ECO-i™ Submittal Data
System:
U-240ME2U9
Heat Pump: 20 Ton System
U-72ME2U9 & U-72ME2U9 & U-96ME2U9 Combination
General Data
Capacities
Rated Cooling Capacity: Btu/h
240,000
Power input: kW
18.2
Rated Heating Capacity: Btu/h
270,000
Power input: kW
20.6
Cooling Mode Nominal Conditions
Indoor: °F WB/°F DB
80/67
Outdoor: °F DB
95
Pipe Length: Feet
25
Level Difference: Feet
0
Heating Mode Nominal Conditions
Indoor: °F DB
70
Outdoor: °F DB/°F WB
47/43
Pipe Length: Feet
25
Level Difference: Feet
0
Operating Range
Cooling: °F DB
14 to 122
Heating: °F WB
-4 to 64
Compressor
Type/Quantity
3 Inverter driven Rotary
Capacity Control Range: %
7 - 100%
Operation Sound dB (A)
61 (Quiet mode: 58)
Fan
Type/Quantity
1 Propeller
Fan Motor Output: (kW)
0.75 kW
External Static Pressure
0 / 0.32
Power Supply
V/PH/Hz.
208 - 230/3/60
Minimum Circuits Amps (MCA): (A)
30 + 30 + 38
Max. Overcurrent Protection
(MOCP): (A)
50 + 50 + 60
Weight: (lbs)
Net
503 + 503 + 560
Shipping
554 + 554 + 591
Refrigerant
410A
Coil
Coil Face Area: (sq. ft.)
32 + 32 + 32
Number of Rows
2 & 2 & 3
Protection Devices
High Pressure Switch
Yes
Overcurrent (CT Method)
Yes
Crankcase Heaters: (W)
30 + 30 + 30
External Finish
Polyester Powder Double Coating
Coil Finish
Hydrophilic Silicate Coating
Performance Data
EER
IEER
COP
Ducted
11.5
19.6
3.4
Non-Ducted
11.9
23.9
3.2
Mix
11.7
21.8
3.3
Compressor Warranty: Six Years.
Parts Warranty: One Year.
Data is subject to change.
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
No
Picture