Tripp Lite SU1500RTXL2UA Runtime Chart for UPS Model SU1500RTXL2Ua

Tripp Lite SU1500RTXL2UA Manual

Tripp Lite SU1500RTXL2UA manual content summary:

  • 1

UPS
Battery Pack
BP Qty.
20W
40W
60W
80W
100W
200W
300W
400W
500W
600W
700W
800W
1000W
1200W
SU1500RTXL2Ua
Included Batteries
0
319
219
164
129
106
52
33
23
18
14
11
10
8
5
SU1500RTXL2Ua
BP48V24-2U
1
1321
946
731
593
497
265
174
127
99
80
66
56
42
34
SU1500RTXL2Ua
BP48V60RT3U
1
2349
1712
1341
1099
928
512
343
256
201
165
137
117
89
71
SU1500RTXL2Ua
BP48V60RT3U
2
4100
3059
2434
2017
1720
978
670
507
404
334
281
242
187
151
SU1500RTXL2Ua
BP48V60RT3U
3
5619
4270
3438
2874
2467
1431
992
757
608
506
428
370
289
235
SU1500RTXL2Ua
BP48V60RT3U
4
6948
5364
4364
3674
3171
1869
1307
1004
811
677
576
499
392
320
SU1500RTXL2Ua
BP48V60RT3U
5
8121
6358
5219
4423
3836
2292
1616
1247
1011
847
722
628
495
406
SU1500RTXL2Ua
BP48V60RT3U
6
9164
7264
6012
5125
4464
2702
1917
1485
1209
1016
868
756
598
492
SU1500RTXL2Ua
BP48V60RT3U
7
10097
8093
6749
5785
5060
3098
2211
1720
1403
1182
1012
883
701
578
SU1500RTXL2Ua
BP48V60RT3U
8
10937
8855
7436
6406
5624
3482
2498
1950
1595
1347
1155
1009
803
664
SU1500RTXL2Ua
BP48V60RT3U
9
11697
9558
8077
6991
6161
3854
2779
2176
1784
1509
1296
1134
904
749
SU1500RTXL2Ua
BP48V60RT3U
10
12388
10209
8678
7544
6671
4213
3054
2399
1971
1669
1436
1258
1005
834
All runtime values are in minutes.
Load in Watts