Tripp Lite 9PXM8S4KPD Eaton 9PXM Installation and User Manual
Tripp Lite 9PXM8S4KPD Manual
View all Tripp Lite 9PXM8S4KPD manuals
Add to My Manuals
Save this manual to your list of manuals |
Tripp Lite 9PXM8S4KPD manual content summary:
- Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 1
Eaton 9PXM UPS Eaton 9PXM UPS 4-20kVA Users Guide p/n: P-164000669 Revision 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 2
. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 3
the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions. This symbol indicates that you should not discard the product in the trash. This - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 4
- Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 5
...28 3.7 No Break Transfer from UPS Mode to Service Mode 29 3.8 Lock-out/Tag-out ...30 3.9 No Break Transfer from Service Bypass to UPS Mode 31 4 UPS Electrical Installation... 63 6.5 Initial Startup Parameters ...65 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 v - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 6
Bypass Switch (Make Before Break Only) Operation 93 9.4 Battery Replacement...94 9.5 Power Module Replacement...95 9.6 UPS Firmware Upgrade ...96 10 Specifications ...97 vi 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 7
and Dimensions...99 10.8 Output Receptacles...100 10.9 Receptacle Circuit Breaker Ratings ...101 11 Troubleshooting...103 11.1 Troubleshooting...103 11.2 Service and Support ...106 11.3 Two-Year Limited Warranty...106 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 vii - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 8
Table of Contents viii 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 9
Switch Positions...28 Bypass From UPS to LINE...30 Bypass From LINE to SERVICE ...30 LOTO Feature ...31 From SERVICE to LINE...32 From LINE to UPS ...32 Typical Installation without a Bypass Emergency Disconnect Switch 46 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 ix - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 10
Communication Port...88 Normally Open Connections ...89 EPO Normally Closed Connections 89 Battery Replacement ...94 Power Module Replacement ...95 Compatible Output Receptacles ...100 x 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 11
Breaker Sizes ...98 Environmental and Safety...98 Battery Ratings ...99 Weights and Dimensions ...99 Receptacle Circuit Breaker Ratings 101 Typicial Alarm Conditions ...103 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 xi - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 12
List of Tables xii 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 13
Power control circuitry in the cabinet senses problems in power modules, and automatically transfers serviceability. 1.2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS This manual contains important instructions Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 1 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 14
SÉCURITÉ IMPORTANTES - CONSERVER CES INSTRUCTIONS Ce manuel comporte des instructions importantes que vous êtes invité antes de poner en funcionamiento el equipo y guarde este manual para referencia en el futuro. • Los módulos de potencia Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 15
of UPS operation. Slots for output receptacles installed by Eaton are available by removable knockout panels depending on the user's requirements (see Figure 2 . 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 3 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 16
covers. Battery slots consist of two battery modules each and can be used in both the right or left hand slots. (see Figure 3. 4 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 17
(Qty 2 battery modules) in the main UPS chassis for every power module present or the UPS will sound a "Not Enough Battery" alarm indication. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 5 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 18
every power module present or the UPS will sound an "Not Enough Battery" alarm indication. Figure 5. Uninterruptible Power Module Super Charger Modules (Optional) 6 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 19
6. UPS Control Panel Indicator Lights LCD Screen OnOlinnleinmeomdeode 1010%0% 2.27.k7WkW 3.30.k0VkAVA 110000%% 1199mmiinn 11EEBBMM EEffffiiccieiennccy:y9: 494%% Power/Navigation Buttons 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 7 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 20
Physical Features 8 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 21
Service Clearance If flexible conduit connects the UPS to the service input and load distribution panels, you may be able to gain access for servicing standard cables allow, contact your service representative or your local distributor are shown in these set up instructions. Do NOT attempt to move - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 22
the leveling feet by turning them clockwise then carefully roll the cabinet down the ramp to its intended operating location ( See Figure 8) . 10 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 23
attached by screws to the floor (see Figure 9 ). The anchor brackets are attached to the cabinet base itself. To install the stabilizer brackets: 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 11 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 24
slot installed. If installed, before moving the cabinets, remove the power modules and battery two battery modules per slot (see "9.1 Routine Maintenance " ). 12 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 25
and washers (see Figure 11 ). Figure 11. Rack Tray Location UPS Rack Rails (Front) UPS Rack Rails Screw Washer Rail Backs Rail Tray 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 13 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 26
Tray Rack Mount Ears 6. If you are installing an optional EBM cabinet refer to, "5.2 Standard Battery Cabinet Installation" or " 5.1 Battery Cabinet Options". 14 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 27
configuration of the Eaton bypass switch refer to the manual "Eaton Bypass Power Module (BPM) User's Guide P-164000628" supplied with the switch or on the with a Bypass Switch Building Service Panel External Bypass Switch BPM Design Service Line UPS Service Line UPS Service Line UPS User-Supplied ( - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 28
it is recommended that initial installation of the Eaton 9PXM UPS contains wiring to support the maximum capacity of the UPS cabinet of 20kVA for 12-slot and the conduit, or long service runs. Follow local code requirements. 16 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 29
of the Eaton bypass switch refer to the manual "Eaton Bypass Power Module (BPM) User's Guide P-164000628" supplied with the switch or on The circuit breaker or disconnect switch must also be OFF at the AC input service panel. To install the UPS with an external bypass switch: 1. Mount the bypass - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 30
220, 120/120 for 240, 120/120 for 208, or 127/127 for 220 Vac, as selected through the front panel display. 18 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 31
terminal covers must be installed on the back of the UPS prior to any battery or power modules being inserted into the UPS. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 19 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 32
the BPM terminal blocks. Tighten all connections as specified in . Use copper wire that is the appropriate size for the current draw. 20 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 33
Terminal Block UPS Connections 9. After installing bypass switch wiring, torque the screws holding all input and output power conductors to the values specified. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 21 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 34
Signal Terminals BYPASS NEUTRAL (black wire) BYPASS NEUTRAL (black wire) (Install conduit over signal wires) ON UPS (white wire) UPS Signal Terminals 22 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 35
Connector Force Bypass Common On UPS 43 2 1 43 2 1 3 2 1 43 2 1 7 6 5 43 2 1 FORCED BYPASS IN (red wire) BYPASS NEUTRAL (black wire) ON UPS (white wire) 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 23 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 36
installation is complete and power available. c. Navigate the 9PXM LCD to the forced and maintain bypass settings Input signals menu in the 9PXM user guide (see Figure 23 ). d. Set both Forced Bypass and Maintain Bypass settings to Enabled and Normally open (see Figure 23 ). Figure 23. Forced and - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 37
See "2.1 Preparing for Installation " for installation and service clearances before installing the UPS. Use flexible conduit or 5.1 Battery Cabinet Options " for installation instructions. UPS output circuits shall be installed in dedicated Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 25 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 38
4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 26 WHITE WIRE COMBINE BLACK WIRES RED WIRE 1 3 2 3 EXTERNAL BPM AUX NO NO (Maintenance Bypass) CONTACT CONTACT 2 UPS INPUT SIGNALS Force Bypass - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 39
27 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 Legacy Bypass 9PXM Compatibility 1. (4) UPS's (9PXMSPPM) split-phase power modules or less installed in a 9PXM UPS*. 2. (3) UPS's (9PXMSPPM) split-phase power modules - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 40
operating on battery power. • If you have any questions or problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). The BPM consists of a load position handle and a described in Table 3 . 28 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 41
UPS Service Description When for troubleshooting, obtaining SERVICE position connects the load directly to AC input power and disconnects UPS output; however, because SERVICE problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). To turn the BPM to SERVICE - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 42
UPS 2. Turn the switch from LINE to SERVICE (see Figure 28 ). The critical load . Bypass From LINE to SERVICE Rotate switch to SERVICE position SERVICE MODE UTILITY INPUT OUTPUT LOAD to keep the BPM bypass switch locked in SERVICE mode while qualified service personnel works on the UPS. To use the - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 43
power. • If you have any questions or problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). To turn the BPM to UPS Mode: 1. Turn the switch from SERVICE to LINE (see Figure 30 ). 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 31 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 44
UPS through the front LCD menu to ensure the UPS is prepared for use. Figure 30. From SERVICE to LINE Rotate switch to LINE position 2. To transition the UPS from LINE to UPS, press uninterrupted power to the critical load. 32 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 45
. If you have any questions or problems with the bypass operation, call the Help Desk at one of the telephone numbers in 11.2 Service and Support and ask for a UPS technical representative 663 mm (6.8") Weight 17 kg (38 lb) 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 33 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 46
No Break Transfer from Service Bypass to UPS Mode 34 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 47
UPS Input Current Ratings Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) should perform the electrical . Figure 32. Typical Installation without a Bypass Switch Building Service Panel Load Distribution Panel User-Supplied External Battery (if required - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 48
recommended that initial installation of the Eaton 9PXM UPS contains wiring to support the maximum capacity of the UPS cabinet : 20kVA for 12-slot cabinets the conduit, or long service runs. Follow local code requirements. 36 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 49
terminal covers. The circuit breaker or disconnect switch must also be OFF at the AC input service panel. To install the UPS without an external bypass switch: 1. Install the AC terminal upper Input Terminals Terminal Cover 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 37 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 50
Modules Split-Phase Power Modules (3-wire plus ground input) (2 PEN) 110/220, 120/208, 120/240, 127/220 Vac GND L2 L1 N 38 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 51
by screwing down the lug screws. 4. Route and connect the AC input cables to the building service panel and the AC output cables to the load distribution panel as shown in Figure 36 . 74 " from signal terminal identification. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 39 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 52
See "2.1 Preparing for Installation " for installation and service clearances before installing the UPS. Use flexible conduit on or 5.1 Battery Cabinet Options " for installation instructions. NOTE 6 UPS output circuits shall be installed Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 53
41 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 Figure 35. Wiring Diagram - UPS with No External Bypass (L1, L2, N) 1 2 UPS NO AUX NO AUX NC INPUT FROM FACILITY UPS INPUT - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 54
System Wiring Diagram 42 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 55
for extended runtime battery support only. There is no SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 56
section. 1. Open the carton containing the external battery cabinet cable assembly and position it in the desired location next to the UPS. 44 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 57
Screws Cover Terminal Block DC input cables from upstream EBM (if installed) DC+ DC- DC- DC+ To UPS UPS/EBM Terminal Block UPS 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 45 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 58
external bypass switch to the SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 46 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 59
this section. 1. Open the carton containing the external battery cabinet cable assembly and position it in the desired location next to the UPS. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 47 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 60
Lug DC input cables from upstream EBM (if installed) DC+ DC- DC- DC+ To UPS G L1 N L2 Screws Terminal Block N L1 G L2 48 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 61
external bypass switch to the SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 49 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 62
terminal covers are shipped in the UPS and EBM accessory kit and do not come installed on the UPS or EBM chassis. 50 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 63
to be connected to the first, in a daisy-chain configuration, connect each EBM with the DC cables supplied in the EBM accessory kit. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 51 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 64
OUT to close the switch and reconnect DC power. Turn the key back counter-clockwise, and remove the key (see Figure 47 ). 52 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 65
supercharger is also supported with this installation SERVICE position. Observe all electrical safety precautions. • Remove all battery modules in the UPS cabinet and/or battery cabinet to ensure DC voltage is removed from the internal DC buses. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 66
terminal covers are shipped in the UPS and EBM accessory kit and do not come installed on the UPS or EBM chassis. 54 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 67
to be connected to the first, in a daisy-chain configuration, connect each EBM with the DC cables supplied in the EBM accessory kit. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 55 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 68
OUT to close the switch and reconnect DC power. Turn the key back counter-clockwise, and remove the key (see Figure 52 ). 56 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 69
Connected Battery Cabinet With Split Phase Input Figure 52. EBM Emergency Disconnect Switch EBM Disconnect Switch 13. Proceed to Chapter 6.1 UPS Startup . 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 57 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 70
Connected Battery Cabinet With Split Phase Input 58 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 71
of the slot. • Repeat the procedure with the upper battery module. • Install the retaining bracket and tighten the captive screw with a Phillips screwdriver. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 59 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 72
EBM. See Figure 54 . Figure 54. EBM Battery Modules and Charger Battery Modules Battery Modules Super Charger EBM Front View (Covers removed) 60 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 73
) 4. When starting the UPS, apply input power to the UPS by closing the service circuit breaker: • If external battery cabinets are installed, close the DC emergency disconnect switch load distribution circuit breaker(s). 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 61 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 74
main circuit breaker in the load service panel or verify that the load few volts, check the terminal block connections and correct any wiring problems. AC Line Input L1 to L2 (7 to 8*) N to more than 20 Vac; if they are, call your service representative. Terminal 3 (AC From UPS Output) To Terminal - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 75
screws. 13. If the UPS will not be operated immediately, switch the bypass switch to SERVICE and push in the DC emergency disconnect switch button on the back panel of the external battery and turn the switch to UPS. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 63 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 76
check the terminal block connections and correct any wiring problems. AC Line input Measurement AC from UPS Output if they are, call your service representative. Terminal 7 to 11 if it is, call your service representative. Terminal 6 to 10 10 the bypass switch to SERVICE and push in the DC - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 77
14. When starting the UPS, apply input power to the UPS by closing the service circuit breaker: l If external battery cabinets are installed, close the DC emergency disconnect the displayed value is correct, press the button. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 65 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 78
displays the normal On/Off function screen. Press the ON button on the display screen to start the UPS. See Figure 56 . 66 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 79
Resolve any active alarms before continuing. See , "11.1 Troubleshooting ". If the indicator is on, do not proceed until power by opening the building service circuit breaker or placing the bypass switch in SERVICE (if installed). Remove DC Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 67 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 80
to bypass occur within one hour. The UPS transfers to Bypass mode when: • User or Service activates Bypass mode through the front panel LCD or by using an external bypass switch (BPM or fault • Over Temperature on heatsinks 68 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 81
Fault" you can select the interruption time when transferring to bypass, default setting is "Half Cycle" but can be changed to "Full cycle". 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 69 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 82
Setting The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in Ah. 7.7.5 Deep Discharge Protection This setting is recommended UPS function and control settings. 70 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 83
). Indicator Green Status On On Description The UPS is operating normally on Online or High Efficiency mode. The UPS is on Battery mode 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 71 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 84
group information 7.13 Display Status Indicators The following table describes the status information provided by the UPS If another indicator not shown appears, see, "11.1 Troubleshooting " for additional information. 72 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 85
to select an option (see Figure 60 ). 7.15 Display Menu Screens Start Screen The start screen shows the required information at first startup. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 73 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 86
: The Menu screen is the main menu and shows the available sub-menus. Menu Measurements √ Control Settings Event Log Identification Register Product 74 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 87
119V 119V Efficiency - - % Battery 96% 999min ABM Charging 138v Average Power Usage 0Wh Cumulat. power usage 0kWh Since: 01/01/2000 00.00 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 75 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 88
set Reset average power Reset Cumul.power Control GReosteot bcyupmausls. power Start baArtteeryyoutesut re? Reset faYueltsstateNo Restore factory set Reset average power 76 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 89
Menus, status, notices and alarms, UPS fault, Event Log data and settings are in all supported languages. Format: [International] [US] Set Time to International format Drop down menu to select format if an alarm occurs. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 77 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 90
max limit 12 % Default disables transfer to Bypass if the measured bypass voltage level is above the nominal output voltage plus 12% 78 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 91
Enabled, UPS will shut-down after de ned duration. of back-up time, if load is less than set value Default: Disabled [200W] 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 79 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 92
battery Manual batt. set. 0 AH Deep. Disch.Protect. Warranty void if no No Yes √ [Yes] [No] If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of back-up time voltage threshold. Warranty void if set to No. Default Value: [Yes] 80 4-20kVA Users Guide - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 93
Open [Enabled] [Disabled] [Normally open] Force Bypass Disabled Normally Open [Enabled] [Disabled] [Normally open] Maintain Bypass Disabled Normally Open [Enabled] [Disabled] [Normally open] 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 81 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 94
bAarteteryyoutessutre? RReessetotrfeaYufealtcsstotaryteNsoet Minislot 1 reset Comm Settings GMointoisblyoptas2s reset Start bAarteteryyoutessutre? RReessetotrfeaYufealtcsstotaryteNsoet Minislot 2 reset [Yes] [No] [Yes] [No] 82 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 95
Log Identification Register Product Fault Log Fault list Reset fault list Fault Log Fault list Reset fault list Fault Log 09/26/20 Battery need service 09/26/20 09:28 Min inverter 09/26/2017 09:28:27 Fault: UPM2 Code: 0x607 1/3 Fault Log Re0s9e/2t6/f2a0ult list 09:28ArAeBMyoOu - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 96
IPv4 NA COM card IPv6 NA COM card MAC 00:00:00:00:00:00 Detected accessories Supercharger: No Maintenance bypass: No 84 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 97
nLaotgional Id2e3n/0t5if/i2c0a2ti0on15 :05 Register Product PleaseDarteeg/iTsitmeer at: Fwowrmw.aet a: ton.com MTMyp/DeD/YYYY US 02/0E5a/2t0o2n0..0.39:P05XM 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 85 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 98
Display Menu Screens 86 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 99
to your computer system. The kit includes the cable, adapters, and instructions. 8.3 Communication Ports Communication Ports UPS Communications Ports External communication ports are located • DB-9 (RS-232) port • USB port 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 87 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 100
as Normally Open (NO) or Normally Closed (NC) contacts. Connector CN7 on the rear panel of the UPS is used for EPO. 88 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 101
to Normal (double conversion) mode as long as High Efficiency is set as the default mode of UPS operation. See IN/Out setting. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 89 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 102
. The jumper setting MUST be changed by a qualified service technician. When enabled, Pin 9 provides supply voltage for directly connect to the Ethernet network and the Internet, supporting real-time monitoring and control of UPSs across the Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 103
relay-connected computer as well as a variety of industrial applications. The Relay Card-MS is compatible with all Eaton UPSs that have a Minislot. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 91 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 104
Communication Slots 92 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 105
system is designed to provide years of trouble-free operation. Its internal control system checks problems with the bypass operation, call the Help Desk (see , " 11.2 Service and Support " ). See " 3.6 Bypass Overview " for additional information. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 106
bracket and tighten the captive screw. 7. Replace the front cover. Figure 78. Battery Replacement Front Covers Battery Modules Retaining Bracket Captive Screw 94 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 107
. 5. Tighten the captive screws to the UPS cabinet. 6. Replace the front cover. Figure 79. Power Module Replacement Front Covers Power Module Captive Screws 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 95 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 108
! IMPORTANT To ensure you have the most up-to-date content and information for this product, please review the latest manual revision on our website, https://www.eaton.com/9PXM FW upgrade program and instructions are located at the following web link: https://www.eaton.com/9PXM. 96 4-20kVA Users - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 109
, 7200 Watts 120/208V or 240V (2 UPMs) 12KVA, 10800 Watts (3 UPMs) 120/208V or 240V Max Input Current/Phase 20 40 60 Output Current L- Input Service N* 16.67A/phase 25A 33.34A/phase 50A 50.01A/phase 75A Heat Dissipation - Normal Mode 850 BTU/hr 1700 BTU/hr 2500 BTU/hr - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 110
100 *Note: Relative to output load factor, for 120V L to N current Output Current L- Input Service N* 66.68A/phase 100A 83.35A/phase 125A Heat Dissipation - Normal Mode 3400 BTU/hr 4250 BTU container. Less than 67 dBA 98 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 111
.7 kg (125 lb) 74.8 kg (165 lb) With Caster Tray (lbs) 93.4 kg (206 lb) 73 kg (161 lb) 91.2 kg (201 lb) 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 99 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 112
output receptacles. Figure 80. Compatible Output Receptacles L14-30 C13 C19 IEC60309 332R6W L6-30 L5-30 5-20 L6-20 L5-20 100 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 113
-20 1 Pole 20 Amp 2 L5-30 1 Pole 30 Amp 2 L6-20 2 Pole 20 Amp 2 L6-30 2 Pole 30 Amp 2 Receptacle Circuit Breaker Ratings 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 101 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 114
Receptacle Circuit Breaker Ratings 102 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 115
11 Troubleshooting 11.1 Troubleshooting The Eaton 9PXM is designed for durable, automatic operation and also alert you whenever potential operating problems may occur condition persists, contact your service representative. 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 103 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 116
Troubleshooting Table 14. Typicial Alarm Conditions (Continued) LED is On. Beep continuous. The UPS does not provide the expected backup time. The batteries need charging or service. Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 117
Troubleshooting and Faults" on page 107 to correct the problem. After the problem has been resolved, press the lower center button SERVICE or the LINE position. In these two positions, utility power flows directly to the load. In the SERVICE Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 105 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 118
to menu in Figure 64 and change the level of system redundancy. 11.2 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one UPS Load Protection Guarantee 106 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 119
Two-Year Limited Warranty 4-20kVA Users Guide P-164000669 4-20kVA Users Guide P-164000669-Rev 10 107 - Tripp Lite 9PXM8S4KPD | Eaton 9PXM Installation and User Manual - Page 120
P-16400066910 P-164000669 10
p/n: P-164000669
Revision 10
Eaton9PXMUPS
4–20kVA Users Guide
Eaton 9PXM UPS