Tripp Lite 9PX1500RT 9PX1500RT runtime chart

Tripp Lite 9PX1500RT Manual

Tripp Lite 9PX1500RT manual content summary:

  • Tripp Lite 9PX1500RT | 9PX1500RT runtime chart - Page 1
    UPS 9PX1500RT 9PX1500RT 9PX1500RT 9PX1500RT 9PX1500RT 9PX1500RT Estimated Runtime Extended Battery Module Internal batteries 9PXEBM48RT 9PXEBM48RT 9PXEBM48RT 9PXEBM48RT EBM QTY 0 1 2 3 4 CONNECTED EQUIPMENT LOAD IN WATTS 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,250 1,300 64
  • 1

Extended
Battery Module
200
300
400
500
600
700
800
900
1,000
1,100
1,200
1,250
1,300
1,350
9PX1500RT
Internal batteries
0
64
42
31
24
19
16
13
11
10
8
7.1
6.6
6.2
5.8
9PX1500RT
9PXEBM48RT
1
239
157
115
89
72
60
51
44
39
34
31.0
29.5
28.0
27.0
9PX1500RT
9PXEBM48RT
2
440
290
212
164
133
111
95
82
72
64
57.0
54.0
52.0
50.0
9PX1500RT
9PXEBM48RT
3
656
432
315
245
199
166
141
122
107
95
86.0
81.0
78.0
74.0
9PX1500RT
9PXEBM48RT
4
886
583
426
331
268
224
191
165
145
129
116.0
110.0
105.0
100.0
9PX1500RT Estimated Runtime
UPS
EBM
QTY
CONNECTED EQUIPMENT LOAD IN WATTS
All runtime values are shown in minutes.