ECO-i™ Submittal Data
System:
U-336ME2U9
Heat Pump: 28 Ton System
U-96ME2U9 & U-120ME2U9 & U-120ME2U9 Combination
General Data
Capacities
Rated Cooling Capacity: Btu/h
336,000
Power input: kW
27.4
Rated Heating Capacity: Btu/h
378,000
Power input: kW
29.1
Cooling Mode Nominal Conditions
Indoor: °F WB/°F DB
80/67
Outdoor: °F DB
95
Pipe Length: Feet
25
Level Difference: Feet
0
Heating Mode Nominal Conditions
Indoor: °F DB
70
Outdoor: °F DB/°F WB
47/43
Pipe Length: Feet
25
Level Difference: Feet
0
Operating Range
Cooling: °F DB
14 to 122
Heating: °F WB
-4 to 64
Compressor
Type/Quantity
5 Inverter driven Rotary
Capacity Control Range: %
5 - 100%
Operation Sound dB (A)
64 (Quiet mode: 61.0)
Fan
Type/Quantity
1 Propeller
Fan Motor Output: (kW)
0.75 kW
External Static Pressure
0 / 0.32
Power Supply
V/PH/Hz.
208 - 230/3/60
Minimum Circuits Amps (MCA): (A)
30 + 46 + 46
Max. Overcurrent Protection
(MOCP): (A)
60 + 60 + 60
Weight: (lbs)
Net
560 + 664 + 664
Shipping
591 + 699 + 699
Refrigerant
410A
Coil
Coil Face Area: (sq. ft.)
32.0 + 37.8 + 37.8
Number of Rows
2 & 2 & 2
Protection Devices
High Pressure Switch
Yes
Overcurrent (CT Method)
Yes
Crankcase Heaters: (W)
30 & 30 + 30 & 30 + 30
External Finish
Polyester Powder Double Coating
Coil Finish
Hydrophilic Silicate Coating
Performance Data
EER
IEER
COP
Ducted
10.3
17.2
3.23
Compressor Warranty: Six Years.
Parts Warranty: One Year.