Panasonic XE15WKUA Installation Manual

Panasonic XE15WKUA Manual

Panasonic XE15WKUA manual content summary:

  • Panasonic XE15WKUA | Installation Manual - Page 1
    connection cable, refer to instruction 5 INDOOR/OUTDOOR UNIT indoor/outdoor unit installation. Guide surface Connection cable Connection grille if necessary such Front as when servicing. grille 1. Set the vertical air ensure opposite side of vane is supported to prevent vane damage by overpush
  • 1

PUSH
PUSH
Piping
Piping
Shock absorber
Intake grille
p
u
l
l
o
u
t
t
h
e
p
i
p
i
n
g
p
u
l
l
o
u
t
t
h
e
p
i
p
i
n
g
INDOOR UNIT
INDOOR UNIT INSTALLATION
Rear view for left piping installation
Drain cap
Indoor unit
drain hose
3/4" (20 mm) nominal PVC pipe
- Install incline downward more than 1°
- Apply PVC glue at the join.
Drain hose adapter
7
Close join by Vinyl Tape (
)
Drain hose
Adjust the piping
slightly downwards.
How to insert the connection cable
and drain hose in the case of left
piping.
Join indoor drain hose to 3/4"
(20 mm) nominal PVC pipe size
by using drain hose adapter
7
when necessary.
(For right piping, follow the same
procedure)
Guide
surface
Connection cable
Connection
cable
Gas side
piping
Liquid side
piping
Drain hose
Cover for the
bottom piping
Tape it with piping in a
position as mentioned in
Fig. below.
Piping
Drain hose
Cover for
the left
piping
Cover for the
bottom piping
Cover for the
bottom piping
Tape it with
piping in a position as
mentioned in
Fig. below.
Piping
Drain
hose
Cover
for the
left
piping
Press the lower left and
right side of the unit
against the installation
plate until hooks engage
with their slot (sound click).
Cover for piping
In case the cover is cut, keep the
cover at the rear of chassis as
shown in the illustration for future
reinstallation.
(Left and 2 bottom covers for piping.)
How to keep the cover
Hook the indoor unit onto the
upper portion of installation
plate. (Engage the indoor unit
with the upper edge of the
installation plate). Ensure the
hooks are properly seated
on the installation plate by
moving it in left and right.
IMPORTANT
1.
This product has been designed and manufactured to meet
ENERGY STAR®
criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant
charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions.
Failure to con
°
rm proper charge and air
°
ow may reduce energy ef
°
ciency and shorten equipment life.
2.
This model is equipped with Room Freeze Protection (RFP) feature. Room Freeze Protection function (RFP) is used in spaces that are unoccupied during the winter, for the purpose
of protecting any equipment or appliances which may be destroyed as a result of freezing temperature. When the RFP is selected, the unit will operate the fan at high speed for proper
room temperature monitoring. When the sensor detects that the room temperature has dropped below 46°F (8°C), the compressor/heat pump operation begins. When the room
temperature reaches 50°F (10°C), the unit shuts off, then will repeat continuously if the temperature drops below 46°F (8°C) again.
The Room Freeze Protection function (RFP) cannot be used unless the unit is energized and set into the RFP mode. In the advent of a power failure this mode will not function. During
the RFP mode, POWERFUL OPERATION, QUIET OPERATION AND FAN SPEED selection are all disabled. Please consult with your HVAC installer or professional for more details.
Read the following “SAFETY PRECAUTIONS” carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.
The items to be followed are classified by the symbols:
Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in
instructions. Please remind the customer to keep the operating instructions for future reference.
SAFETY PRECAUTIONS
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
WARNING
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over
the handrail causing an accident.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact,
poor insulation or over current will cause electrical shock or fire.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specified refrigerant, eg. air etc mix into refrigeration cycle (piping). Mixing of air etc will
cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.
For R32/R410A model, use piping, flare nut and tools which is specified for R32/R410A refrigerant. Using of existing (R22) piping, flare nut and tools may cause abnormally
high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used.
Since the working pressure for R32/R410A is higher than that of refrigerant R22 model, replacing conventional piping and fl
are nuts on the outdoor unit side are recommended.
If reuse piping is unavoidable, refer to instruction “IN CASE OF REUSING EXISTING REFRIGERANT PIPING”
Thickness for copper pipes used with R32/R410A must be more than
1
/
32
" (0.8 mm). Never use copper pipes thinner than
1
/
32
" (0.8 mm).
It is desirable that the amount of residual oil is less than 0.00004 oz/ft (40 mg/10 m).
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fire.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For installation work, follow all electrical, building, plumbing, local codes, regulations and these installation instructions. If electrical circuit capacity is not enough or a defect is
found in electrical work, it will cause electrical shock or fire.
Do not use spliced wires for indoor / outdoor connection cable. Use the specified indoor / outdoor connection cable, refer to instruction
5
INDOOR/OUTDOOR UNIT
ELECTRICAL WIRING
and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fixing is
not perfect, it will cause heat-up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause fire or electrical shock.
This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance Leakage Current Interrupter (ALCI) that
has been certified by an NRTL Certified Testing Agency and that is suitable for the voltages and amperages involved. Otherwise, if may cause electrical shock and fire in case
of equipment breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fixing refrigeration piping and valves at opened
condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are
opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.
After completion of installation, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant comes into contact with fire.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant comes into contact with fire.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electrical
shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fin, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Power supply connection to the room air conditioner.
Power supply cord shall be UL listed or CSA approved 3 conductor with minimum AWG14 wires.
Power supply point should be in an easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
Fix power supply connection to a circuit breaker for permanent connection.
Use NRTL approved fuse or circuit breaker (rating refers to name plate) for permanent connection.
Installation work.
It may take two people to carry out the installation work.
Replace the drain hose
Drain hose adapter
7
usage
1. FOR THE RIGHT REAR
PIPING
Step-1
Pull out the Indoor
piping
Step-2
Install the Indoor Unit
Step-3
Secure the Indoor Unit
Step-4
Insert the connection
cable
2. FOR THE RIGHT BOTTOM
PIPING
Step-1
Pull out the Indoor
piping
Step-2
Install the Indoor Unit
Step-3
Insert the connection
cable
Step-4
Secure the Indoor Unit
3. FOR THE EMBEDDED
PIPING
Step-1
Replace the drain hose
Step-2
Bend the embedded
piping
Use a spring bender or equivalent
to bend the piping so that the
piping is not crushed.
Step-3
Pull the connection
cable into Indoor Unit
The inside and outside connection
cable can be connected without
removing the front grille.
Step-4
Cut and flare the
embedded piping
When determining the dimensions
of the piping, slide the unit all the
way to the left on the installation
plate.
Refer to the section “Cutting and
flaring the piping”.
Step-5
Install the Indoor Unit
Step-6
Connect the piping
Please refer to “Connecting the
piping” column in outdoor unit
section. (Below steps are done
after connecting the outdoor piping
and gas-leakage confirmation.)
Step-7
Insulate and finish the
piping
Please refer to “Insulation of piping
connection” column as mentioned
in indoor/outdoor unit installation.
Step-8
Secure the Indoor Unit
Do not turn over the unit
without it’s shock absorber
during pulling out the piping.
It may cause intake grille
damage.
Use shock absorber
during pulling out
the piping to protect
the intake grille from
damage.
Right Rear piping
Right Bottom piping
Install the indoor unit
Secure the Indoor Unit
To take out the unit,
push the
marking at
the bottom unit, and pull
it slightly towards you to
disengage the hooks from
the unit.
Insert the connection cable
(This can be used for left rear piping and bottom piping also.)
Drain hose
Sleeve for
piping hole
Indoor unit
Hooks at
installation
plate
Piping
Installation
plate
Unit’s hook
g
n
i
k
r
a
m
Drain hose
Connection cable
Sleeve for piping hole
Drain hose
Piping
Connection cable
Cable
45°
Drain
hose
Piping
About
2
3
/
4
" - 3
5
/
32
"
(70-80 mm)
More than 37
13
/
32
"
(950 mm)
How to pull the piping and drain hose out, in case
of embedded piping
.
PVC tube
for drain
hose
Indoor unit
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connection
cable
Piping
PVC tube (VP-65) for piping
and connection cable
PVC tube for drain hose (VP-30)
PVC tube for drain
hose (VP-20)
Drain hose
from main unit
4
17
/
64
" (108 mm)
More than
18
1
/
2
" (470 mm)
More than
37
13
/
32
"
(950 mm)
More than
27
9
/
16
"
(700 mm)
Remarks :
Make sure indoor unit drain hose
& 3/4" (20 mm) nominal PVC pipe
are fully inserted to drain hose
adapter
7
.
Piping direction
Do not bend up
drain hose
(Front side)
Right
Rear
Right
bottom
Left
Rear
Left bottom
Left
Indoor/Outdoor Unit Installation Diagram
Applicable piping kit
Piping size
Gas
Liquid
CZ-3F5, 7BP
3/8" (9.52 mm)
1/4" (6.35 mm)
CZ-4F5, 7, 10BP
1/2" (12.7 mm)
1/4" (6.35 mm)
CZ-52F5, 7, 10BP
5/8" (15.88 mm)
1/4" (6.35 mm)
This illustration is for
explanation purposes only.
The indoor unit will actually face
a different way.
It is advisable to avoid more
than 2 blockage directions.
For better ventilation &
multiple-outdoor installation,
please consult authorized
dealer/specialist.
INDOOR UNIT
Do not install the unit in excessive oil fume area such as kitchen, workshop and etc.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Indoor unit of this air conditioner shall be installed in a height of at least 1.8 m.
SELECT THE BEST LOCATION
OUTDOOR UNIT
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat
radiation from the condenser is not obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If piping length is over the [piping length for additional gas], additional refrigerant should
be added as shown in the table.
Recommended installation height for outdoor unit should be above the seasonal
snow level.
Be careful not to locate outdoor unit directly under a roof line where falling snow or ice
can cause damage or dripping water can increase ice accumulation and defrost cycles.
Model
Capacity
(Btu/h)
Piping size
Std.
Length
Max.
Elevation
Min.
Piping
Length
Max.
Piping
Length
Additional
Refrigerant
Piping
Length for
add. gas
Gas
Liquid
XE9****
8700
3/8"
(9.52 mm)
1/4"
(6.35 mm)
24.6 ft
(7.5 m)
49.2 ft
(15 m)
9.8 ft
(3 m)
65.6 ft
(20 m)
0.2 oz/ft
(15 g/m)
24.6 ft
(7.5 m)
XE12****
11500
1/2"
(12.7 mm)
XE15****
14700
0.2 oz/ft
(20 g/m)
Example: For XE9****
If the unit is installed at 32.8 ft (10 m) distance, the quantity of additional refrigerant
should be 1.64 oz (37.5 g)
....
(32.8 - 24.6) ft x 0.2 oz/ft = 1.64 oz. ((10-7.5) m
x 15 g/m = 37.5 g).
(Left and right are identical)
Installation plate
1
Sleeve (
)
Bushing-Sleeve (
)
Bend the pipe as
closely on the wall
as possible, but be
careful that it doesn’t
break.
Saddle (
)
Additional drain
hose (
)
Gas side piping (
)
Connection cable (
)
Power supply cord (
)
Putty (
)
(Gum Type Sealer)
Installation parts you
should purchase (
)
Vinyl tape (wide) (
)
Apply after carrying
out a drainage test.
To carry out the
drainage test, remove
the air filters and pour
water into the heat
exchanger.
Liquid side piping (
)
Remote control holder fixing screws
6
Remote control holder
5
Remote
control
3
Attaching the remote control holder
to the wall
Vinyl tape
Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Insulation of piping connections
2
9
/
16
"
(65 mm)
or more
1
31
/
32
"
(50 mm)
or more
3
15
/
16
"
(100 mm)
or more
39
3
/
8
"
(1000 mm)
or more
3
15
/
16
"
(100 mm)
or more
11
13
/
16
"
(300 mm)
or more
Attached accessories
No.
Accessories part
Qty
No.
Accessories part
Qty
1
Installation plate
1
5
Remote control holder
1
2
Installation plate fixing
screw
5
6
Remote control holder
fixing screw
2
3
Remote Control
1
7
Drain hose adapter
1
4
Battery
2
8
Drain elbow
1
9
Rubber cap
4
Air conditioner
Installation Instruction
MODEL NO. :-
CS-XE9, XE12, XE15WKUA Series.
CU-XE9, XE12, XE15WKUA Series.
Required tools for Installation Works
1
Philips screw driver
2
Level gauge
3
Electric drill, hole core drill (ø2
3
/
4
" (ø70 mm))
4
Hexagonal wrench (
5
/
32
" (4 mm))
5
Spanner
6
Pipe cutter
7
Reamer
8
Knife
9
Gas leak detector
10 Measuring tape
11 Thermometer
12 Megameter
13 Multimeter
14 Torque wrench
13.3 Ibf•ft (18 N•m (1.8 kgf•m))
31.0 Ibf•ft (42 N•m (4.3 kgf•m))
40.6 Ibf•ft (55 N•m (5.6 kgf•m))
47.9 Ibf•ft (65 N•m (6.6 kgf•m))
73.8 Ibf•ft (100 N•m (10.2 kgf•m))
15 Vacuum pump
16 Digital Micron Gauge
ACXF60-38950-AB
2
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
The center of installation plate should be at more than
1
at right and left of the wall.
The distance from installation plate edge to ceiling should more than
2
.
From installation plate left edge to unit’s left side is
3
.
From installation plate right edge to unit’s right is
4
.
b
: For left side piping, piping connection for liquid should be about
5
from this line.
: For left side piping, piping connection for gas should be about
6
from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2. Drill the piping plate hole with ø2
3
/
4
" (ø70 mm) hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 5
1
/
16
" (128 mm) for left and right
hole respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
Model
Dimension
A
B
C
D
E
F
XE9****, XE12****, XE15****
19
9
/
32
"
(490 mm)
3
35
/
64
"
(90 mm)
17
9
/
32
"
(439 mm)
17"
(432 mm)
1
11
/
16
"
(43 mm)
3
3
/
4
"
(95 mm)
Wall
Wall
Wall
Installation
plate
1
2
screw
More than
A
More than
A
Measuring
Tape
9
17
/
32
"
(241.5 mm)
9
17
/
32
"
(241.5 mm)
5
1
/
16
"
(128 mm)
More
than
B
5
1
/
16
" (128 mm)
5
1
/
16
"
(128 mm)
6
5
3
4
DISTANCE TO
PIPE HOLE
CENTER
128 mm
DISTANCE TO PIPE HOLE
CENTER 128 mm
PIPE HOLE CENTER
PIPE HOLE
CENTER
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
1
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about
19
/
32
" (15 mm) from the wall.
4. Finish by sealing the sleeve with putty
or caulking compound at the final stage.
TO DRILL A HOLE IN THE WALL AND
INSTALL A SLEEVE OF PIPING
Putty or caulking compound
Indoor
Outdoor
Sleeve
for tube
assembly
Bushing for tube
assembly
Wall
CAUTION
When the wall is hollow, please be sure
to use the sleeve for tube assembly to
prevent dangers caused by mice biting
the connection cable.
19
/
32
" (15 mm)
ø2
3
/
4
"
(ø70 mm)
through hole
Approx.
7
/
32
" -
9
/
32
"
(5-7 mm)
3
4
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs are not removed, gas leakage may be
caused. Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the copper pipes.
1. To cut
When properly flared, the internal surface of the
flare will evenly shine and be of even thickness.
Since the flare part comes into contact with the
connections, carefully check the flare finish.
Improper flaring
Inclined
Surface
damaged
Cracked
Uneven
thickness
3. To flare
Bar
Handle
Core
Yoke
Clamp handle
Bar
0 –
1
/
32
" (0-0.5 mm)
Copper
pipe
Reamer
2. To remove burrs
Point down
Pipe
Red arrow mark
CONNECT THE CABLE TO THE INDOOR
UNIT
5
1. The inside and outside connection cable can be connected without removing the front grille.
2. Unscrew the conduit cover and fix the conduit connector to conduit cover with lock nut, then secure it
against chassis.
3. Connection cable between indoor unit and outdoor unit should be UL listed or CSA approved 4 conductor
wires minimum AWG16 in accordance with local electric codes.
Ensure the colour of wires of outdoor unit and terminal number are the same as the indoor's repectively.
Terminals on the indoor unit
1
2
3
Colour of wires (connection cable)
Terminals on the outdoor unit
1
2
3
Earth lead wire shall be Yellow/Green (Y/G) in colour and shall be longer than other lead wires as shown
in the figure for electrical safety in case of slipping.
WARNING
This equipment must be properly earthed.
Rear Side of Indoor Unit
Chassis
Conduit Connector
Conduit Cover
Lock Nut
Holder
Indoor and
outdoor
connection
cable
Terminal
Board
Earth wire
longer than
others
AC wires
for safety
reason
Wire stripping
7
/
32
" (5 mm)
or more
(gap between wires)
ACCEPT
PROHIBITED
Conductor
over inserted
No loose strand
when inserted
Indoor/outdoor
connecting
terminal board
Conductor
fully inserted
PROHIBITED
Conductor not
fully inserted
WIRE STRIPPING AND CONNECTING REQUIREMENT
13/32" ± 1/16"
(10 ± 1 mm)
PRINTED IN MALAYSIA
ACXF60-38950-AB
ENGLISH
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at
flare nut connection?
Is the connection cable being fixed to terminal
board firmly?
Is the connection cable being clamped firmly?
Is the drainage ok?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the
installation plate?
Is the power supply voltage complied with
rated value?
Is there any abnormal sound?
Is the cooling/heating operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
CHECK THE DRAINAGE
Open front panel and remove air filters.
(Drainage checking can be carried out without removing the front grille.)
Pour a glass of water into the drain tray-styrofoam.
Ensure that water flows out from drain hose of the indoor unit.
Drain
tray-
styrofoam
EVALUATION OF THE PERFORMANCE
Operate the unit at cooling/heating operation mode for fifteen minutes or more.
Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and the discharge is
more than 46.4°F (8°C) during Cooling operation or more than 57.2°F (14°C)
during Heating operation.
Discharge air
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed
and released before 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously
for more than 5 sec. to below 8 sec..
A “pep” sound will occur at the fifth sec., in order to identify the starting of Test Run
operation.
3. HEATING TRIAL OPERATION
Press the “AUTO” switch continuously for more than 8 sec. to below 11 sec. and release when a “pep pep” sound
is occured at eight sec. (However, a “pep” sound is heard at fifth sec..) then press Remote controller “A/C Reset”
button once. Remote controller signal will activate operation force heating mode.
4. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be changed by the following steps:
a) Press “AUTO” switch continuously for more than 16 sec. to below 21 sec..
A “pep”, “pep”, “pep”, “pep” sound will occur at the sixteenth sec..
b) Press the “AC Reset” button once, “pep” sound will occur indicates that Remote controller receiving sound
setting mode is activated.
c) Press “AUTO” switch again. Everytime “AUTO” switch is pressed (within 60 sec. interval),
Remote controller receiving sound status will be reversed between ON and OFF.
Long “peep” sound indicates that Remote controller receiving sound is ON.
Short “pep” sound indicates that Remote controller receiving sound is OFF.
AUTO SWITCH OPERATION
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
The unit should be mounted on a stand that suits to a local environmental
requirement.
When the Drain elbow
8
being used, please ensure to:-
- Provide a minimum clearance of 2" (50mm) to access the bottom of
base pan.
- Seal the four 25/32" (20mm) diameter holes with Rubber caps
9
(refer to illustration at right).
- Use a rigid or flexible PVC pipe (local supply) to dispose drained water from the elbow or use a stainless steel tray
(local supplied) to collect and dispose water.
If the unit is used in an area where temperature falls below 32°F (0°C) for 2 or 3 consecutive days, it is recommended
not to use the Drain elbow
8
and Rubber caps
9
, water from defrost process will trap, freeze up and obstruct fan
rotation. Water may drip from the basepan hole area during defrost function, do not stand or place objects underneath.
Drain
elbow
8
Rubber
cap
9
x 4
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if necessary such
as when servicing.
1. Set the vertical airflow direction vane to the horizontal position.
2.
Remove the 2 caps on the front grille as shown in the illustration
at right, and then remove the 2 mounting screws.
3. Remove screw on the right side of airflow vane.
Slide the lever, from locked position into released position.
Take out vane.
(When remove the screw, ensure opposite side of vane is
supported to prevent vane damage by overpush)
4.
Pull the lower section of the front grille towards you to remove the front grille.
When reinstalling the front grille, carry out above step 2 - 3 in the reverse order.
Cap
Screw
Front
grille
Vane
(Move the
vane to
downward)
Lever
Slightly lift this shape
by finger to move lever
LOCKED
position
RELEASED
position
Slide this lever to left to release
Screw
HOW TO REPLACE NETWORK ADAPTER
Remove the front grille (refer how to take out front grille) from the unit.
Remove the network adapter box by releasing the hook (Figure 1.0).
Remove the cover by unclipping it and pulling it out (Figure 1.1)
Remove the top casing by pressing the side of the network adapter box. (Figure 1.2)
After that, network adapter can be easily replaced (Figure 1.3).
.
i
.
i
.
i
.
i
Hook
Figure 1.0
Figure 1.1
Figure 1.2
Figure 1.3
Unclip & pull down
Press
Press
IN CASE OF REUSING EXISTING REFRIGERANT PIPING
Observe the followings to decide reusing the existing refrigerant piping.
Poor refrigerant piping could result in product failure.
In the circumstances listed below, do not reuse any refrigerant piping. Instead, make sure to install a
new piping.
- Heat insulation is not provided for either liquid-side or gas-side piping or both.
- The existing refrigerant pipe has been left in an open condition.
- The diameter and thickness of the existing refrigerant piping does not meet the requirement.
- The piping length and elevation does not meet the requirement.
Perform proper pump down before reuse piping.
In the circumstances listed below, clean it thoroughly before reuse.
- Pump down operation cannot be performed for the existing air-conditioner.
- The compressor has a failure history.
- Oil color is darken. ( ASTM 4.0 and above ).
- The existing air-conditioner is gas/oil heat pump type.
Do not reuse the flare to prevent gas leak. Make sure to install a new flare.
If there is a welded part on the existing refrigerant piping, conduct a gas leak check on the welded part.
Replace deteriorated heat insulating material with a new one.
Heat insulating material is required for both liquid-side and gas-side piping.
Proper Pump Down Method
Most Important Process
Purpose: To make the oil
& refrigerant mix together.
They are in separated
condition when
air conditioner
is stopped.
Mixed refrigerant
& oil will be
collected into
outdoor unit.
Only very small
amount of oil remain
inside piping, which
is acceptable.
1
Operate air conditioner
at cooling mode for
10 ~ 15 minutes.
2
After 10 ~ 15 minutes of pre
operation, close 2 way valve.
After 3 minutes, close 3 way
valve.
3
Take out air
conditioner
unit.
4
Install New
Refrigerant air
conditioner.
OUTDOOR UNIT
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
CONNECT THE PIPING
Please make flare after inserting flare nut (locate at joint
portion of tube assembly) onto the copper pipe. (In case of
using long piping)
Connect the piping
Align the center of piping and sufficiently tighten the flare nut
with fingers.
Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
Connecting The Piping to Indoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make flare after inserting the flare nut (locate at valve)
onto the copper pipe.
Align center of piping to valve and then tighten with torque
wrench to the specified torque as stated in the table.
Torque
wrench
Spanner
or Wrench
Connecting The Piping to Outdoor
Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system.
If the pressure holds, release the nitrogen and proceed to section 4.
Gas Leak Checking
Do not over tighten, overtightening may cause gas leakage.
Piping size
Torque
1/4" (6.35 mm)
13.3 Ibf•ft [18N•m (1.8 kgf•m)]
3/8" (9.52 mm)
31.0 Ibf•ft [42 N•m (4.3 kgf•m)]
1/2" (12.7 mm)
40.6 Ibf•ft [55 N•m (5.6 kgf•m)]
5/8" (15.88 mm)
47.9 Ibf•ft [65 N•m (6.6 kgf•m)]
3/4" (19.05 mm)
73.8 Ibf•ft [100 N•m (10.2 kgf•m)]
1
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally with a bolt nut ø13/32" (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.
INSTALL THE OUTDOOR UNIT
A
B
C
D
Model
A
B
C
D
XE9****
XE12****
21
1
/
4
"
(540 mm)
6
19
/
64
"
(160 mm)
23
/
32
"
(18.5 mm)
12
63
/
64
"
(330 mm)
XE15****
24
1
/
8
"
(613 mm)
5
5
/
32
"
(131 mm)
15
/
16
"
(24 mm)
14
3
/
16
"
(360.5 mm)
2
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation
by using POLY-E FOAM with thickness 1/4" (6 mm) or above.
PIPING INSULATION
6
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR
UNIT AND PIPES in the following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the
3-way valve.
2. Connect the micron gauge between vacuum pump and service port of outdoor units.
3. Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and
to pull down to a value of 500 microns.
4. To make sure micron gauge a value 500 microns and close the low side valve of the charging set and
turn off the vacuum pump.
5. Disconnect the vacuum pump house from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valv
e at a torque of 13.3 Ibf•ft (18 N•m) with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to
“Open” using a hexagonal wrench (5/32" (4 mm)).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
If micron gauge value does not descend 500 microns, take the following measures:
- If the leak stops when the piping connections are tightened further, continue working from step
3
.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Be careful with the liquid refrigerant, it may cause frostbite.
Gas side
Liquid side
Outdoor unit
Two-way valve
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
EVACUATION OF THE EQUIPMENT
4
3
CONNECT THE CABLE TO THE OUTDOOR
UNIT
Model
XE9**** , XE12****
1.
Remove Top panel.
2.
Remove Control Board Cover (Resin and Metal).
3. Remove plugs.
4.
Fix the conduit connectors to the knockout holes with lock-nuts,
then secure them against the side panel.
5.
All wires pass through conduits .
6.
Connection wires between indoor unit and outdoor unit should
be UL listed or CSA approved 4 conductor wires minimum
AWG16 in accordance with local electric codes.
7.
Wire connection to the power supply (208/230V 60Hz) through
circuit breaker.
Connect the UL listed or CSA approved wires minimum
AWG14 to the terminal board, and connect the other end
of the wires to ELCB/GFCI.
8.
Connect the power supply cord and connection wires between
indoor unit and outdoor unit according to the diagram below.
9.
Secure the wire onto the control board with the holder (clamper).
10. After completing wiring connections, reattach the control board
cover (Metal and Resin) and the top panel to the original
position with the screws.
11. For wire stripping and connection requirement, refer to
instruction
5
of indoor unit.
Model
XE15****
1.
Remove control board cover (Resin and Metal).
2. Remove particular plate.
3. Remove plugs.
4.
Fix the conduit connectors to the knockout holes with lock-nuts,
then secure them against the side panel.
5.
All wires pass through conduits & particular plate’s opening hole.
6.
Connection wires between indoor unit and outdoor unit should
be UL listed or CSA approved 4 conductor wires minimum
AWG16 in accordance with local electric codes.
7.
Wire connection to the power supply (208/230V 60Hz) through
circuit breaker.
Connect the UL listed or CSA approved wires minimum
AWG14 to the terminal board, and connect the other end
of the wires to ELCB/GFCI.
8.
Connect the power supply cord and connecting wire between
indoor unit and outdoor unit according to the diagram below.
9.
Secure the wire onto the control board with the holder (clamper).
10. After completing wiring connections, reattach the particular
plate and control board cover (metal and resin) to the original
position with the screws.
11. For wire stripping and connection requirement, refer to
instruction
5
of indoor unit.
Earth lead wire shall be Yellow/Green (Y/G) in colour and should be longer than
other lead wires as shown in the figure for electrical safety in case of slipping.
WARNING
This equipment must be properly earthed.
Outdoor Unit
1
2
3
1
2
L1
L2
3
l
a
n
i
m
r
e
T
l
a
n
i
m
r
e
T
Indoor Unit
Disconnect Switch
Field supply
Grounding wire
Grounding wire
min AWG16
Power Supply
Single Phase
208/230V 60Hz
min AWG14
208/230V min AWG16
208/230V min AWG16
208/230V min AWG16
Holder
Power supply
cord
Indoor & outdoor
connection cable
Earth wire
longer
than other
AC wires
for safety
reasons
Earth wire
longer
than other
AC wires
for safety
reasons
Terminal
Board
5
Control Board
Cover (Metal)
Lock Nuts
Knockout
Holes
Connecting
wires
Side Panel
Top Panel
Control Board
Cover (Resin)
Connectors
Plugs
Control Board
Cover (Metal)
Lock Nuts
Knockout
Holes
Front Panel
Connecting wires
Control Board
Cover (Resin)
Connectors
Particular Plate
Plugs
Particular Plate
Opening hole