- Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 1
Eaton 9PXM UPS Eaton 9PXM UPS 4-20kVA Users Guide p/n: P-164000669 Revision 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 2
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this . All other trademarks are property of their respective companies. ©Copyright 2020 Eaton, Raleigh, NC, USA. All rights reserved. No part of this - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 3
. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions. This symbol indicates that you should information for this product, please review the latest manual revision on our website, Eaton.com/9PXM . - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 4
- Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 5
No Break Transfer from UPS Mode to Service Mode 29 3.8 Lock-out/Tag-out ...30 3.9 No Break Transfer from Service Bypass to UPS Mode 31 4 Without an External Bypass Switch 61 6.3 Startup for Units Installed with an Eaton BPM Bypass Switch 62 6.4 Startup for Units installed with a BPE Type - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 6
Bypass Switch (Make Before Break Only) Operation 93 9.4 Battery Replacement...94 9.5 Power Module Replacement...95 9.6 UPS Firmware Upgrade ...96 10 Specifications ...97 vi 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 7
and Dimensions...99 10.8 Output Receptacles...100 10.9 Receptacle Circuit Breaker Ratings ...101 11 Troubleshooting...103 11.1 Troubleshooting...103 11.2 Service and Support ...106 11.3 Two-Year Limited Warranty...106 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 vii - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 8
Table of Contents viii 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 9
Switch Positions...28 Bypass From UPS to LINE...30 Bypass From LINE to SERVICE ...30 LOTO Feature ...31 From SERVICE to LINE...32 From LINE to UPS ...32 Typical Installation without a Bypass Emergency Disconnect Switch 46 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 ix - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 10
Communication Port...88 Normally Open Connections ...89 EPO Normally Closed Connections 89 Battery Replacement ...94 Power Module Replacement ...95 Compatible Output Receptacles ...100 x 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 11
Breaker Sizes ...98 Environmental and Safety...98 Battery Ratings ...99 Weights and Dimensions ...99 Receptacle Circuit Breaker Ratings 101 Typicial Alarm Conditions ...103 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 xi - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 12
List of Tables xii 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 13
senses problems in power serviceability. 1.2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS This manual contains important instructions Battery modules to be used in the Eaton 9PXM system are model P-103002954. Each Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 1 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 14
CES INSTRUCTIONS Ce manuel comporte des instructions importantes que de batterie à utiliser dans le système Eaton 9PXM correspondent au modèle P-103002954. Chaque en funcionamiento el equipo y guarde este manual para referencia en el futuro. • Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 15
Physical Features 1.3 Physical Features The Eaton 9PXM UPS is available in eight or twelve-slot cabinet allow for remote monitoring of UPS operation. Slots for output receptacles installed by Eaton are available by removable knockout panels depending on the user's requirements (see Figure 2 . - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 16
covers. Battery slots consist of two battery modules each and can be used in both the right or left hand slots. (see Figure 3. 4 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 17
(Qty 2 battery modules) in the main UPS chassis for every power module present or the UPS will sound a "Not Enough Battery" alarm indication. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 5 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 18
every power module present or the UPS will sound an "Not Enough Battery" alarm indication. Figure 5. Uninterruptible Power Module Super Charger Modules (Optional) 6 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 19
6. UPS Control Panel Indicator Lights LCD Screen OnOlinnleinmeomdeode 1010%0% 2.27.k7WkW 3.30.k0VkAVA 110000%% 1199mmiinn 11EEBBMM EEffffiiccieiennccy:y9: 494%% Power/Navigation Buttons 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 7 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 20
Physical Features 8 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 21
Eaton Service Clearance If flexible conduit connects the UPS to the service input and load distribution panels, you may be able to gain access for servicing Eaton Eaton 9PXM UPS. If the batteries will be farther from the cabinet than the standard cables allow, contact your service up instructions. Do - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 22
the leveling feet by turning them clockwise then carefully roll the cabinet down the ramp to its intended operating location ( See Figure 8) . 10 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 23
the anchor brackets to the floor. See or 4.2 UPS Electrical Installation . The Eaton 9PXM UPS cabinet is shipped with four anchor (stabilizer) brackets (Kit P-157002300). base itself. To install the stabilizer brackets: 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 11 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 24
power and battery modules and before making connections to the intended power source. The Eaton 9PXM UPS and the battery cabinet are very heavy with power modules and two battery slot (see "9.1 Routine Maintenance " ). 12 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 25
and washers (see Figure 11 ). Figure 11. Rack Tray Location UPS Rack Rails (Front) UPS Rack Rails Screw Washer Rail Backs Rail Tray 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 13 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 26
Tray Rack Mount Ears 6. If you are installing an optional EBM cabinet refer to, "5.2 Standard Battery Cabinet Installation" or " 5.1 Battery Cabinet Options". 14 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 27
shock. Only qualified service personnel (such as a licensed electrician) should perform the electrical installation in this section. NOTE For installation and configuration of the Eaton bypass switch refer to the manual "Eaton Bypass Power Module (BPM) User's Guide P-164000628" supplied with - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 28
expandability, it is recommended that initial installation of the Eaton 9PXM UPS contains wiring to support the maximum capacity of the UPS cabinet of 20kVA for conduit, or long service runs. Follow local code requirements. 16 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 29
Eaton bypass switch refer to the manual "Eaton Bypass Power Module (BPM) User's Guide P-164000628" supplied with the switch or on the Eaton website input service panel. To install the UPS with an external bypass switch: 1. Mount the bypass switch within sight of the UPS. If you do not have an Eaton - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 30
220, 120/120 for 240, 120/120 for 208, or 127/127 for 220 Vac, as selected through the front panel display. 18 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 31
terminal covers must be installed on the back of the UPS prior to any battery or power modules being inserted into the UPS. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 19 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 32
the BPM terminal blocks. Tighten all connections as specified in . Use copper wire that is the appropriate size for the current draw. 20 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 33
Terminal Block UPS Connections 9. After installing bypass switch wiring, torque the screws holding all input and output power conductors to the values specified. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 21 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 34
Signal Terminals BYPASS NEUTRAL (black wire) BYPASS NEUTRAL (black wire) (Install conduit over signal wires) ON UPS (white wire) UPS Signal Terminals 22 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 35
Connector Force Bypass Common On UPS 43 2 1 43 2 1 3 2 1 43 2 1 7 6 5 43 2 1 FORCED BYPASS IN (red wire) BYPASS NEUTRAL (black wire) ON UPS (white wire) 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 23 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 36
installation is complete and power available. c. Navigate the 9PXM LCD to the forced and maintain bypass settings Input signals menu in the 9PXM user guide (see Figure 23 ). d. Set both Forced Bypass and Maintain Bypass settings to Enabled and Normally open (see Figure 23 ). Figure 23. Forced and - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 37
" for installation and service clearances before installing the " for installation instructions. UPS output Eaton-supplied power cables between the UPS and EBM(s) (PN:P-103003231). CN3 and CN4 CAN cables ground separately to each cabinet chassis. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 38
4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 26 WHITE WIRE COMBINE BLACK WIRES RED WIRE 1 3 2 3 EXTERNAL BPM AUX NO NO (Maintenance Bypass) CONTACT CONTACT 2 UPS INPUT SIGNALS Force Bypass - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 39
27 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 Legacy Bypass 9PXM Compatibility 1. (4) UPS's (9PXMSPPM) split-phase power modules or less installed in a 9PXM UPS*. 2. (3) UPS's (9PXMSPPM) split-phase power modules - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 40
operating on battery power. • If you have any questions or problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). The BPM consists of a load position handle and a described in Table 3 . 28 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 41
UPS Service Description When for troubleshooting, obtaining SERVICE position connects the load directly to AC input power and disconnects UPS output; however, because SERVICE problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). To turn the BPM to SERVICE - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 42
UPS 2. Turn the switch from LINE to SERVICE (see Figure 28 ). The critical load . Bypass From LINE to SERVICE Rotate switch to SERVICE position SERVICE MODE UTILITY INPUT OUTPUT LOAD to keep the BPM bypass switch locked in SERVICE mode while qualified service personnel works on the UPS. To use the - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 43
power. • If you have any questions or problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). To turn the BPM to UPS Mode: 1. Turn the switch from SERVICE to LINE (see Figure 30 ). 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 31 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 44
UPS through the front LCD menu to ensure the UPS is prepared for use. Figure 30. From SERVICE to LINE Rotate switch to LINE position 2. To transition the UPS from LINE to UPS, press uninterrupted power to the critical load. 32 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 45
must be in Normal Mode to provide battery backup power. If you have any questions or problems with the bypass operation, call the Help Desk at one of the telephone numbers in 11.2 Service and Support and ask for a UPS technical representative. • Press the button on the front panel display. The main - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 46
No Break Transfer from Service Bypass to UPS Mode 34 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 47
UPS Input Current Ratings Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) should perform the electrical . Figure 32. Typical Installation without a Bypass Switch Building Service Panel Load Distribution Panel User-Supplied External Battery (if required - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 48
system expendability, it is recommended that initial installation of the Eaton 9PXM UPS contains wiring to support the maximum capacity of the UPS cabinet : 20kVA for , or long service runs. Follow local code requirements. 36 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 49
equipment, verify that the Eaton 9PXM UPS is OFF before you remove the terminal covers. The circuit breaker or disconnect switch must also be OFF at the AC input service panel. To install the Input Terminals Terminal Cover 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 37 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 50
Modules Split-Phase Power Modules (3-wire plus ground input) (2 PEN) 110/220, 120/208, 120/240, 127/220 Vac GND L2 L1 N 38 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 51
by screwing down the lug screws. 4. Route and connect the AC input cables to the building service panel and the AC output cables to the load distribution panel as shown in Figure 36 . 74 " from signal terminal identification. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 39 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 52
electrical shock. Only qualified service personnel (such as a for Installation " for installation and service clearances before installing the UPS. Cabinet Options " for installation instructions. NOTE 6 UPS output electrical circuits. NOTE 7 Use only Eaton-supplied power cables between the UPS and - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 53
41 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 Figure 35. Wiring Diagram - UPS with No External Bypass (L1, L2, N) 1 2 UPS NO AUX NO AUX NC INPUT FROM FACILITY UPS INPUT - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 54
System Wiring Diagram 42 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 55
for extended runtime battery support only. There is no SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 56
section. 1. Open the carton containing the external battery cabinet cable assembly and position it in the desired location next to the UPS. 44 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 57
Screws Cover Terminal Block DC input cables from upstream EBM (if installed) DC+ DC- DC- DC+ To UPS UPS/EBM Terminal Block UPS 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 45 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 58
external bypass switch to the SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 46 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 59
this section. 1. Open the carton containing the external battery cabinet cable assembly and position it in the desired location next to the UPS. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 47 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 60
Lug DC input cables from upstream EBM (if installed) DC+ DC- DC- DC+ To UPS G L1 N L2 Screws Terminal Block N L1 G L2 48 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 61
external bypass switch to the SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 49 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 62
terminal covers are shipped in the UPS and EBM accessory kit and do not come installed on the UPS or EBM chassis. 50 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 63
to be connected to the first, in a daisy-chain configuration, connect each EBM with the DC cables supplied in the EBM accessory kit. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 51 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 64
OUT to close the switch and reconnect DC power. Turn the key back counter-clockwise, and remove the key (see Figure 47 ). 52 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 65
connected Eaton 9PXM split is also supported with this SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 66
terminal covers are shipped in the UPS and EBM accessory kit and do not come installed on the UPS or EBM chassis. 54 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 67
to be connected to the first, in a daisy-chain configuration, connect each EBM with the DC cables supplied in the EBM accessory kit. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 55 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 68
OUT to close the switch and reconnect DC power. Turn the key back counter-clockwise, and remove the key (see Figure 52 ). 56 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 69
Connected Battery Cabinet With Split Phase Input Figure 52. EBM Emergency Disconnect Switch EBM Disconnect Switch 13. Proceed to Chapter 6.1 UPS Startup . 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 57 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 70
Connected Battery Cabinet With Split Phase Input 58 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 71
power modules and battery modules is the reverse of these procedures. Install the UPMs into the Eaton 9PXM cabinet: as follows: 1. Remove the front cover(s) of the cabinet. The covers screw with a Phillips screwdriver. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 59 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 72
EBM. See Figure 54 . Figure 54. EBM Battery Modules and Charger Battery Modules Battery Modules Super Charger EBM Front View (Covers removed) 60 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 73
Bypass Switch, 6.3 Startup for Units Installed with an Eaton BPM Bypass Switch or 6.4 Startup for Units installed with UPS, apply input power to the UPS by closing the service circuit breaker: • If external battery cabinets are installed, Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 61 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 74
an Eaton circuit breaker in the load service panel or verify that the few volts, check the terminal block connections and correct any wiring problems. AC Line Input L1 to L2 (7 to 8*) N to more than 20 Vac; if they are, call your service representative. Terminal 3 (AC From UPS Output) To Terminal - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 75
screws. 13. If the UPS will not be operated immediately, switch the bypass switch to SERVICE and push in the DC emergency disconnect switch button on the back panel of the external battery and turn the switch to UPS. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 63 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 76
check the terminal block connections and correct any wiring problems. AC Line input Measurement AC from UPS Output if they are, call your service representative. Terminal 7 to 11 if it is, call your service representative. Terminal 6 to 10 10 the bypass switch to SERVICE and push in the DC - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 77
apply input power to the UPS by closing the service circuit breaker: l If external battery cabinets are . To set these initial configuration parameters: 1. After the Eaton® logo screen appears, select the desired language for the display Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 65 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 78
100% 10.1kW 10.1kV 100% 19min 24 Efficiency: 94% 7. If you have a "Standard" Eaton 9PXM battery cabinet or a "Connected" No AC battery cabinet option installed navigate to the battery settings menu and UPS. See Figure 56 . 66 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 79
, "11.1 Troubleshooting ". If the SERVICE (if installed). Remove DC power by pressing the DC disconnect switch on the back of the EBM(s) and removing all battery modules from the UPS cabinet. 7.4 Operating Modes 7.4.1 Online Mode The Eaton Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 67 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 80
to bypass occur within one hour. The UPS transfers to Bypass mode when: • User or Service activates Bypass mode through the front panel LCD or by using an external bypass switch (BPM or fault • Over Temperature on heatsinks 68 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 81
Fault" you can select the interruption time when transferring to bypass, default setting is "Half Cycle" but can be changed to "Full cycle". 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 69 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 82
Setting The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in Ah. 7.7.5 Deep Discharge Protection This setting is recommended UPS function and control settings. 70 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 83
). Indicator Green Status On On Description The UPS is operating normally on Online or High Efficiency mode. The UPS is on Battery mode 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 71 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 84
group information 7.13 Display Status Indicators The following table describes the status information provided by the UPS If another indicator not shown appears, see, "11.1 Troubleshooting " for additional information. 72 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 85
to select an option (see Figure 60 ). 7.15 Display Menu Screens Start Screen The start screen shows the required information at first startup. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 73 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 86
Date / Time Format : International 23/05/2020 15 :05 Please register at: www.eaton.com Type Eaton...9PXM Status Screen The status screen shows the status of the installed units. Figure 60. Identification Register Product 74 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 87
119V 119V Efficiency - - % Battery 96% 999min ABM Charging 138v Average Power Usage 0Wh Cumulat. power usage 0kWh Since: 01/01/2000 00.00 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 75 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 88
set Reset average power Reset Cumul.power Control GReosteot bcyupmausls. power Start baArtteeryyoutesut re? Reset faYueltsstateNo Restore factory set Reset average power 76 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 89
Menus, status, notices and alarms, UPS fault, Event Log data and settings are in all supported languages. Format: [International] [US] Set Time to International format Drop down menu to select format if an alarm occurs. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 77 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 90
max limit 12 % Default disables transfer to Bypass if the measured bypass voltage level is above the nominal output voltage plus 12% 78 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 91
Enabled, UPS will shut-down after de ned duration. of back-up time, if load is less than set value Default: Disabled [200W] 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 79 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 92
battery Manual batt. set. 0 AH Deep. Disch.Protect. Warranty void if no No Yes √ [Yes] [No] If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of back-up time voltage threshold. Warranty void if set to No. Default Value: [Yes] 80 4-20kVA Users Guide - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 93
Open [Enabled] [Disabled] [Normally open] Force Bypass Disabled Normally Open [Enabled] [Disabled] [Normally open] Maintain Bypass Disabled Normally Open [Enabled] [Disabled] [Normally open] 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 81 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 94
bAarteteryyoutessutre? RReessetotrfeaYufealtcsstotaryteNsoet Minislot 1 reset Comm Settings GMointoisblyoptas2s reset Start bAarteteryyoutessutre? RReessetotrfeaYufealtcsstotaryteNsoet Minislot 2 reset [Yes] [No] [Yes] [No] 82 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 95
Log Identification Register Product Fault Log Fault list Reset fault list Fault Log Fault list Reset fault list Fault Log 09/26/20 Battery need service 09/26/20 09:28 Min inverter 09/26/2017 09:28:27 Fault: UPM2 Code: 0x607 1/3 Fault Log Re0s9e/2t6/f2a0ult list 09:28ArAeBMyoOu - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 96
IPv4 NA COM card IPv6 NA COM card MAC 00:00:00:00:00:00 Detected accessories Supercharger: No Maintenance bypass: No 84 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 97
The Register product screen provides directions to register the product with Eaton. Figure 73. Register Product Menu DaMteen/ uTime SEFevotertmnintagLtso: g FInatuelrt com MTMyp/DeD/YYYY US 02/0E5a/2t0o2n0..0.39:P05XM 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 85 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 98
Display Menu Screens 86 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 99
software, Eaton offers interface cable kits for connecting the Eaton 9PXM system to your computer system. The kit includes the cable, adapters, and instructions. 8.3 , goes to EBM CSB • DB-9 (RS-232) port • USB port 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 87 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 100
used. 8.4 Dedicated Input Signals Dedicated Input Signals Emergency Power-off (EPO):Connection to a facility Emergency Shutdown switch provides a method for emergency Eaton 9PXM system shutdown. EPO Connections In the 9PXM UPS, EPO can be configured either as Normally Open (NO) or Normally Closed - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 101
any other cicuits. Maintenance Bypass: The signal from an external bypass switch, to isolate the Eaton 9PXM system for maintenance purposes, tells the UPS to go into Internal Bypass mode. On Generator . See IN/Out setting. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 89 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 102
The jumper setting MUST be changed by a qualified service technician. When enabled, Pin 9 provides supply voltage for The Eaton Network Card-M2 allows an Eaton UPS to directly connect to the Ethernet network and the Internet, supporting real- Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 103
and Modbus Card MS The Eaton Network and MODBUS Card-MS traps, or any web browser. Relay Card-MS The Eaton Relay Card-MS enables automatic shutdown and network monitoring of adapter that provides the essential dry-contact interface between an Eaton UPS and any relay-connected computer as well as a - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 104
Communication Slots 92 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 105
if the UPS is operating on battery power. • If you have any questions or problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). See " 3.6 Bypass Overview " for additional information. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 93 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 106
replace the battery modules without disconnecting the load or damaging the batteries. NOTE The Eaton 9PXM UPS will operate with uncharged (or no) batteries, but will have limited Modules Retaining Bracket Captive Screw 94 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 107
Power Module Replacement 9.5 Power Module Replacement The Eaton 9PXM easy replace feature lets you replace a power module without disconnecting Figure 79. Power Module Replacement Front Covers Power Module Captive Screws 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 95 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 108
and information for this product, please review the latest manual revision on our website, https://www.eaton.com/9PXM FW upgrade program and instructions are located at the following web link: https://www.eaton.com/9PXM. 96 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 109
and Output This section provides the following specifications for the Eaton 9PXM models: • Nominal Electrical Input and Output • 120/208V or 240V Max Input Current/Phase 20 40 60 Output Current L- Input Service N* 16.67A/phase 25A 33.34A/phase 50A 50.01A/phase 75A Heat Dissipation - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 110
to output load factor, for 120V L to N current Output Current L- Input Service N* 66.68A/phase 100A 83.35A/phase 125A Heat Dissipation - Normal Mode clean and free of dust, corrosive chemicals, and other contaminants. The Eaton 9PXM UPS uses internal fans to circulate the air for cooling. The - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 111
.7 kg (125 lb) 74.8 kg (165 lb) With Caster Tray (lbs) 93.4 kg (206 lb) 73 kg (161 lb) 91.2 kg (201 lb) 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 99 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 112
output receptacles. Figure 80. Compatible Output Receptacles L14-30 C13 C19 IEC60309 332R6W L6-30 L5-30 5-20 L6-20 L5-20 100 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 113
-20 1 Pole 20 Amp 2 L5-30 1 Pole 30 Amp 2 L6-20 2 Pole 20 Amp 2 L6-30 2 Pole 30 Amp 2 Receptacle Circuit Breaker Ratings 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 101 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 114
Receptacle Circuit Breaker Ratings 102 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 115
11 Troubleshooting 11.1 Troubleshooting The Eaton 9PXM is designed for durable, automatic operation and also alert you whenever potential operating problems may occur condition persists, contact your service representative. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 103 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 116
Troubleshooting Table 14. Typicial Alarm Conditions (Continued) LED is On. Beep continuous. The UPS does not provide the expected backup time. The batteries need charging or service. Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 117
Troubleshooting and Faults" on page 107 to correct the problem. After the problem has been resolved, press the lower center button SERVICE or the LINE position. In these two positions, utility power flows directly to the load. In the SERVICE Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 105 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 118
64 and change the level of system redundancy. 11.2 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Eaton 9PXM Two-Year Limited Warranty Eaton 9PXM UPS Load Protection Guarantee 106 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 119
Two-Year Limited Warranty 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 107 - Tripp Lite 9PXM08AAXXX | Eaton 9PXM UPS 4-20kVA Users Guide - Page 120
P-16400066910 P-164000669 10
p/n: P-164000669
Revision 10
Eaton9PXMUPS
4–20kVA Users Guide