Copyright © 2018 EATON All rights reserved. 614-20623-00_EN 9SX 0-3 KVA AMER 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9SX2000 9SX2000G 9SX3000 9SX3000G 9SX3000GL 9SX3000HW 9SXEBM36 9SXEBM48 9SXEBM96 Installation and user manual - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 2
SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. The 9SX models that are covered in this manual are intended for installation in an environment within 0 to 40 °C, free of - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 3
within the system. It should be opened exclusively by qualified service personnel. • The system must be properly grounded. • The battery grounded supply circuit). Product safety • The UPS connection instructions and operation described in the manual must be followed in the indicated order. • CAUTION - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 4
SAFETY INSTRUCTIONS Special precautions • The unit is heavy: wear safety shoes and use lifter to contact your EATON representative. • All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS. • For potential safety issue - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 5
to replace batteries 30 6.4 Replacing batteries ...31 6.5 Recycling the used equipment 33 7. Troubleshooting 34 7.1 Typical alarms and faults 34 7.2 Silencing the alarm ...35 7.3 Service and support ...35 7.4 CE compliance contact 35 8. Specifications 36 8.1 Model specifications 36 9. Glossary - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 6
9SX, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products End of life EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 7
you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, • ABM® technology that uses advanced battery management to increase battery service life, optimize recharge time, and provide a warning before the end - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 8
2. Presentation 2.1 Standard installation Tower installation Description 9SX700 9SX1000 9SX1500 9SX2000 9SX3000 9SX3000HW 9SX1000G 9SX1500G 9SX2000G 9SX3000G 9SX3000GL 9SXEBM36V 9SXEBM48V 9SXEBM96V 2.2 Rear panels 9SX700 Weights (lb/kg) Dimensions (inch/mm) W x H x D 25.4 / 11.5 6.3 x 9.9 x 14.1 - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 9
9SX1000 9SX1000G 2. Presentation 1 Input AC power source 2 Slot for optional communication card 3 Relay output contact 4 Connector for Extended Battery Modules 5 Primary outlets 6 Group 1: programmable outlets 7 Group 2: programmable outlets 8 Connector for automatic recognition of an additional - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 10
automatic recognition of an additional battery module 9 RS232 communication port 10 USB communication port 11 RPO port (Remote Power Off) 12 Output AC 9SX3000G 9SX3000GL 9SX3000HW Page 10 614-20623-00 - 9SX 0-3 KVA AMER_EN - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 11
9SXEBM36 / 9SXEBM48 9SXEBM96 2. Presentation 13 Connector for Extended Battery Modules (to the UPS or to the other battery modules) 14 Connectors for automatic recognition of battery modules 2.3 Accessories Part number Network-MS / Network M2 Modbus-MS INDGW-M2 Relay-MS INDRELAY-MS EBMCBL36T - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 12
equipment; 2. Send a copy of the damage claim within 15 days to your service representative. Check the battery recharge date on the shipping carton label. If the only) 4 RS232 communication cable 5 USB communication cable 6 Safety instructions 7 Quick start Page 12 614-20623-00 - 9SX 0-3 KVA - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 13
3. Installation B - Installation If you ordered other UPS accessories, refer to specific user manuals to check the tower installation with the UPS. 1. Place the UPS on a flat, stable surface in its final location. 2. Always keep 150 mm of free - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 14
3. Installation D - UPS connection (Except 9SX3000HW) Check that the indications on the name plate located on the back of the UPS meets to the AC-power source and the true electrical - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 15
3. Installation E - UPS connection 9SX3000HW Check that the indications on the name plate located on the back of the UPS meets to the AC-power source and the true electrical - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 16
9SX EBM 2 Battery power cable, attached with battery detection cable 3 Quick start 4 EBM Installation manual. Discard the EBM user's guide if you are installing the EBM with a new UPS at the same time. Use the UPS user's guide to install both the UPS and the EBM. If you ordered other UPS accessories - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 17
The UPS is on Battery mode. On Orange On Red The UPS is on Bypass mode. The UPS has an active alarm or fault. See troubleshooting on page 34 for additional information. 614-20623-00 - 9SX 0-3 KVA AMER_EN Page 17 - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 18
and load group information The following table describes the status information provided by the UPS. Note: If other indicator appears, see troubleshooting on page 34 for additional information. Operation status Standby mode Cause Description The UPS is Off, waiting for start-up Equipment is - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 19
Commands the load segments Start battery test Connectivity test Starts a manual battery test Tests dry contact relay outputs and relay card contacts the first time. fault, Event Log data and settings are in all supported languages. Format: [International] [US] [US] LCD Local settings Modify - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 20
4. Interfaces and Communication In/Out settings On/Off settings Submenu Available settings Default settings Output voltage [200V] [208V] [220V] [230V] [240V] [230V] Output frequency Mode: [Normal] [Converter] [Marine] [Normal] Frequency can be changed in Frequency [Converter] mode In [ - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 21
only when percentage of battery charge is reached. Battery charge mode External battery [ABM® cycling] [Constant charge] [Auto detection] [Manual EBM set.] [Manual battery set.] [ABM® cycling] [Auto detection] Using standard EBM, UPS detects automatically the number of EBM connected Deep Disch - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 22
4. Interfaces and Communication Com settings Submenu Output signals Available settings Default settings [Relay] [DB9-1] [DB9-8] Sets events or fault that will actuate Output signal parameters through external contact connector or RS232 port [Relay]: [On bat] [Low bat] [Bat fault] [Relay] [ - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 23
4. Interfaces and Communication 4.5 Communication ports Connection of RS232 or USB communication port Independent Communication Bay Any connectivity card Any connectivity card USB Available Not in use Multiplexed RS-232 Not in use Available 1. Connect the RS232 17 or USB 18 communication - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 24
4. Interfaces and Communication 4.6 UPS remote control functions Programmable Signal Inputs The 9SX incorporates 2 programmable signal inputs: one RPO terminal input, one RS-232 input (pin-4). Signal inputs can be configured (see User settings > Com settings > Signal Input on page 21) to have one - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 25
4. Interfaces and Communication • Remote control connection and test 1. Check the UPS is shut down and the electrical supply network disconnected. 2. Remove RPO connector from the UPS by unfitting the screws. 3. Connect a normally closed volt-free contact between the two pins of connector. Contact - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 26
4. Interfaces and Communication Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices.The 9SX models have one available communication bay for the following connectivity cards: • Network-MS card - has SNMP and - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 27
display changes status to "UPS starting...". 5. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing. See "Troubleshooting" on page 34. If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front panel - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 28
5. Operation Low-battery warning • The indicator illuminates solid. • The audio alarm beeps every three seconds. The remaining battery power is low. Shut down all applications on the connected equipment because automatic UPS shutdown is imminent. End of battery backup time • LCD displays "End of - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 29
(0% by default). This threshold can be modified. External battery setting The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in Ah. Deep discharge protection This setting is recommended to avoid damaging the battery. Warranty is void if deep - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 30
recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use them. Contact your service representative. 6.3 When to replace batteries Eaton UPS batteries have an expected life span of 3-5 years. After 4 years of operation, the UPS will provide - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 31
Wear rubber gloves and boots. • When replacing batteries, replace with the same type and number of batteries or battery packs. Contact your service representative to order new batteries. • Proper disposal of batteries is required. Refer to your local codes for disposal requirements. • Never dispose - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 32
6. UPS maintenance • Replacing the internal battery - TOWER 0-3KVA The internal battery is heavy. Use caution when handling heavy batteries. To replace the battery pack: 1. Unlock the lugs on the upper part of the front panel. 2. Rotate the front face. 3. Remove the lower part of the front panel. A - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 33
8. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable surface. Use two hands to support the battery pack. See "Recycling the used equipment" on page 33 for proper disposal. 9. Verify that the replacement batteries have the same rating as the - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 34
7. Troubleshooting The Eaton 9SX are designed for durable, automatic operation and also alert you whenever potential operating problems may all batteries are properly connected. If the condition persists, contact your service representative. The battery test is failed due to bad or disconnected - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 35
7. Troubleshooting UPS overtemperature LED is On. 1 beep every 3 seconds. The UPS does not overriding the previous alarm silencing. 7.3 Service and support If you have any question or problem with the UPS, call your distributor, your local service representative or connect to: powerquality.eaton. - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 36
For power ratings 1000VA 1500VA 2000-3000VA Table 3. Weights and dimensions Catalog Number (UPS) Weights (lb/kg) 9SX700 9SX1000 9SX1500 9SX2000 9SX3000 9SX3000HW 9SX1000G 9SX1500G 9SX2000G 9SX3000G 9SX3000GL 25.4 / 11.5 32.6 / 14.8 40.8 / 18.5 73.4 / 33.3 73.6 / 33.4 73.9 / 33.5 25.4 / 11.5 32 - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 37
: 200-276V at ≤25% load: 140-276V Table 5. Electrical input connections Catalog Number 9SX700 Input connection NEMA 5-15P 9SX1000 9SX1500 9SX2000 9SX3000 9SX3000HW 9SX1000G NEMA 5-20P NEMA L5-30P Hardwired IEC C14-10A 9SX1500G 9SX2000G 9SX3000G 9SX3000GL IEC C14-10A IEC C20-16A IEC C20-16A - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 38
8. Specifications Table 6. Electrical output All models Voltage regulation Efficiency 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9SX2000 9SX2000G 9SX3000 9SX3000G Frequency regulation Nominal output Frequency Normal mode High Efficiency mode Battery mode ±2% ±3% 86% 93% 79,5% 87% 93% 82% - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 39
8. Specifications Table 7. Electrical output connection Catalog Number 9SX700 9SX1000 9SX1500 9SX2000 9SX3000 9SX3000HW 9SX1000G 9SX1500G 9SX2000G 9SX3000G 9SX3000GL Output connection (2) NEMA 5-15R (2) NEMA 5-15R Group1 (2) NEMA 5-15R Group2 (2) NEMA 5-20R + (1) NEMA L5-20R (2) NEMA 5-20R Group1 - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 40
36Vdc - 2 x 3 x 12V. 9Ah 48Vdc - 2 x 4 x 12V. 9Ah 96Vdc - 2 x 8 x 12V. 9Ah Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25 °C (77 °F). Lifetime is reduced above 25°C (77°F) Advanced monitoring for earlier failure detection and warning 400 mm / 15 - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 41
9. Glossary Frequency converter Low-battery warning Backup time Load HE mode Normal (double conversion) mode Normal AC source Relay contacts UPS Operating mode used to convert the AC-power frequency between the UPS input and output (50Hz -> 60Hz or 60Hz -> 50Hz). This is a battery-voltage level - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 42
Page 42 614-20623-00 - 9SX 0-3 KVA AMER_EN - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 43
614-20623-00 - 9SX 0-3 KVA AMER_EN Page 43 - Tripp Lite 9SX1500G | Owners Manual - 9SX700 9SX1000 9SX1000G 9SX1500 9SX1500G 9 - Page 44