Panasonic S-36MF2U6 - Submittal

Panasonic S-36MF2U6 Manual

Panasonic S-36MF2U6 manual content summary:

  • Panasonic S-36MF2U6 | - Submittal - Page 1
    ECO-i™ Submittal Data S-36MF2U6 Indoor Unit: Concealed Ducted Job Name: Location: Engineer: Submitted to: Submitted by: Reference: Capacities Cooling: Btu/h Heating: Btu/h Sensible Heat Ratio 36,000 39,000 0.76 Cooling Mode Nominal Conditions Indoor: °F DB/°F WB 80/67 Outdoor: °F DB 95 Pipe
  • Panasonic S-36MF2U6 | - Submittal - Page 2
    Dimensions Panasonic North America Air Conditioning Division 1690 Roberts Blvd., NW, Suite 110 Kennesaw, GA 30144 http://www.panasonic.com/aircon
  • 1
  • 2

ECO-i
Submittal Data
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit#:
Drawing#:
Data is Subject to Change.
Capacities
Cooling: Btu/h
36,000
Heating: Btu/h
39,000
Sensible Heat Ratio
0.76
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
80/67
Outdoor: °F DB
95
Pipe Length: Feet
25
Level Difference: Feet
0
Heating Mode Nominal Conditions
Indoor: °F DB
70
Outdoor: °F DB/°F WB
47/43
Pipe Length: Feet
25
Level Difference: Feet
0
Refrigerant and Piping
Refrigerant Type
410A
Metering Device (Electronic
Expansion Valve)
EEV
Liquid Piping (Inches)
3/8
Gas Piping (Inches)
5/8
Condensate
Drain Piping (OD) Inches
1.25
Fan
Type
Centrifugal
Drive
Direct
Fan Motor Output: (W)
235
Airflow rate (L/M/H)
812/989/1204
External Static Pressure (in.WG)
0.28 - .60
Power Supply
V/PH/Hz.
208 - 230/1/60
Minimum Circuits Amps (MCA): (A)
15
Nominal Power Input - Cooling (W)
220
Full Load Amps (FLA): (A)
1.53
Max. Overcurrent Protection
(MOCP): (A)
15
Nominal Power Input - Heat (W)
220
Parts Warranty: One Year
Built in Drain Pump
Bottom or Rear Return Air
Remote Sensor Option
Wired or Wireless Remote Control
Weight
Weight: (lbs)
99
Sound Data
Sound Level (L/M/H) 5' below
unit (dB-A)
32/35/39
Coil
Coil Face Area: (sq. ft.)
4.34
Number of Rows
3
S-36MF2U6
Indoor Unit: Concealed Ducted