    ® ® ® ® Installation Manual for EL MODELS Telephone entry/access control system © 2010 The Chamberlain Group, Inc. All Rights Reserved
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 2
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 3
    Table of Contents Mounting the Unit Dimensions EL25 Installation Rotating the Keypad for Vertical Mounting Unlocking/Locking ... and Checking the LEDs 20 20-21 22 Troubleshooting Repair Parts Repair Parts 23-24 "Your" Set-Up "Your" System Diagram and Wiring Configuration Accessories FCC and...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 4
    Dimensions EL25 Units 6 in. 3-1/16 in. 10-1/4 in. 3-15/16 in. 3 in. 3-1/16 in. 1-1/16 in. Conduit Hole Mounting Holes (4) for 5/16 in. 5-1/8 in. Dimensions Caution! A Static Discharge can Damage Circuit Boards EL2000 Units Knockouts for 3/8 in. Knockouts for 5/16 in. 9 in. AUG 10, 2005 ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 5
    EL25 Installation Caution! A Static Discharge can Damage Circuit Boards 1 Unlock Unit. NOTE: ... Hinge Out. 5 Remove Back Mounting Plate from Cover. EL25 Installation Screw Notch DO NOT pinch ...! A Static Discharge can Damage Circuit Boards 1 For EL25 ONLY Disconnect all Plugs from Main Circuit ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 6
    # # # # # # Unlocking EL2000 1. Apply pressure to the right-side of the unit. 2. While maintaining pressure, turn key clockwise. # 1 2 3 1 4 2 5 3 6 ? 1 2 5 3 6 ? # # 4 1 2 4 5 3 6 7 8 9 7 8 ? 9 * 0 # * 0 # 7 8 * # 0 9 # # 3. Open cover. # Unlocking/...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 7
    EL2000 Installation NOTE: This unit is for surface and recessed mount ONLY. 1 Unlock Unit. 2 Open Cover. 1 2 5 3 6 ? 4 7 8 9 1 2 4 5 * 0 # # 3 6 ? 7 8 # * 9 0 # EL2000 Model Installation 4 3 Unplug the 2 Main Harnesses (Optional). Slide Front Cover Out of Hinges (...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 8
    Wire Connections to the Unit IO Output Board EXIT REQ 4 COM DOOR STAT 4 EXIT REQ 3 COM DOOR STAT 3 EXIT REQ 2 NO J5 4 J7 10 LED 4 NC C RELAY 4 NO RES 3 J6 POSTAL 5 6 7 J3 J6 8 J4 11 NC C LED 3 RELAY 3 NO Wire Connections to the Unit COM DOOR STAT 4 EXIT REQ 1 COM DOOR STAT 1 2 ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 9
    .... The high voltage may interfere with the Telco Wires, possibly causing the system to malfunction. * Total distance from Telco to residence regardless of number of ...to its own 10 AMP minimum circuit breaker. This will prevent two problems: • Other equipment cannot introduce spikes, noise, surges or...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 10
    Grounding the Units Ensure that the system is grounded properly. The units contain a number of static sensitive components that can be damaged by static discharge. ... units to a pedestal post (gooseneck) if one is used. Earth Ground Rod Ground to Existing Electrical System Electrical Panel Page 8
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 11
    ... the unit to be disconnected without interrupting normal telephone operation. NOTE: Installation where fiber optic ... may require additional modifications from your telephone provider. Contact your provider for more ..., you MUST connect the telephone line to the alarm system first. If the units are not ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 12
    ...Tip Ring IMPORTANT: You must program the unit ID's for each unit wired in the series. See Keypad Programming Manual. Never run Telco wires and High Voltage wires in the same conduit. The high voltage wires may interfere with the Telco wires, ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 13
    ... IMPORTANT: You must program the unit ID's for each unit wired in the series. See Keypad Programming Manual. IMPORTANT: Only disable the Telco mode of the unit farthest away from the house. See "Disable Telco Mode" in the Keypad Programming Guide....
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 14
    ... (Up to 7) IMPORTANT: You must program the Unit ID's for each unit wired in the series. See Keypad Programming Manual. To next unit (Unit ID 5 then 4 etc.) Unit ID 1 is farthest away from Telco Box. IO Output Board NO J5 NC LED 4 C ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 15
    ...NO J5 NC Wiring to an Internal Phone System LED 4 C RELAY 4 NO J4 NC C LED 3 EX 1 T R Tip Ring Ring Use 18-24 AWG 2 ... program the unit ID's for each unit wired in the series. See Keypad Programming Manual. To next unit (Unit ID 5 then 4 etc.) Unit ID 1 is farthest away from Telco Box. IO Output ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 16
    ... (Up to 7) IMPORTANT: You must program the Unit ID's for each unit wired in the series. See Keypad Programming Manual. To next unit (Unit ID 5 then 4 etc.) Unit ID 1 is farthest away from Telco Box. IO Output Board NO J5 NC LED 4 C ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 17
    Wiring a Door Strike Lock Output Board (See page 6) DO NOT overload the removable terminal block connectors. One wire per hole. IO Output Board NO J5 NC C RELAY 4 NO J4 J6 NC C LED 3 LED 4 RES Wiring a Door Strike Lock/Maglock RELAY 3 NO Normally Open TELCO For AC Power: Install a Siemens ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 18
    ... 18-24 AWG NOTE: The gate operator can be connected to any of the 4 relays. C LED 1 RELAY 1 NOTE: Refer to your gate operators owner's manual for proper relay strike time. Wiring a Key Switch/PIR/REX Any auxiliary opening device such as a key switch or PIR (Passive Infrared Device), or an exit...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 19
    Wiring a Door Sensing Device The units can monitor the position of up to four doors/gates and may react to a change in their status with one of the relays (not set as a control relay). For example, if a door is pried open or is held open after its relay deactivates, the unit will record the breach ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 20
    ... if the residents will access a controlled area with a transmitter. Refer to instructions supplied with the optional RF Module for more information. NOTE...2 optional Wiegand modules that can be placed in the unit. Each Wiegand module supports two card readers/keypads. Some Wiegand card reader/keypads ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 21
    ... activate one of the four relays (Configurable with programming number 69 , in the Keypad Programming Manual). J7 Wiring a Postal Lock Switch / Internal Camera (CCTV) In J6 N.C. ... (Monitor with a .25 volt p-p composite signal sensitivity) EL25 EL2000 A Closed Circuit Monitor Page 19
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 22
    ... back to its own 10 Amp minimum circuit breaker. This will prevent two problems: • Other equipment cannot introduce spikes, noise, surges or dips into ... all connections have been made. Any other type of outlet will cause damage to the system. Wiring Power to the Unit AC Power 12 Vac or 16 Vdc EL ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 23
    ...Label D300 J405 J500 J406 Used on Model EL25 EL2000 X X X X X X X 5 6 7 8 9 10 11 12 13 14 ... and Power. Provides power to LCD Display. For the EL25 provides power to bottom lighted LEDs for .... Measure the voltage at power block J1 to confirm. For the EL25, provides power to the top lighted LEDs for...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 24
    ... with Unit • Make sure Wiegand is configured to a door (program step 60). • Check Wiegand reader module connections... Did you assign a relay to the REX? See the unit's programming manual. • Check connections at Door # terminal(s). Wires to "COM" and "EXT REQ #" connection. Transmitter...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 25
    Repair Parts Installation and Service Information is Available EL25 Parts 4 6 5 1 Call our Toll Free Number 1-800-528-2806 www.chamberlain.com 21 12 2 ...20-Pin Cable, EL25 Focus Assembly, 14-Pin Cable, EL25 Focus Assembly, Call Button Board Direct Connect Cable ...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 26
    ...21 Part Description Interconnect Board Assembly, Lock and Key EL2000 Replacement Key Assembly, Keypad 16 Button Gasket, Keypad Assembly, Mike Cable EL Series Assembly, Entry LED Board Assembly, Keypad Light Board Lens Black, Camera Lens Clear, Camera Gasket and Display Window...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 27
    Your System Diagram Your System Diagram Page 25
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 28
    Your Wiring Configuration External Access Control Device(s) connected to optional board(s) (Default Internal Keypad) Device 0 _____ J400 Position on Main Board RF Module Wiegand Device 1 _____ Wiegand Device 2 _____ J407 Position on Main Board Your Wiring Configuration RF Module Wiegand Device 3...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 29
    ...Directory Insert ELDI Wiegand Module Kit WOMODKT EL25 Camera Kits EL25BWCAMKT (Black & White Camera... EL2000 Heater Kit ELHTRKT EL2000 ONLY EL25 1 4 7 2 5 8 0 3 6 9 ? * # For Single Quic k St F rt Gu id... phone line. These ue, it is th end user e to e o the man nsure that the tota lc uals and...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 30
    ... right to file a complaint with the FCC. Your Telephone Company may make changes in its facilities,..., to give you an opportunity to maintain uninterrupted telephone service. Connections to party lines are subject ... cannot be used on public coin service lines provided by the telephone company. FCC and...
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 31
  • LiftMaster EL25 | EL25 Installation Ver. 3.0 Manual - Page 32
    ® ® 845 Larch Avenue Elmhurst, Illinois 60125-1196 114A4170B © 2010 The Chamberlain Group, Inc. All Rights Reserved