Tripp Lite 5P1550GR Eaton 5P UPS Installation and User Manual
Tripp Lite 5P1550GR Manual
View all Tripp Lite 5P1550GR manuals
Add to My Manuals
Save this manual to your list of manuals |
Tripp Lite 5P1550GR manual content summary:
- Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 1
Copyright © 2012 EATON All rights reserved. Service and support: Call your local service representative 620-00082-01-us (en) Installation and user manual Tower models 5P 750 5P 1000 5P 1500 5P 850G 5P 1550G 1U Rack models 5P 550 R 5P 750 R 5P 1000 R 5P 1500 R 5P 850G R 5P 1550G R ENGLISH - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 2
Page 2 620-00082-01-us (en) - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 3
. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 4
system. It should be opened exclusively by qualified service personnel. • The system must be properly grounded • The UPS connection instructions and operation described in the manual must be followed in ANSI/NFPA 75 (US installations only). Contact Eaton resellers to order a special battery kit, if - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 5
Shutdown...20 4.4 Operation on Battery Power 20 4.5 Return of AC Input Power 21 4.6 UPS remote control functions 21 5. Maintenance 22 5.1 Troubleshooting...22 5.2 Battery-module replacement 23 6. Appendices 25 6.1 Technical specifications...25 6.2 Glossary...27 620-00082-01-us (en) Page 5 - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 6
booklet presenting the safety instructions. Then follow the instructions in this manual. To discover the entire range of EATON products and the options . End of life EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 7
ENGLISH 2.1 Standard installations Tower models D H Description 5P 750 5P 1000 5P 1500 5P 850G 5P 1550G W Weights (lb/kg) 22.7 / 10.3 24.4 / 11.05 35.3 / 16.01 21.9 / 9.9 35.2 / 15.9 Dimensions (inch/mm) D x W x H 13.6 x 5.9 x 9.1 / 345 x 150 x 233 13.6 x 5.9 x 9.1 / 345 x 150 x 233 17.5 x 5.9 - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 8
2. Presentation 2.2 Tower rear panels 5P 750 / 5P 1000 6a 5 3 2 6b 1 8 4 7 9 5P 1500 6a 5 3 2 6b 1 4 9 7 8 5P 850G 6a 5 3 2 6b 1 7 4 8 5P 1550G 6a 5 3 2 6b 1 4 8 7 Page 8 (1) USB communication port (2) RS232 communication port (3) Slot for optional - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 9
ENGLISH 2.3 Rack rear panels 5P 550 R / 5P 750 R / 5P 1000 R 8 7 2149 5 6a 6b 3 5P 1500 R 387 2149 5 6a 6b 2. Presentation (1) USB communication port (2) RS232 communication port (3) Slot for optional communication card (4) Connector for ROO (remote ON/OFF) or RPO (Remote Power OFF) - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 10
Green The UPS is operating normally. On Yellow On Red The UPS is on battery mode. The UPS has an active alarm or fault. See troubleshooting on page 18 for additional information. Page 10 620-00082-01-us (en) - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 11
button to restore the screen. The following table describes the status information provided by the UPS Note: If other indicator appears, see troubleshooting on page 18 for additional information. Operation status Standby mode Possible cause Action The UPS is OFF, waiting for start-up Equipment - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 12
user settings for load segments. Start battery test Starts a manual battery test Reset fault state Clears active faults (UPS restart and alarms, UPS fault, Event Log data and settings are in all supported languages. Modify LCD screen brightness and contrast to adapt to room light conditions - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 13
ENGLISH 2. Presentation In/Out settings ON/OFF settings Battery settings Description Load segments - Auto shutdown delay Overload prealarm Cold start Forced reboot Auto restart Energy saving Sleep mode Remote command RPO delay Automatic battery test Low battery warning Restart battery level - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 14
3. Installation 3.1 Unpacking and contents check Tower models 1 8 4 2 3 5 Rack models 9 1 2 6 3 7 8 4 5 (1) 5P UPS (2) Quick start and safety instructions (3) User manual and IPSS (Intelligent Power Software Suite) CD-ROM (4) RS232 communication cable (5) USB communication cable (6) 1U Rack - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 15
ENGLISH 3. Installation 3.2 Battery module connection (Tower) Caution: Before starting the UPS, please connect the internal battery. Note: A small amount of arcing may occur when connecting the batteries. This is normal and does not damage the UPS or present any safety concern. A - R emove front - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 16
3. Installation 3.4 Installation of tower models 3.5 Installation of rack model for 2 post (option) Follow steps 1 to 5 for 2 post mounting. 1 1 2 2 3 3 5 4 5 Use optional 1U 2 post rail kit. Page 16 620-00082-01-us (en) - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 17
3 for rack mounting. 1 2 3 3. Installation 2 3 3.7 Installation of rack models Follow steps 1 to 4 for module mounting on the rails. 1 1 2 3 2 3 4 4 The rails and necessary hardware are supplied by EATON. 620-00082-01-us (en) Page 17 - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 18
3. Installation 3.8 Installation of rack model for wall mounting 1 2 1 1 2 2 Page 18 620-00082-01-us (en) - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 19
end of the communication cable (5) or (6) to the USB (1) or RS232 (2) communication port on the UPS. The UPS can now communicate with EATON power management software. Installation of the communication cards (optional, standard on the Network bundle models) It is not necessary to shutdown the UPS - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 20
power cord is plugged in. 2. The UPS front panel display illuminates and shows EATON logo. 3. Verify that the UPS status screen shows . 4. Press the button active alarms or notices. Resolve any active alarms before continuing. See "Troubleshooting" on page 22. If the indicator is on, do not proceed - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 21
. • RPO: Remote Power Off allow a remote contact to be used to disconnect all the equipment connected to the UPS. Restarting the UPS requires manual intervention. • ROO: Remote ON/OFF allows remote action of button to shut down the UPS. These functions are obtained by opening a contact connected - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 22
5. Maintenance 5.1 Troubleshooting Operation status Batteries disconnected Overload End of battery if the load increases. The alarm resets when the condition becomes inactive. Contact your service representative for battery replacement. Event UPS fault An UPS event occurs Example: Remote Power OFF - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 23
-circuit currents. The following safety precautions are required before servicing the battery components: • remove watches, rings, bracelets and module Carry out the above instructions in reverse order. • To ensure safety and high performance, use only batteries supplied by EATON. • Take care to - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 24
remove the battery block and replace it. E Mounting the new battery module Carry out the above instructions in reverse order. • To ensure safety and high performance, use only batteries supplied by EATON. • Take care to firmly press together the two parts of the connector during remounting. Page 24 - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 25
ENGLISH 6.1 Technical specifications Filter Transformer "AVR" Charger Inverter 6. Appendices Battery Tower Rack Output Power @ 120 V Output Power capacity @ 125 V Output Power @ 100 V AC Input power • Rated input voltage • Input voltage range • Input frequency range Output on battery - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 26
6. Appendices 6.1 Technical specifications Filter Transformer "AVR" Charger Inverter Battery Tower Rack Output Power @ 230 V Output Power capacity @ 208 V Output Power @ 200 V AC Input power • Rated input voltage • Input voltage range • Input frequency range Output on battery power • - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 27
ENGLISH 6. Appendices 6.2 Glossary Backup time Time during which the load can be supplied by the UPS operating on battery power. Battery test Internal UPS test to check battery status. Cold start Deep discharge Load The devices connected to the UPS can be started even if AC input power is - Tripp Lite 5P1550GR | Eaton 5P UPS Installation and User Manual - Page 28
Page 28 620-00082-01-us (en)
ENGLISH
Tower models
5P 750
5P 1000
5P 1500
5P 850G
5P 1550G
Copyright © 2012
EATON
All rights reserved.
Service and support:
Call your local service representative
620-00082-01-us (en)
1U Rack models
5P 550 R
5P 750 R
5P 1000 R
5P 1500 R
5P 850G R
5P 1550G R
Installation
and user manual