / NS2 Panel Connection Detail diagram. N-485-PCI-2 Null Modem Cable Cable (9-25 Pin) Male 9 Pin (RX) 2 (TX) 3 (Comm) 5 Female 25 Pin 2 (TX) 3 (RX) 7 (Comm) RS-232 (50 Ft.) M-9600-LA RS-485 (4,000 Ft.) Honeywell Access Systems Lease Line Phone
  • Honeywell NS2 | Configuration Guide - Page 13
    Honeywell Access Systems RS-485 Short Haul Modem Connection Thirty-one NS2 panels for each drop line. NStar Server RS-232, 50 Ft. Max. RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9
  • Honeywell NS2 | Configuration Guide - Page 14
    NS2 Configuration Guide RS-232 Short Haul Modem Connection One NS2 panel for each loop. NStar Server RS-232, 50 Ft. Max. SHM-B-ASYNC Short Haul Modem Honeywell Access Systems RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (Null) 2 (TX) 3 (RX) or 7 (GND) 2 (RX) 3 (TX) 7 (GND
  • Honeywell NS2 | Configuration Guide - Page 15
    Honeywell Access Systems M-9600 Dial-up Modem, RS-485 Connection Thirty-one NS2 panels for each drop line. NS2 Configuration Guide NStar Server Refer to 485-PCI / NS2 Panel Connection Detail diagram. N-485-HUB-2 Straight Thru Cable (9-25 Pin) M-9600-2 Female 9 Pin (RX) 2 (TX) 3 (Comm) 5 Male
  • Honeywell NS2 | Configuration Guide - Page 16
    NS2 Configuration Guide M-56K Dial-up Modem, RS-485 Connection Thirty-one NS2 panels for each drop line. Honeywell Access Systems NStar Server Refer to 485-PCI/ NS2 Panel Connection Detail diagram. N-485-HUB-2 COM Port Female 9 Pin (RX) 2 (TX) 3 (Comm) 5 Straight Thru Cable M-56K FAX/MODEM
  • Honeywell NS2 | Configuration Guide - Page 17
    Honeywell Access Systems Fiber Converter to RS-485 Connection Thirty-one NS2 panels for each drop line. NS2 Configuration Guide COM Port Refer to 485-PCI/NS2 Panel Connection Detail diagram. RS-232 (50 Ft. Max.) RS-485 (4000 Ft. Max.) NStar Server N-485-PCI-2 FC485 RS-485 Fiber Converter RXD
  • Honeywell NS2 | Configuration Guide - Page 18
    NS2 Configuration Guide 485-PCI/NS2 Panel Connection Detail DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) To Serial Connection See 485 Interface connection note. Honeywell Access Systems 485 Interface Connection Types RS-485 N-485-
  • Honeywell NS2 | Configuration Guide - Page 19
    with the NStar access control system? NStar software will support up to 128 access points. System expansion is via RS-485 or TCP/IP. How does the NStar software communicate to the NS2 panel? NS2 panels communicate using either RS-485 or RS-232 protocol. Can I upgrade my NStar software to WIN
  • Honeywell NS2 | Configuration Guide - Page 20
    a firmware chip to take advantage of system upgrades or new features. See Honeywell Access Systems website (www.honeywellaccess.com) for further details and downloads. Question: NOTE: NOTE: How do I default the NS2 panel? 1. Change all of the NS2 Panel DIP switches to OFF (address Zero) 2. Power
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

7-101004-01
1
NS2 Configuration Guide
Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Backup Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Secondary Backup Battery. . . . . . . . . . . . . . . . . . . . . . . . 1
Reader & Aux Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Reader Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Supervised Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 2
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Enclosure Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 4
Communications & Wiring . . . . . . . . . . . . . . . . . . . . . . . 4
DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Connection Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Configuration Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
RS-232 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
RS-485 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
NSLAN1 Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
LANSRL100 Connection. . . . . . . . . . . . . . . . . . . . . . . . 10
LANSRLU1 Connection . . . . . . . . . . . . . . . . . . . . . . . . 11
Lease Line Modem Connection . . . . . . . . . . . . . . . . . . . 12
RS-485 Short Haul Modem Connection . . . . . . . . . . . . 13
RS-232 Short Haul Modem Connection . . . . . . . . . . . . 14
M-9600 Dial-up Modem, RS-485 Connection . . . . . . . 15
M-56K Dial-up Modem, RS-485 Connection . . . . . . . . 16
Fiber Converter to RS-485 Connection . . . . . . . . . . . . . 17
485-PCI/NS2 Panel Connection Detail . . . . . . . . . . . . . 18
Frequently Asked Questions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Description
The NS2 is a two reader panel providing access control for up
to two doors through the use of Wiegand readers.
The NS2 may be used as a standalone panel with independent
card and transaction storage or, with a software upgrade, as a
fully monitored online access control device. Communication
to the front-end computer is achieved through an RS-232 serial
cable (included with installation kit) or an optional RS-485
interface. Each RS-485 interface is capable of communicating
with up to 31 panels.
The NS2 is designed for tile mount using the ENC10 enclo-
sure. The I/O terminals are organized by operational utility
with connectors for power and RS-485 communications
located on the lower right followed from right to left by the
relays, auxiliary power, door control inputs, and readers. The
Tamper and External Power Fail terminal are located at the left
edge above the main line of connectors.
Specifications
Power
AC Non-Polarized:
16.5 VAC utilizing a UL-listed 50 VA Class 2 transformer
(TB9-4 AC+/TB9-5 AC–)
or
DC Polarized:
24 VDC, 1.25 Amp (TB9-4 DC+/TB9-5 DC–)
Power Wire
Two-wire, 18 AWG, shielded cable.
Backup Battery
Casil 12 VDC (NCI Part #: BAT-3) 4Ah, sealed acid/lead
backup battery (J6 DC+/J7 DC–)
Backup battery will provide 2.5 hours of standby backup
power.
Charging voltage: 13.7 +/– 0.1 VDC
NOTE:
The NS2 panel has deep discharge protection built in for the
protection of the battery and will only utilize a backup battery down to
10.2 VDC before the NS2 shuts down. Backup battery should be
replaced 2 to 2.5 years: more often if panel has a high rate of backup
use.
Secondary Backup Battery
The NS2 panel memory is backed up using a super capacitor
for one week in the absence of power or a backup battery. The
super capacitor will backup panel memory and real-time clock
and does not require maintenance or replacement.
Reader & Aux Power
Reader and AUX power is supplied at 10.8-12.7 VDC with a
maximum current of 600 mA.
Five volt (5 VDC) readers require five-volt regulators (North-
ern part no. 5VRDREG)
Maximum draw is less then 600 mA: (Reader 1+ Reader 2 +
Aux Power) < 600 mA.
NOTE:
Aux power must not be used to power locks.