Tripp Lite SMX2200XLRT2U Runtime Chart for UPS Model SMX2200XLRT2U

Tripp Lite SMX2200XLRT2U Manual

Tripp Lite SMX2200XLRT2U manual content summary:

  • 1

SMX2200XLRT2U Estimated Runtime
Load in Watts
UPS
Battery Pack
500W
600W
700W
800W
900W
1,000W
1,100W
1,200W
1,300W
1,400W
1,500W
1,600W
All runtime values are in minutes.
SMX2200XLRT2U
Internal Batteries
27
22
18
17
13
11
9.5
8.3
7.5
7.0
6.5
6.0
SMX2200XLRT2U
1 BP48V24-2U
109
88
73
62
53
46
41
36
32
29
27
25
SMX2200XLRT2U
1 BP48V60RT3U
219
179
150
129
111
97
85
76
69
63
57
53
SMX2200XLRT2U
2 BP48V60RT-3U
439
362
306
264
229
202
179
161
146
133
122
113
SMX2200XLRT2U
3 BP48V60RT-3U
658
546
465
403
351
311
278
250
228
208
192
177
SMX2200XLRT2U
4 BP48V60RT-3U
876
730
624
543
475
421
377
341
311
285
263
244
SMX2200XLRT2U
5 BP48V60RT-3U
1,091
912
781
682
598
531
477
432
394
362
335
311
SMX2200XLRT2U
6 BP48V60RT-3U
1,302
1,091
937
820
720
641
576
523
478
440
407
378
SMX2200XLRT2U
7 BP48V60RT-3U
1,510
1,269
1,092
957
841
750
675
614
561
517
479
445
SMX2200XLRT2U
8 BP48V60RT-3U
1,715
1,444
1,245
1,093
962
858
774
704
645
594
551
513
SMX2200XLRT2U
9 BP48V60RT-3U
1,917
1,617
1,396
1,227
1,082
966
872
794
728
672
623
580
SMX2200XLRT2U
10 BP48V60RT-3U
2,116
1,788
1,546
1,360
1,201
1,074
970
884
811
748
695
648