Panasonic MVA24FBAS6HBCP MVA24FBAS6HBCP - Vertical Air Handler 24 000 BTU Indo

Panasonic MVA24FBAS6HBCP Manual

Panasonic MVA24FBAS6HBCP manual content summary:

  • 1
  • 2

Split System Submittal Data
MVA24FBAS6HBCP
Indoor Unit: Vertical Air Handler
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Capacities
Total Cooling: Btu/h
24,700
Sensible Cooling: Btu/h
16,200
Heating: Btu/h
28,000
Sensible Heat Ratio
0.66
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
80/67
Outdoor: °F DB
95
Pipe Length: Feet
25
Level Difference: Feet
0
Heating Mode Nominal Conditions
Indoor: °F DB
70
Outdoor: °F DB/°F WB
47/43
Pipe Length: Feet
25
Level Difference: Feet
0
Coil
Coil Face Area: (sq. ft.)
2.01
Number of Rows
4
Condensate
Drain Piping, Inches FPT
3/4
Fan
Type
Forward Curved
Drive
Direct
Fan Motor Output (W)
396
Airflow Rate (H/M/L)
882/769/718
External Static Pressure (in WC)
0.3
Max. Available ESP (in WC)
0.5
Power Supply
V/PH/Hz.
208/230/1/60
Full Load Amps
3.00
Minimum Circuits Amps (MCA):
Amps
3.8
Max. Overcurrent Protection
(MOCP)
15
Parts Warranty: One Year
Right Horizontal Options
Electric Heat - Factory or Field Installed
Weight
Weight: (lbs)
165
Refrigerant and Piping
Refrigerant Type
410A
Metering Device (Electronic
Expansion Valve)
EEV
Liquid Piping (inches)
3/8
Gas Piping (inches)
7/8
Data is Subject to Change.