Tripp Lite 9PX1500RTL Eaton 9PX Lithium-Ion Owners Manual

Tripp Lite 9PX1500RTL Manual

Tripp Lite 9PX1500RTL manual content summary:

  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 1
    Eaton 9PX Lithium-Ion Eaton 9PX Lithium-Ion Advanced Users Guide 9PX1500RT-L / 9PX2200RT-L / 9PX3000RT-L / 9PX1500GRT-L / 9PX2200GRT-L / 9PX3000GRT-L / 9PXEBM48RT-L / 9PXEBM72RT-L p/n: P-164001006 Revision 01
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 2
    . This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 3
    resent within the system. It should be opened exclusively by qualified service personnel. • The system must be properly grounded at all times. supply circuit). Product Safety • To connect the UPS, instructions and operation described in the manual must be followed in the indicated order. • CAUTION -
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 4
    there are any questions, don't hesitate to contact your local EATON representative. • All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS. • For potential safety issue on defective UPS : DISCONNECT INTERNAL BATTERY for
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 5
    Table of Contents 1 Introduction ...1 1.1 Introduction...1 1.2 Environmental Protection ...1 2 Presentation ...3 2.1 Standard Installations ...3 2.2 Rear Panels ...4 2.3 Accessories...5 2.4 Control Panel ...5 2.5 LCD Description ...6 2.6 Display Functions ...7 2.7 User Settings...8 3 Installation
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 6
    the UPS Equipped with a HotSwap MBP 35 6.4 Recycling The Used Equipment ...35 7 Troubleshooting ...37 7.1 Typical Alarms and Faults ...37 7.2 Silencing the Alarm ...38 7.3 Service and Support ...38 7.4 CE Compliance Contact ...39 8 Specifications ...41 8.1 Model Specifications ...41 vi Eaton
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 7
    9PX, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products of Life Eaton will process products at the end of their service life in compliance with local regulations. Eaton works with companies in charge of
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 8
    compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing center for least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 9
    Chapter 2 Presentation 2.1 Standard Installations Figure 1. Tower Installation D W H Figure 2. Rack Installation D Table 2. Weights and Dimensions Model 9PX1500RT-L 9PX2000RT-L 9PX3000RT-L 9PX1500GRT-L 9PX2200GRT-L 9PX3000GRT-L 9PXEBM48RT-L 9PXEBM72RT-L H W Dimensions D x W x H(inch/mm) 17.7 x
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 10
    Rear Panels 2.2 Rear Panels 9PX 1500RT-L 1 23 4 5 6 11 10 9 8 9PX 2000RT-L 1 238 4 7 5 6 9 11 10 7 9PX 3000RT-L (*) 1 238 4 5 6 1 Socket for connection to AC power source 2 Slot for optional communication card 3 Relay output contact 4 Connector for additional battery module 5
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 11
    Accessories 9PXEBM48RT-L 12 9PXEBM72RT-L 13 12 Connectors for battery modules (to the UPS or to the other battery modules) 13 Connectors for automatic recognition of battery modules 12 13 12 2.3 Accessories Table 3. UPS Accessories Part number 9PXEBM48RT-L 9PXEBM72RT-L 9RK Network-M2 INDGW-
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 12
    LCD Description Online mode indicator (green) Battery mode indicator (orange) Fault indicator (red) Bypass mode indicator (orange) Online mode 100% 2.4k W 3.0kVA Efficiency: 94 % 100% 19min 1EBM Escape Up Down Enter On/Off button Indicator Green Orange Orange Red 2.5 LCD Description
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 13
    Display Functions The following table describes the status information provided by the UPS Note: If other indicator appears, see the troubleshooting for additional information. Table 4. LCD Operating Status Operation status Standby mode Cause The UPS is Off, waiting for startup command from user.
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 14
    information or Menu function Commands the load segments Starts a manual battery test Tests dry contact relay outputs and relay card notices and alarms, UPS fault, Event Log data and settings are in all supported languages. Format: [International] [US] Default settings [English] User selectable when
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 15
    User Settings Table 6. User Settings (Continued) Submenu Available settings Default settings LCD Audible alarm Modify LCD screen brightness and contrast to be adapted to room light conditions. Mode: [Enabled] [Disabled on battery] [Always disabled] Enable or disable the buzzer if an alarm
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 16
    User Settings Table 6. User Settings (Continued) Submenu Available settings to Disabled, shutdown sequence will not complete, UPS stays on. Default settings Energy saving [Enabled] [Disabled] [Timer] [1min] ... [15min] [Level] [100W] ... [1000W] If Enabled, UPS will shut-down after defined
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 17
    User Settings Table 6. User Settings (Continued) Submenu Available settings Default settings - [Function]: [No] [ROO] [RPO] [Building No alarm] [Forced bypass] [On generator] [Remote shutdown] - [Delay]: [0s] ... [999s] - [Active]: [Open] [Closed] [0s] [Open] DB9-4 port: No - [Function]: [
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 18
    User Settings Table 6. User Settings (Continued) Submenu On battery notice delay General alarm Available settings [Group 2] [Group 1 + Group 2] [OFF delay]: [0s] ...[999s] [Restart]: [Yes] [No] [0s] ... [99s] Sets delay before noticing on battery information to software. [On battery] [Battery
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 19
    ; 2. Send a copy of the damage claim within 15 days to your service representative. ! IMPORTANT Check the battery recharge date on the shipping carton label. lea et 22 Safety instructions 23 Quick start 24 Mounting kit for 19-inch enclosures 25 2 supports for tower position Elements supplied
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 20
    systems 21 Software lea et 22 Safety instructions 23 Quick start 24 Mounting kit for 19-inch enclosures 25 2 supports for tower position Elements supplied depending on 3 Rack kit for 19-inch enclosures (optional) 4 EBM Installation manual. 4 1 2 3 14 Eaton 9PX Lithium-Ion P-164001006-Rev 01
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 21
    are installing the EBM with a new UPS at the same time. Use the UPS user's guide to install both the UPS and the EBM. Remember If you ordered other UPS accessories, refer to specific user manuals to check the packing contents. 3.3 Connecting the Internal Battery NOTE Do not connect the UPS to
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 22
    Tower Installation 3.4 Tower Installation Tip If you ordered other UPS accessories, refer to specific user manuals to check the tower installation with the UPS. To install the cabinet: 1. Place the UPS on a flat, stable surface in its final location. 2. Always keep 6"
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 23
    Rack Installation 3.5 Rack Installation • Rack mounting of UPS, EBM, and accessory modules. Follow steps 1 to 4 for module mounting on the rails. 1 1 2 3 3 4 4 The rails and necessary hardware are supplied by EATON. Eaton 9PX Lithium-Ion P-164001006-Rev 01 17
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 24
    Connecting the EBM(s) 3.6 Connecting the EBM(s) CAUTION A small amount of arching may occur when connecting an EBM to the UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly. 1. Plug the EBM power cable(s) into the battery
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 25
    , regulation and lifecycle monitoring of the integrated battery management system (BMS). 3.7 Detecting other Accessories Tip If you ordered other UPS accessories, refer to specific user manuals to check the connection to the UPS. Eaton 9PX Lithium-Ion P-164001006-Rev 01 19
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 26
    UPS Connection without Hotswap MBP Module 3.8 UPS Connection without Hotswap MBP Module Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and the true electrical consumption of the total load. 1. 9PX 2000RT-L / 3000RT-L connect the UPS
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 27
    with a Hotswap MBP Module ( Optional Accessory) 3.9 Connection with a Hotswap MBP Module ( Optional Accessory) The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. 9PX 2000RT-L 1 238 4 5 6 1. Connect the input 36 on the HotSwap
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 28
    Connection with a Hotswap MBP Module ( Optional Accessory) 9PX 2200GRT-L & 9PX 3000GRT-L 5 1 MBP 6 7 28 29 30 31 32 33 34 35 36 15 LOAD HotSwap MBP module operation 1. Connect the input 36 on the HotSwap MBP module to the AC-power source. 2. Connect the UPS input cable 1 to the "UPS
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 29
    Chapter 4 Communication 4.1 Communication Ports The RS232 and USB communication ports cannot operate simultaneously. 1. Connect the RS232 17 or USB 18 18 communication cable to the serial or USB port on the com- puter equipment. 2. Connect the other end of the 17 communication cable 17 or
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 30
    UPS Remote Control Functions 4.2 UPS Remote Control Functions Programmable Signal Inputs The 9PX incorporates 3 programmable signal inputs: one Remote Power Off (RPO) input terminal, one Remote On/Off (ROO) input terminal, one RS-232 input (pin-4). Signal inputs can be configured see Settings > Com
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 31
    UPS Remote Control Functions RPO connections: RPO Connector type External breaker specification Comments Terminal, 14 AWG maximum wires 60 V DC/30V AC 20mA max ROO 11 RPO Remote On/Off (ROO) • Remote On/Off allows remote action of button to switch On/Off the UPS. • When contact changes from open
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 32
    UPS Remote Control Functions 6. Activate the external remote shut down contact to test the function. Always test the RPO function before applying your critical load to avoid accidental load loss. Programmable Signal Outputs The 9PX incorporates 4 programmable signal outputs: one relay output, three
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 33
    UPS Remote Control Functions low, UPS alarm/OK, or on Bypass. Figure 9. Connectivity Card Options 100/1Gb ACT AUX RESTART BOOT SETTINGS NETWORK-M2 Card RS232/Relay contacts Relay-MS Card NETWORK-M2 NETWORK-M2 100/1Gb ACT AUX 0V T+ T- R+ R- RESTART BOOT SETTINGS INDGW-M2 Eaton
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 34
    UPS Remote Control Functions 28 Eaton 9PX Lithium-Ion P-164001006-Rev 01
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 35
    or notices besides the "Battery mode" notice and notices that indicate missing utility power. Resolve any active alarms before continuing. See the "Troubleshooting" section . Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary. 5.3 UPS
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 36
    Return of AC Power Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack environment. See section 2.7 User Settings . Battery Mode When the UPS is operating during a power outage, the alarm beeps once every ten seconds and the indicator illuminates solid. The
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 37
    Configuring Bypass Settings Eaton recommends to use the HE mode only to protect IT equipment. To set the High Efficiency mode: 1. Select Settings, In/Out settings, and High Efficiency mode. 2. Select Enabled and Enter to confirm. 3. The UPS transfers to High Efficiency mode after 5 minutes. 5.7
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 38
    Retrieving the Event Log 5.9 Retrieving the Event Log To retrieve the Event log through the display: 1. Press any button to activate the menu options, then select Event log. 2. Scroll through the listed events. 5.10 Retrieving the Fault Log To retrieve the Fault log through the display: 1. Press any
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 39
    date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use them. Contact your service representative. 6.2 Replacing Batteries ! IMPORTANT DO NOT DISCONNECT the batteries while the UPS is in Battery mode. Batteries can be replaced easily without
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 40
    . 6. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable surface. Use two hands to support the battery pack. See "Recycling the used equipment" on page 38 for proper disposal. 7. Verify that the replacement batteries have the same rating as the
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 41
    Equipped with a HotSwap MBP 1 238 4 5 6 9 11 10 7 28 MBP-120 29 LOAD 33 34 35 36 15 The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. Maintenance 1. Set switch 33 to Bypass position. The red LED on the HotSwap MBP module
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 42
    Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important Recycling The Uinsfoermd aEtiqoun:ipment Special Symbols RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of The following aerleecetrxicamshpolcekssoyfmsbyoml. bols
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 43
    Troubleshooting 7.1 Typical Alarms and Faults The Eaton 9PX are designed for durable, automatic operation and also alert you whenever potential operating problems are properly connected. If the condition persists, contact your service representative. The battery test is failed due to bad or
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 44
    the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. 7.3 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or your local service representative and ask for a UPS technical representative. Please have the following
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 45
    CE Compliance Contact If repair is required, you will be given a Returned Material Authorization (RMA) number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 46
    CE Compliance Contact 40 Eaton 9PX Lithium-Ion P-164001006-Rev 01
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 47
    Chapter 8 Specifications 8.1 Model Specifications Input Filter Bypass AC/DC Boost DC/AC Inverter DC/DC Outpout Filter Charger Battery Table 7. Power Module List Model 9PX1500RT-L 9PX2000RT-L 9PX3000RT-L 9PX1500GRT-L 9PX2200GRT-L 9PX3000GRT-L Power ratings 1500VA / 1350W 2000VA / 1800W
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 48
    Model Specifications Table 9. Weights and Dimensions (Continued) Model Dimensions D x W x H(inch/mm) 9PXEBM48RT-L 17.6 x 17.2 x 1.7 / 448 x 438 x 42.9 9PXEBM72RT-L 23.7 x 17.2 x 1.7 / 603 x 438 x 42.9 Weight (lb / kg) 36.5 / 16.6 46.6 / 21.2 Table 10. Electrical Input Model Default Input
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 49
    Model Specifications Table 12. Electrical Output (Continued) All Models Normal Mode Efficiency Mode Battery Mode Frequency Regulation Sync with line ±5% of nominal line frequency (outside this range: ±0.5% of auto-selected nominal frequency) ±0.5% of auto-selected nominal frequency Nominal
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 50
    Model Specifications Table 13. Electrical Output Connections (Continued) Model Output Connection 9PX2200GRT-L 9PX3000GRT-L (4) IEC10A + (1) IEC16A (2) IEC10A + (1) IEC16A group 1 (2) IEC10A group 2 Output Cable (2) IEC 10A Table 14. Environmental and Safety Certifications EMC ( Emissions)*
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 51
    EBM 1500VA: 48Vdc 2200VA: 72Vdc 3000VA: 72Vdc 9PXEBM48RT: 48Vdc 9PXEBM72RT: 72Vdc Lithium Iron Phosphate (LFP) battery module Lithium-Ion float service life 8 years /25°C Integrated battery management system (BMS) for temperature regulation and life cycle monitoring. 350 mm / 13.78 in
  • Tripp Lite 9PX1500RTL | Eaton 9PX Lithium-Ion Owners Manual - Page 52
    P-16400100601 P-164001006 01
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

p/n:P-164001006
Revision01
Eaton9PXLithium-IonAdvancedUsersGuide
9PX1500RT-L/9PX2200RT-L/9PX3000RT-L/9PX1500GRT-L/
9PX2200GRT-L/9PX3000GRT-L/9PXEBM48RT-L/
9PXEBM72RT-L
Eaton9PXLithium-Ion