Tripp Lite SU2200RTXLCD2U Runtime Chart for UPS Model SU2200RTXLCD2U

Tripp Lite SU2200RTXLCD2U Manual

Tripp Lite SU2200RTXLCD2U manual content summary:

  • 1

UPS
Battery Pack
BP Qty.
300W
400W
500W
600W
700W
800W
1000W
1200W
1300W
1400W
1500W
1600W
1700W
1800W
SU2200RTXLCD2U
Included Batteries
0
44
31
24
19
16
13
10
7.6
6.8
6.1
5.5
5.0
4.5
4.0
SU2200RTXLCD2U
BP48V24-2U
1
170
124
96
78
65
55
42
33
30
27
25
23
21
19
SU2200RTXLCD2U
BP48V60RT3U
1
346
257
202
165
138
119
91
73
66
60
55
51
47
44
SU2200RTXLCD2U
BP48V60RT3U
2
674
509
405
335
284
245
191
154
140
128
118
109
101
95
SU2200RTXLCD2U
BP48V60RT3U
3
998
760
610
507
432
375
294
239
218
200
185
171
160
149
SU2200RTXLCD2U
BP48V60RT3U
4
1315
1007
813
678
581
506
399
326
298
274
254
236
220
206
SU2200RTXLCD2U
BP48V60RT3U
5
1625
1251
1013
849
728
636
504
413
379
349
323
301
281
263
SU2200RTXLCD2U
BP48V60RT3U
6
1928
1491
1211
1017
875
766
608
501
459
424
393
366
342
321
SU2200RTXLCD2U
BP48V60RT3U
7
2224
1726
1406
1184
1020
895
713
588
540
499
463
432
404
379
SU2200RTXLCD2U
BP48V60RT3U
8
2513
1957
1599
1348
1164
1022
817
675
621
574
533
497
466
438
SU2200RTXLCD2U
BP48V60RT3U
9
2795
2184
1788
1511
1306
1149
920
762
701
648
603
563
527
496
SU2200RTXLCD2U
BP48V60RT3U
10
3071
2407
1975
1672
1447
1274
1022
848
781
723
672
628
589
554
All runtime values are in minutes.
SU2200RTXLCD2U Estimated Runtime
Load in Watts