LG PQDSBC Owner's Manual - Page 11
Control mode setting
View all LG PQDSBC manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 11 highlights
Setting and using method 4. Control mode setting I Use the CONTROL_MODE_SW to set the control mode you want from 0~D. CONTROL_MODE_SW ➲ Indoor control priority Central control > Dry contact for communication > Wired/Wireless remote controller, indoor unit button ➲ Dry contact for communication controls the indoor unit according to the applicable mode when there is a change in input of A and B. I Description of each control mode 1) Cancel mode for use of dry contact for communication CONTROL_ MODE S/W 0 Input A OFF ON OFF ON Input B OFF OFF ON ON Operating mode The indoor unit cannot be controlled through the Dry contact for communication No change in indoor unit condition ➲ Set this when the Dry contact for communication is connected but not used. Owner's & installation manual 11