Tripp Lite 9PX1000RT 9PX1000RT runtime chart

Tripp Lite 9PX1000RT Manual

Tripp Lite 9PX1000RT manual content summary:

  • 1

Extended
Battery Module
200
300
350
400
450
500
550
600
650
700
750
800
850
900
9PX1000RT
Internal batteries
0
45
29
25
21
18
16
14
12
11
10
8.5
7.7
6.9
6.3
9PX1000RT
9PXEBM36RT
1
138
89
75
64
56
50
44
40
36
33
30.0
28.0
26.0
24.0
9PX1000RT
9PXEBM36RT
2
248
161
135
116
101
89
79
71
64
59
54.0
50.0
46.0
43.0
9PX1000RT
9PXEBM36RT
3
370
239
201
172
150
132
117
105
95
87
80.0
74.0
68.0
64.0
9PX1000RT
9PXEBM36RT
4
501
324
272
233
203
178
159
143
129
118
108.0
99.0
92.0
86.0
9PX1000RT Estimated Runtime
UPS
EBM
QTY
CONNECTED EQUIPMENT LOAD IN WATTS
All runtime values are shown in minutes.