Tripp Lite SMART2200RMXL2U Runtime Chart for UPS Model SMART2200RMXL2U

Tripp Lite SMART2200RMXL2U Manual

Tripp Lite SMART2200RMXL2U manual content summary:

  • 1

UPS
Battery Pack
BP Qty.
100W
200W
300W
400W
600W
800W
875W
960W
1200W
1400W
1600W
1750W
1850W
1920W
SMART2200RMXL2U
Internal batteries
0
149
74
47
33
20
14
13
12
8
6
5
4.9
4.6
4.5
SMART2200RMXL2U
1 BP48V24-2U
1
515
272
179
131
82
58
52
47
34
28
23
SMART2200RMXL2U
1 BP48V60RT3U
1
989
541
364
270
174
125
112
101
75
61
51
SMART2200RMXL2U
2 BP48V60RT3U
2
1827
1031
708
534
352
258
232
211
159
131
110
SMART2200RMXL2U
3 BP48V60RT3U
3
2613
1505
1047
797
532
394
356
324
247
204
173
SMART2200RMXL2U
4 BP48V60RT3U
4
3352
1964
1378
1056
711
531
481
438
336
279
238
SMART2200RMXL2U
5 BP48V60RT3U
5
4048
2406
1701
1310
889
667
605
553
426
355
304
SMART2200RMXL2U
6 BP48V60RT3U
6
4704
2833
2017
1559
1065
802
729
667
516
432
370
SMART2200RMXL2U
7 BP48V60RT3U
7
5323
3246
2324
1804
1238
936
852
780
605
508
436
SMART2200RMXL2U
8 BP48V60RT3U
8
5909
3644
2625
2045
1410
1069
974
893
695
584
502
SMART2200RMXL2U
9 BP48V60RT3U
9
6464
4030
2918
2281
1579
1201
1095
1005
784
660
568
SMART2200RMXL2U
10 BP48V60RT3U
10
6990
4403
3204
2512
1746
1332
1215
1116
872
735
634
All runtime values are in minutes.