LG PQDSBC Owner's Manual - Page 13

Fan level setting mode, Power save mode, Input A, Input B, Operating mode

Page 13 highlights

Setting and using method 3) Fan level setting mode CONTROL_ MODE S/W 7 8 Input A OFF ON OFF ON OFF ON OFF ON Input B OFF OFF ON ON OFF OFF ON ON Operating mode Indoor unit operating at low level, locked Indoor unit operating at low level, unlocked Indoor unit stopped, locked Indoor unit stopped, locked Indoor unit operating at low level, locked Indoor unit operating at low level, unlocked Indoor unit stopped, locked Indoor unit prior operating condition maintained, unlocked ➲ When the indoor unit is operating in Dry contact for communication, the fan level can be changed by other controller when the fan level is set to low level and the indoor is in unlocked condition. 4) Power save mode CONTROL_ MODE S/W 9 A Input A OFF ON OFF ON OFF ON OFF ON Input B OFF OFF ON ON OFF OFF ON ON Operating mode Indoor unit operating in power save mode, locked Indoor unit operating in power save mode, unlocked Indoor unit stopped, locked Indoor unit operating not in power save mode, unlocked Indoor unit operating in power save mode, locked Indoor unit operating in power save mode, unlocked Indoor unit stopped, locked Indoor unit stopped, locked ➲ When setting 9, A mode, the TEMP_SETTING must always be set to ON. ➲ Power save mode: Adjust the set temperature to +3°C for cooling and -3°C for heating. Owner's & installation manual 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

Setting and using method
Owner’s & installation manual
13
3) Fan level setting mode
4) Power save mode
When the indoor unit is operating in Dry contact for communication, the fan level can be changed by
other controller when the fan level is set to low level and the indoor is in unlocked condition.
When setting 9, A mode, the TEMP_SETTING must always be set to ON.
Power save mode: Adjust the set temperature to +3
°
C for cooling and -3
°
C for heating.
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit operating at low level, locked
Indoor unit operating at low level, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit operating at low level, locked
Indoor unit operating at low level, unlocked
Indoor unit stopped, locked
Indoor unit prior operating condition maintained, unlocked
CONTROL_
MODE S/W
7
8
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit operating in power save mode, locked
Indoor unit operating in power save mode, unlocked
Indoor unit stopped, locked
Indoor unit operating not in power save mode, unlocked
Indoor unit operating in power save mode, locked
Indoor unit operating in power save mode, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
CONTROL_
MODE S/W
9
A