Honeywell VISTA 15P Operation Guide

Honeywell VISTA 15P - Ademco 6 Zone Control Panel Manual

Honeywell VISTA 15P manual content summary:

  • Honeywell VISTA 15P | Operation Guide - Page 1
    ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems Installation and Operation Guide K5305-1V8 4/09 Rev. A
  • Honeywell VISTA 15P | Operation Guide - Page 2
    Detectors TO BEDROOM BR BEDROOM LVNG RM KTCHN . CLOSED DOOR GARAGE BASEMENT floor_plan-001-V1 • Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located
  • Honeywell VISTA 15P | Operation Guide - Page 3
    4229 Expansion Zones ...2-7 Installing the RF Receiver and Wireless Transmitter Zones 2-8 Compatible Receivers...2-8 Receiver Connections ...2-8 RF Receiver Notes...2-8 Installing a 5800TM Module ...2-9 Installing the Transmitters ...2-9 Transmitter Battery Life ...2-9 Installing a Keyswitch...2-10
  • Honeywell VISTA 15P | Operation Guide - Page 4
    Code Formats...3-1 Ademco Contact ID® ...3-3 Uploading/Downloading via the Internet ...3-4 System Security Codes ...3-5 Panic Keys...3-7 Setting the Real-Time Clock ...3-7 Various System Trouble Automatic Standby Battery Tests...4-2 Specifications & Accessories...5-1 Security Control...5-1 Compatible
  • Honeywell VISTA 15P | Operation Guide - Page 5
    1 Features and Installation Highlights This manual applies to the following Honeywell security systems: ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred to as VISTA
  • Honeywell VISTA 15P | Operation Guide - Page 6
    Alarm output Auxiliary Power Output Backup Battery Long Range Radio (Communication Device) AC Power Supply VISTA-20P 8 4 Up to 5 for up to 40 exp. zones Up to 40 RF zones Up to 16 2 Up to 48 Partition 1 only Using AAV module 12VDC, 2 AMP output See note. See note. See note. See note. VISTA-15P
  • Honeywell VISTA 15P | Operation Guide - Page 7
    lock knockout from the door. Insert the key into the lock. CHECK POSITION LOCKED PUSH SNAP TAB UNLOCKED CABINET DOOR BOTTOM SNAP TAB STEP 1 PUSH ON LOCK UNTIL IT IS SEATED SECURELY STEP 2 Mounting the PC Board Alone (no RF Receiver) Figure 1. Installing the Cabinet Lock 3. Position the lock
  • Honeywell VISTA 15P | Operation Guide - Page 8
    ARE INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT. ANTENNA MOUNT (2 PLACES) DETAIL B ANTENNA AND GROUNDING LUG INSTALLATION pc_mount-001-V1 Figure 3. Mounting the PC Board and RF Receiver Auxiliary Device Current Draw Worksheet DEVICE CURRENT 6150 Fixed-Word Keypad 40mA/70mA** 6160 Alpha
  • Honeywell VISTA 15P | Operation Guide - Page 9
    AFTER AC POWER IS APPLIED Battery Saver Feature Earth Ground CONTROL BOARD 25 CONNECT PROPER EARTH GROUND IF DESIRED earth_gnd-001-V0 The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored
  • Honeywell VISTA 15P | Operation Guide - Page 10
    output to trip). • You must install a battery, since the battery supplies this current. ALARM OUTPUT 10.5 - 13.5 VDC 2A control's keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program
  • Honeywell VISTA 15P | Operation Guide - Page 11
    14-15 apply to the VISTA-20P. †† Addressable devices are identified by "1" plus the device address when reporting. Enter report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199 for addressable device 3-digit/2-digit identification keypad display
  • Honeywell VISTA 15P | Operation Guide - Page 12
    9 DETECTOR HI LO ZONE 1 2-6 5806-001-V0 This feature provides two hardwired normally closed zones for each standard hardwired zone connected to the control's terminals (but does not increase the total number of zones supported by the control). If enabled (Zone Programming mode, "Hardwire Type
  • Honeywell VISTA 15P | Operation Guide - Page 13
    Output 17 for Power Reset 1. Connect each module to the control's keypad terminals and set the device addresses. See the Table of Device Addresses to select an appropriate address for each module. • VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules. • VISTA-15P: Up to 16 expansion
  • Honeywell VISTA 15P | Operation Guide - Page 14
    TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS. WIRING OPENING KNOCKOUT AREA FOR SURFACE WIRING VISTA-15P: transmitter zones 9-34 button zones 49-56 RF Receiver Notes † These fields must be enabled for Residential Fire, UL Residential Burglar Alarm, and UL Commercial Burglar Alarm installations
  • Honeywell VISTA 15P | Operation Guide - Page 15
    ) or follow the instructions provided with the device. • Use *56 or *58 Zone Programming Menu modes to program zone information and enroll transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons 49-56). • Wireless Keys: Use Wireless Key Programming Templates section of the
  • Honeywell VISTA 15P | Operation Guide - Page 16
    , the keyswitch's tamper switch must be connected in to the alarm system. This tamper switch zone must also be programmed for Zone Type 05 - Trouble by Day / Alarm by Night. • a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad. • Use 4146 keyswitch or any
  • Honeywell VISTA 15P | Operation Guide - Page 17
    the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used) VISTA-15P: Up to 8 devices (if no relays are used) 2. Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode. 3. See connections diagram in
  • Honeywell VISTA 15P | Operation Guide - Page 18
    Wiring the AC Transformer section for transformer connections. • If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied with the control) as shown below. 8-PIN TRIGGER CONNECTOR 1 345678 8-PIN TRIGGER CONNECTOR 1 345678 KEY KEY (RED) (BLACK) (GREEN) +12 AUX. GND
  • Honeywell VISTA 15P | Operation Guide - Page 19
    : 4286 Phone Modules must have software version WA428615.1 or higher (refer to the label on the square 4286 microprocessor chip). UL The 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations. Connect incoming phone line and handset wiring
  • Honeywell VISTA 15P | Operation Guide - Page 20
    UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS system). AUXILIARY AUDIO LEVEL ADJUSTMENT TRIM POT UVCM MODULE CONTROL 45 GND +12VDC 29 30 31 32 33 34 1 2 3 4 5 6 7 8 9 10 11 NOTE: REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO
  • Honeywell VISTA 15P | Operation Guide - Page 21
    AVS operation (refer to the Programming Guide for details of the AVS Quick Command options): a. Install the AVS module according to its instructions. b. Use one of the control's AVS Quick Program commands as follows : • installer code + [#] + 03: enable AVS operation without panel sounds on the AVST
  • Honeywell VISTA 15P | Operation Guide - Page 22
    BUTTON KEYPAD MIC AAV YEL GRN BLK RED FOR EXTERNAL ANTENNA 50 OHM, MMCX ONLY GSM GPPS WEB MODE 2 MODE 1 RSSI TB 1 1 2 3 4 5 6 7 8 9 10 11 Honeywell GSMV (OPTIONAL) BASE UNIT DEVICE ADDRESS VISTA-15P = 8 ON 12345 VISTA-20P = 11 ON 12345 GRY BRN (EARTH GND VISTA SERIES RESIDENTIAL CONTROL
  • Honeywell VISTA 15P | Operation Guide - Page 23
    attempts to the secondary telephone number (if programmed) to get a valid message through. If the panel is not successful after its numerous attempts, the keypad displays COMM. FAILURE (on alpha keypads) or FC (on fixedword keypads). Report Code Formats The following chart indicates the types of
  • Honeywell VISTA 15P | Operation Guide - Page 24
    : SSS or SSSS = Subscriber ID C = Close Code-1st Digit A = Alarm Code-1st digit U = User Number (in hex) Z = Typically Zone Number*-2nd digit Gg = Test Code (1st & 2nd digits) Tt = Trouble Code (1st & 2nd digits) R = Restore Code (Alarm) Bb = Bypass Code (1st & 2nd digits) RTt = Restore
  • Honeywell VISTA 15P | Operation Guide - Page 25
    Trouble Fire Loop Trouble Exit Error Alarm Global Trouble, Trouble Day/Night Code 381 382 383 384 393 401 403 406 407 408 409 441 442 455 459 570 601 602 606 607 623 625 627 628 642 750 789 Definition RF Sensor Supervision Supervision Auxiliary Wire Zone RF Sensor Tamper RF Sensor Low-battery
  • Honeywell VISTA 15P | Operation Guide - Page 26
    if desired. If they are installed on one computer, the computer must have a fixed IP Address. To set up the control panel, do the following: 1. Connect the module to the control panel's ECP (keypad) terminals. 2. Internet Users: For wired modules, connect the module to the Internet via a cable/DSL
  • Honeywell VISTA 15P | Operation Guide - Page 27
    perform all security functions, add/delete users in either partition, change system master code, view event log, set system clock, program keypad macro, program scheduled events, activate output devices (triggers/relays) Partition Master (default) P1 = 03 P2 = 33 VISTA-20P. Same as Master, except
  • Honeywell VISTA 15P | Operation Guide - Page 28
    the security code and press the OFF key) again. Enter code + AWAY [2] or simply press appropriate lettered key on the keypads (see "Single-Button Arming" above). If the "Auto-Stay Arm" feature is enabled (field *84) and the entry/exit door is not opened and closed within the programmed exit delay
  • Honeywell VISTA 15P | Operation Guide - Page 29
    Armed Yes No only those zones listed in NightStay zone list No Yes System Operation Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key can be programmed for 24-hour Silent, 24
  • Honeywell VISTA 15P | Operation Guide - Page 30
    change in the environment that prevents the receiver from receiving signals from a particular sensor. with no zone number indicates that the system's standby battery is weak. with a zone number and a once-per-minute beeping at the keypad indicates that a low-battery condition exists in the wireless
  • Honeywell VISTA 15P | Operation Guide - Page 31
    battery life). 3. Test all sensors using the procedure described in the User's Guide "Testing the System" section. 4. After checking sensors, turn off the test mode by entering installer code keypads in both partitions will display all zone numbers of wireless units (in both partitions) programmed
  • Honeywell VISTA 15P | Operation Guide - Page 32
    by the following key commands: installer code + [#] + 0 + 0 = test report sent every 24 hours installer code + [#] + 0 + 1 = test report sent once per week installer code + [#] + 0 + 2 = test report sent every 28 days Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P) to the selected
  • Honeywell VISTA 15P | Operation Guide - Page 33
    -44003-AL-E 4. Maximum Zone Resistance: Zones 1-8 = 300 ohms excluding EOLR standard zones Compatible Devices Keypads: 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V and 6160V Voice Keypads, 6270 Touch Screen Keypad, Symphony Advanced User Interface Wireless Receivers:5881L/5882L: accepts
  • Honeywell VISTA 15P | Operation Guide - Page 34
    Installation and Setup Guide 2-Wire Smoke Detector: Detector Type Photoelectric w/heat sensor, direct wire Photoelectric, direct wire Photoelectric w/heat sensor, direct wire Photoelectric Photoelectric w/heat sensor Ionization, direct wire Ionization Photoelectric duct detector Ionization duct
  • Honeywell VISTA 15P | Operation Guide - Page 35
    the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15
  • Honeywell VISTA 15P | Operation Guide - Page 36
    ∗81 Zone List mode. 14. Duress code is assigned by using the "add a user code" procedure found in the User Guide. Enable Duress code reporting by programming zone 92 using ∗56 Zone Programming mode. 15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16
  • Honeywell VISTA 15P | Operation Guide - Page 37
    installation. This wireless system, however, can identify a true low-battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system. Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm
  • Honeywell VISTA 15P | Operation Guide - Page 38
    EOLR 2-6, 5-1 Exit Delay 3-7, 3-8 Exit Error Alarm 3-8 Expansion Zones 2-7 Fast Busy Signal 2-13 FCC 6-1 Go/No Go Test Mode 4-2 Handshake 3-1 Hardwired Zones 1-1 HAYES Modem 1-1 House ID 2-9 Ideal Model 61-035 2-3 Installer Code 4-1, 4-2 Keypad Addresses 2-5 Keyswitch 2-10, 3 Kissoff
  • Honeywell VISTA 15P | Operation Guide - Page 39
    IF CONTROL'S VOLTAGE DROPS BELOW 9.6V. ALL DEVICES AND ACCESSORIES USED IN A CANADIAN INSTALLATION MUST BE LISTED FOR USE IN CANADA 6.2k TYPICAL WIRING FOR ZONE DOUBLING (VISTA-20P ONLY) ADEMCO VISTA-20P / VISTA-20PSIA SERIES / VISTA-15P / VISTA-15PSIA SERIES SUMMARY OF CONNECTIONS LO ZONE 8 HI
  • Honeywell VISTA 15P | Operation Guide - Page 40
    WARRANTY INFORMATION For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2004 Honeywell International Inc. www.honeywell.com/security ÊK5305-1V88Š K5305-1V8 4/09 Rev. A
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40

ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems
Installation and Operation Guide
K5305-1V8
4/09
Rev. A