Panasonic S-18MK1U6 CZ-CLNC1U Installation Manual

Panasonic S-18MK1U6 Manual

Panasonic S-18MK1U6 manual content summary:

  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 1
    • Consult the dealer or an experienced radio/TV technician for help. FCC Caution: To assure continued compliance, follow the attached installation instructions. Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 2
    1. LonWorks Interface Overview Product Overview This interface is a communications interface for connecting LonWorks to an air conditioner unit control network. From the host connected to LonWorks, basic settings and status monitoring is possible for up to 16 groups of A/C units. System Diagram
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 3
    Functions Start/stop A/C unit settings from the LonWorks Settings for each group of indoor units Temp. setting(*1) Operation mode Option 1 settings(*2) Option 2 settings(*2) Settings for all units Emergency stop Start/stop Temp. setting Operation mode A/C unit status notifications made to
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 4
    a test run to check for operating trouble. As you do, use the central control device Operating Instructions and explain operating procedures to the customer. Then request that the customer store this manual together with the central control device Operating Instructions. Warning • Be sure to arrange
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 5
    conduit, or place the cables near one another. Doing so can cause the system to malfunction. • Before turning the power on, follow the instruction in Power Board Initial Settings. • When using the spare inter-unit cotrol line, connect [1] and [3] at CN002. • When using the spare LON communication
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 6
    Indoor Unit Enabling Switches 1 2 3 4 OFF OFF Indoor unit group 3 is disabled. ON Indoor unit group 3 is enabled. OFF Indoor unit group 2 is disabled. ON Indoor unit group 2 is enabled. OFF Indoor unit group 1 is disabled. ON Indoor unit group 1 is enabled. OFF Indoor unit group 0 is disabled.
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 7
    Product Specifications Connects to LonWorks network FTT-10 A transceiver device Power 100-120/200-240 V 50/60 Hz 1-PH Power consumption 11 W max. Service environment conditions Temp. 32 to 104°F, humidity 20 to 80% Indoor use only External dimensions 3-7/64 in.(H) × 19-11/16 in.(W) × 8-15/32
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 8
    3. Assigning Central Control Addresses • Before assigning central control addresses for the LonWorks Interface, use the remote controller to make central control address settings for A/C units. • Follow only the steps for "Assigning Central Control Addresses" when a system controller or other
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 9
    4. LonWorks Interface Test Run Before performing a test run of the LonWorks Interface, perform test runs of the A/C units and assign central control addresses for A/C units. [LonWorks Interface Test Run Procedure] (1) Press and hold touch-switch S001 on the main circuit board for 5 seconds or
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 10
    5. Checking the LonWorks Interface Version (1) Press touch-switch S002. Version display mode is enabled on that circuit board for a period of 18 seconds. LD001 illuminates, and LD002 flashes at high speed. COM Lit 12 High-speed flashing (2) While the version is displayed (18 seconds), the
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 11
    6. List of LonWorks Network Variables A/C unit Indoor group 0 Indoor group 1 Indoor group 2 Indoor group 3 Indoor groups 0 - 3 Input/output Input Output Input Output Input Output Input Output Input Item Start/stop Temp. setting Operating mode Option 1 setting Option 2 setting Start/stop status
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 12
    7. Details of LonWorks Network Variables [nv1] Unit start/stop command network input SNVT_switch nviOnOff_00; network input SNVT_switch nviOnOff_01; network input SNVT_switch nviOnOff_02; network input SNVT_switch nviOnOff_03; [nv4] Temperature setting status notification network output SNVT_temp_p
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 13
    [nv7] Option 1 setting command [nv9] Option 2 setting command network input SNVT_switch nviOption1_00; network input SNVT_switch nviOption1_01; network input SNVT_switch nviOption1_02; network input SNVT_switch nviOption1_03; network input SNVT_switch nviOption2_00; network input SNVT_switch
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 14
    [nv11] Alarm notification network output SNVT_switch nvoAlarm_00; network output SNVT_switch nvoAlarm_01; network output SNVT_switch nvoAlarm_02; network output SNVT_switch nvoAlarm_03; These output network variables are output when an alarm occurs at an indoor unit, and when the alarm is reset at an
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 15
    8. Locations Where Neuron ID is Applied The Neuron ID is applied in the following 3 locations. (1) Packaging box (2) Top panel lid (3) On the main circuit board Neuron chip Neuron ID Node0 : 00 03 18 69 95 01 Node1 : 00 03 18 69 96 01 Node2 : 00 03 18 69 97 01 Node3 : 00 03 18 69 98 01 (1) (2)
  • Panasonic S-18MK1U6 | CZ-CLNC1U Installation Manual - Page 16
    1BOB@$;$-/$6@&OHJOEE Printed in Japan
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

––
Contents
––
1.
LonWorks Interface Overview
2
Product Overview
System Diagram
Functions
2.
Installation Instructions of LonWorks Interface
4
Safety Precautions
Included Parts
Installation Method
Wiring Specifications
LonWorks Interface Structure
Power Board Initial Settings
5
Power Board Wiring
Wiring Procedure
Main Circuit Board
Indoor Unit Enabling Switches
6
Setting Switches
Address Switches
Communications LED (Green)
7
Data LED (Red)
Diagram of External Dimensions
Product Specifications
3.
Assigning Central Control Addresses
8
4.
LonWorks Interface Test Run
9
5.
Checking the LonWorks Interface Version
10
6.
List of LonWorks Network Variables
11
7.
Details of LonWorks Network Variables
12
8.
Locations Where Neuron ID is Applied
15
Note:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: To assure continued compliance, follow the attached installation instructions.
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
operate this equipment.
LonWorks is a registered trademark of the Echelon Corporation.
85464369526011
INSTALLATION INSTRUCTIONS
LonWorks Interface
Model No. CZ-CLNC1U
Pana_CZ-CLNC1U_Eng.indd 1
Pana_CZ-CLNC1U_Eng.indd
1
2011/11/11 12:23:41
2011/11/11
12:23:41